ILLINOIS POLLUTION CONTROL BOARD
    October 2, 1997
    DAVID and SUSI SHELTON,
    Complainants,
    v.
    STEVEN and NANCY CROWN,
    Respondents.
    )
    )
    )
    )
    )
    )
    )
    )
    )
    PCB 96-53
    (Enforcement - Noise)
    JEFFERY R. DIVER AND STEVEN KAISER OF THE JEFF DIVER GROUP APPEARED
    ON BEHALF OF COMPLAINANTS;
    RICHARD R. ELLEDGE AND ROBERT A. CARSON OF GOULD AND RATNER
    APPEARED ON BEHALF OF RESPONDENTS.
    OPINION AND ORDER OF THE BOARD (by G.T. Girard):
    On September 8, 1995, David and Susi Shelton (Sheltons or complainants) filed this
    citizen’s enforcement action (Comp.) concerning an air conditioner owned by Steven and Nancy
    Crown (Crowns or respondents) at the Crowns’ home located at 685 Ardsley Road, Winnetka,
    Cook County, Illinois. This action was filed pursuant to Section 31(b) of the Illinois
    Environmental Protection Act (Act) (415 ILCS 5/31(b) (1994). The Sheltons allege that noise
    from the air conditioner at the Crowns’ home has unreasonably interfered with the enjoyment of
    their lives and property, and, in addition, the air conditioner is in violation of Illinois numeric
    noise standards. The Sheltons claim that the Crowns have therefore violated Section 23 and 24
    of the Act (415 ILCS 5/23, 5/24 (1994)) and Board regulations at 35 Ill. Adm. Code 900.102,
    900.102(a), 900.102(b), and 901.104. The Sheltons request that the Board find that the Crowns
    violated the Act and Board regulations, and order a civil penalty pursuant to Section 42 of the
    Act (415 ILCS 5/42 (1994)).
    Hearings were held in this matter before Board Hearing Officer June Edvenson on July 1,
    July 2, July 12, July 16, July 20, July 21, August 19, and August 20, 1996. Complainants filed
    their post-hearing brief (Comp. Br.) on February 21, 1997. Respondents filed their post-hearing
    brief (Resp. Br.) and a motion to dismiss with prejudice (Mot. Dis.) on May 5, 1997. On May
    19, 1997, complainants filed their reply brief (Reply Br.) and Response to Motion to Dismiss
    (Res. Mot. Dis.). On June 2, 1997, respondents filed a “Motion to Strike” and an exhibit titled
    “Exhibit 1” to the reply brief. The Board denies the motion to strike. The Board also denies the
    motion to dismiss for the reasons discussed in a following section.
    For the reasons discussed below, the Board finds that there is sufficient proof that noise
    from the Crowns’ air conditioner unreasonably interfered with the Sheltons’ enjoyment of their
    lives and property during those times when the air conditioner was operating between September

    2
    15, 1993, and January 1996. The Board does not find that the air conditioner noise violated the
    Board’s numeric noise standards. The Board finds that no monetary penalty is warranted in this
    case.
    LEGAL FRAMEWORK
    The Sheltons allege that the Crowns have violated Sections 23 and 24 of the Act and the
    Board’s rules at 35 Ill. Adm. Code 900.102, 901.102(a), 901.102(b), and 901.104. Comp. at 2.
    These statutes and regulations prohibit noise pollution in Illinois which exceeds specified
    numeric limits or which produces nuisance noise. The Sheltons allege that noise from the
    Crowns’ air conditioner has violated numeric noise standards and created nuisance noise which
    has unreasonably interfered with the Sheltons’ lives and enjoyment of their property. See
    Ferndale Heights Utilities Co. v. Illinois Pollution Control Board, 44 Ill. App. 3d 967, 358
    N.E.2d 1224, 1228 (1st Dist. 1976).
    Noise violations are defined by Section 23 and 24 of the Act. With regard to nuisance
    noise, the prohibitions in the Act and Board regulations turn on the degree to which the noise
    interferes with a complainant’s normal activities. Section 23 of the Act states:
    The General Assembly finds that excessive noise endangers physical and
    emotional health and well-being, interferes with legitimate business and
    recreational activities, increases construction costs, depresses property values,
    offends the senses, creates public nuisances, and in other respects reduces the
    quality of our environment. It is the purpose of this Title to prevent noise which
    creates a public nuisance. 415 ILCS 5/23 (1996).
    Section 24 of the Act prohibits noise pollution stating:
    No person shall emit beyond the boundaries of his property any noise that
    unreasonably interferes with the enjoyment of life or with any lawful business or
    activity, so as to violate any regulation or standard adopted by the Board under
    this Act. 415 ILCS 5/24 (1996).
    Thus, under the Act, a noise violation has occurred if the complainant has proven that the
    activity violates any numeric regulation or standard adopted by the Board or if a nuisance noise
    has unreasonably interfered with the complainant’s enjoyment of life or with the pursuit of any
    lawful business or activity.
    In this proceeding, the Sheltons allege that noise emitted by the Crowns’ air conditioner
    violated Board regulations found at 35 Ill. Adm. Code 900.102, 901.102(a), 901.102(b), and
    901.104. The specific language of those Sections provides:
    Section 900.102 Prohibition of Noise Pollution
    No person shall cause or allow the emission of sound beyond the boundaries of
    his property, as property is defined in Section 25 of the Illinois Environmental

    3
    Protection Act, so as to cause noise pollution in Illinois, or so as to violate any
    provision of this Chapter.
    Section 901.102 Sound Emitted to Class A Land
    a)
    Except as elsewhere in this Part provided, no person shall cause or allow
    the emission of sound during daytime hours from any property-line-noise-
    source located on any Class A, B or C land to any receiving Class A land
    which exceeds any allowable octave band sound pressure level specified
    in the following table, when measured at any point within such receiving
    Class A land, provided, however, that no measurement of sound pressure
    levels shall be made less than 25 feet from such property-line-noise-
    source.
    Octave Allowable Octave Band Sound Pressure
    Band Levels (dB) of Sound Emitted to any
    Center Receiving Class A Land from
    Frequency
    Class C
    Class B
    Class A
    (Hertz) Land
    Land
    Land
    31.5
    75
    72
    72
    63
    74
    71
    71
    125
    69
    65
    65
    250
    64
    57
    57
    500
    58
    51
    51
    1000
    52
    45
    45
    2000
    47
    39
    39
    4000
    43
    34
    34
    8000
    40
    32
    32
    b)
    Except as elsewhere in this Part provided, no person shall cause or allow
    the emission of sound during nighttime hours from any property-line-
    noise-source located on any Class A, B or C land to any receiving Class A
    land which exceeds any allowable octave band sound pressure level
    specified in the following table, when measured at any point within such
    receiving Class A land, provided, however, that no measurement of sound
    pressure levels shall be made less than 25 feet from such property-line-
    noise-source.

    4
    Octave Allowable Octave Band Sound Pressure
    Band Levels (dB) of Sound Emitted to any
    Center Receiving Class A Land from
    Frequency
    Class C
    Class B
    Class A
    (Hertz) Land
    Land
    Land
    31.5
    69
    63
    63
    63
    67
    61
    61
    125
    62
    55
    55
    250
    54
    47
    47
    500
    47
    40
    40
    1000
    41
    35
    35
    2000
    36
    30
    30
    4000
    32
    25
    25
    8000
    32
    25
    25
    Section 901.104 Impulsive Sound
    Except as elsewhere in this Part provided, no person shall cause or allow the
    emission of impulsive sound from any property-line-noise-source located on any
    Class A, B or C land to any receiving Class A or B land which exceeds the
    allowable A-weighted sound levels specified in the following table, when
    measured at any point within such receiving Class A or B land, provided,
    however, that no measurement of sound levels shall be made less than 25 feet
    from such property-line-noise-source.
    Classification of
    Allowable A-weighted Sound Levels in
    Land on which
    Decibels of Impulsive Sound Emitted
    Property-Line-
    to Receiving Class A or B Land
    Noise-Source
    is Located
    Class A Land
    Class B Land
    Daytime
    Nighttime
    Class A Land
    50
    50
    45
    Class B Land
    57
    50
    45
    Class C Land
    61
    56
    46
    The Board has previously determined in nuisance noise proceedings that unreasonable
    interference is more than an ability to distinguish sounds attributable to a particular source.
    Rather, the sounds must objectively affect the complainant’s life or business activities. See
    Kvatsak v. St. Michael’s Lutheran Church, (Aug. 30, 1990) PCB 89-182, 114 PCB 765, 773
    (Kvatsak);
    Kochanski v. Hinsdale Golf Club, (July 13, 1989) PCB 88-16, 1001 PCB 11, 20-21,
    rev’d on other grounds
    , 197 Ill. App. 3d 634, 555 N.E.2d 31 (2d Dist. 1990).

    5
    In determining whether unreasonable interference has occurred under the Act and Board
    rules, the Illinois Supreme Court has directed that the Board must consider the facts of the case
    in light of the factors outlined in Section 33(c) of the Act. Wells Manufacturing Co. v. Pollution
    Control Board, 73 Ill. 2d 226, 232-33, 383 N.E.2d 148, 150-51 (1978), see also Ferndale Heights
    Utilities, 44 Ill. App. 3d at 967-68, 358 N.E.2d at 1228. Those factors as set forth in Section
    33(c) of the Act are as follows:
    (i)
    the character and degree of injury to, or interference with the protection
    of the health, general welfare and physical property of the people;
    (ii)
    the social and economic value of the pollution source;
    (iii)
    the suitability or unsuitability of the pollution source to the area in
    which it is located, including the question of priority of location in the
    area involved;
    (iv)
    the technical practicability and economic reasonableness of reducing or
    eliminating the emissions...resulting from such pollution source; and
    (v)
    any subsequent compliance. 415 ILCS 5/33(c) (1996).
    FACTS
    General Information
    The Sheltons and their three children moved into their home at 707 Ardsley Road,
    Winnetka, Illinois, in 1990. Tr. at 357, 395. In June 1991, the Crowns purchased the property at
    685 Ardsley Road, which lies immediately south of the Sheltons’ home. Tr. at 12, 1267. The
    Crowns’ nearest property line is approximately 28 feet from the nearest wall of the Sheltons’
    home. Tr. at 364. The neighborhood is quiet, with private streets and individual properties
    larger than one-half acre each. Tr. at 356-357.
    Prior to taking up residence, the Crowns extensively remodeled their home, which
    included removing the existing heating and air conditioning system in the structure. Tr. at 17.
    After remodeling, the finished structure enclosed approximately 18,000 square feet. Stip. No. 1.
    Remodeling began in fall of 1991. Tr. at 14, 366. The Crowns moved into their home in March
    1995. Tr. at 80.
    The Crowns’ new HVAC [heating, ventilation, air conditioning] system was designed
    and installed by Mid/Res, Inc. (Mid/Res), according to specifications established by the
    architect, Mr. Paul Constant. Tr. at 19. On February 12, 1992, Mid/Res provided Mr. Constant
    with an initial proposal for the Crowns’ HVAC system (Exh. 66; Exh. 69; Tr. at 322-323), and
    Mid/Res began installation in spring 1992. Tr. at 194. The HVAC system included a 25-ton
    exterior unit (chiller unit) manufactured by the Trane Corporation (Trane), Model RAUC 25.
    Ex. 73. Trane Model RAUC 25 is used primarily in commercial applications. Tr. at 181. This
    chiller unit consists of two compressors (one ten-ton and one fifteen ton), and three fans. Tr. at

    6
    17. A Trane Engineering Bulletin published in February 1993 warned that installing commercial
    size equipment near a residential lot line would be a misapplication that increased the likelihood
    of a noise problem. Exh. 43 at III. The Bulletin also warned against locating outdoor HVAC
    equipment in proximity to a sound reflective wall. Exh. 43 at III. The Crowns’ chiller unit was
    located in front of a two-story stone wall of the Crown residence and was about 60 feet from the
    nearest wall of the Shelton residence. Exh. 2, 51; Tr. at 794. The completed HVAC system for
    the Crown home cost approximately $300,000. Stip. No. 1.
    The chiller unit was first tested in September 1993. Tr. at 21, 366-368. When the unit
    was first turned on, the Sheltons called the local police because they thought the noise resembled
    an explosion. Tr. at 367. The Sheltons then called the Crowns who agreed to turn off the unit.
    Tr. at 368. During the next three years the Sheltons and the Crowns had numerous meetings and
    exchanged correspondence over the Sheltons’ objection to the noise level of the chiller unit. Tr.
    at 372, 373, 419, 421, 435, 438, 525-527, 792, 811, 815, 816, 822, 823, 826, 841, 842, 848, 853;
    Exh. 6, 17, 18(a)(b), 19, 21, 22, 40, 41, 43, 45 49, 90, 107.
    The Crowns determined that moving the chiller was not a feasible because major HVAC
    components were already installed. Tr. at 1201, 1320. Mid/Res, Inc. attempted to attenuate the
    noise in fall 1993 and spring 1994 by several methods. Tr. at 222; Exh. 32. Sheets of one-half
    inch thick acoustic material, Armaflex, were applied to the interior of the chiller casing in
    October 1993. Tr. at 218, 621, 628. The chiller was rotated 90 degrees so that the air intake
    pointed east, away from the Sheltons’ house, rather than north toward the Sheltons’ house. Tr. at
    1301; Resp. Br. at 8. Finally, metal “cones” were fabricated for installation over the chiller fans
    (Tr. at 1301, 1303), which Mid/Res considered at the time to be the major noise source. Tr. at
    225. In June 1994, the Crowns initiated 24-hour operation of the chiller unit to protect the
    millwork from humidity and dry out the plaster. Tr. at 79-80. The 24-hour a day operation
    continued through the summer of 1994. Tr. at 80. In June 1994, the Crowns also installed
    wooden fences and shrubbery between the Crown and Shelton properties to reduce the sound.
    Tr. at 398, 1395, 1401. Ms. Marjorie Julian, the Sheltons’ neighbor to the north testified that the
    chiller unit noise was not reduced by the fences and shrubbery. Tr. at 156-157.
    On January 5, 1995, Mr. Shelton wrote a letter to the Village of Winnetka (Winnetka)
    including a petition signed by neighbors who had visited the Sheltons’ home, asking Winnetka,
    pursuant to Winnetka noise ordinance, to order the Crowns to significantly reduce the noise from
    their chiller unit. Exh. 7. Mr. Williams, Winnetka Village Manager, convened a meeting of the
    parties on January 17, 1995. Tr. at 1352. At that meeting, plans to construct an acoustic
    enclosure were discussed. Exh. 35. The acoustic structure constructed by the spring of 1995
    was eight feet high, two feet higher than the chiller, and constructed of acoustic panels. Tr. at
    1131.
    The Crowns again activated the chiller unit in April 1995. Tr. 442, 498. The Sheltons’
    noise complaints continued through the spring and summer of 1995. Tr. at 443-447. Mr. Allen
    Shiner of Shiner and Associates, acoustical engineers, measured noise from the chiller unit on
    June 19, 1995. Exh. 60. He determined that the discharge cones did not mitigate the sound and
    they were removed. Tr. at 217-221; Exh. 60. After removal of the cones prior to the 1995
    cooling season (Tr. at 501), the Sheltons noticed “a very slight improvement in the sound.” Tr.

    7
    At 502. However, correspondence about the noise from the chiller unit was exchanged between
    the Sheltons and the Crowns during summer 1995, culminating in the Sheltons’ complaint filed
    before the Board in September 1995. The Sheltons relocated their family to Greenville, Ohio, in
    January 1996. Comp. Br. at 23. The Sheltons apparently sold their home in April or May 1997
    (May 5, 1997, affidavit of Arie Steven Crown).
    In July and August 1996, Mid/Res installed fan motor variable speed controls. Mid/Res
    modified the height and configuration of the chiller unit acoustic shield to include a roof over the
    chiller unit. Tr. at 1534-1535. On August 15, 1996, Shiner and Associates measured sound
    levels at the Shelton property line and residence and found that the modifications resulted in
    significantly reduced noise levels from the chiller unit. Exh. 125, 126, 127. The specific results
    of these final sound measurements are more fully described in the subsection below entitled
    “Sound measurements by George Kemperman.” Greg Zak, a noise expert with the Illinois
    Environmental Protection Agency (IEPA), testified that the final sound mitigation measures
    represented an “elegant solution” to the problem based on his visit to the Crown and Shelton
    properties on August 21, 1996. Tr. at 1477. Greg Zak further testified that based on his personal
    observation and review of the date available, the chiller unit operates in compliance with both
    the nighttime numeric noise standards at Section 901.102(b) and nuisance noise standards. Tr. at
    1477.
    Sound Monitoring Data
    Sound emanating from the Crown chiller unit was measured on seven different occasions
    between July 1994 and August 1996 by Allen Shiner (7-5-94 & 6-19-95), George Kemperman
    (5-2-96, 8-9-96 & 8-15-96), Greg Zak (6-27-96), and Robert Elfering (8-15-96). A brief
    summary of the sound monitoring data obtained on each of the seven monitoring events is
    presented below.
    Sound Measurements by Allen Shiner and Robert Elfering
    Shiner and Associates, acoustical engineers, were retained by both the complainants and
    the respondents to monitor sound levels in the vicinity of the Crown chiller unit. Shiner’s
    engineers measured sound levels on three occasions. On the first two occasions, Allen Shiner
    monitored sound levels emanating from the Crown chiller unit on behalf of the complainants.
    On July 5, 1994, Shiner measured the sound levels from the Shelton’s property within 20 feet of
    Shelton’s south property line. Shiner stated that the instrumentation was established in
    accordance with the Board regulations. Tr. at 293. Based on a comparison of the measured
    sound levels with the allowable octave band sound pressure levels specified under the numeric
    noise standards at 35 Ill. Adm. Code 901.102, Shiner concluded that the Crown chiller unit
    exceeded the allowable levels at all frequencies during the night hours of operation. Exh. 56.
    The sound levels from the Crown chiller unit were again measured by Shiner on June 19,
    1995, after installation of the acoustical housing. Exh. 60. The sound levels were measured
    under different operating conditions to assess the sound-reducing effectiveness of the discharge
    cones and the acoustical housing placed on the chiller unit. Again, Shiner testified that the
    measurements were made in accordance with applicable Board regulations. Tr. at. 302. Shiner

    8
    concluded that the sound levels exceeded the Board’s nighttime standards at all frequencies,
    except for the sound level at octave band center frequency of 250 Hz. Tr. at 318.
    On August 15, 1996, Robert Elfering, an engineer with Shiner and Associates, measured
    sound levels from the Crown chiller unit on behalf of the respondents. Exh. 124, 125. Elfering
    measured sound levels at five locations: near the fence (property line) between the Shelton and
    Crown residences; on the Shelton patio opposite the Shelton window air conditioner; near the
    fence, 50 feet north-east of the Crown chiller unit; on the roof of the enclosed porch; and on the
    edge of the Crown driveway, opposite the Crown chiller unit. The sound levels were measured
    at different operating conditions, which included: the Crown chiller unit operating in nighttime
    mode with the Shelton air conditioner switched on and off; the Crown chiller unit operating in
    day time mode at 60 Hz (fan at full speed) with Shelton air conditioner switched off; the Crown
    chiller unit operating in day time mode at 20 Hz (fan speed at 33% of full speed) with the
    Shelton air conditioner off; and with both Crown and Shelton air conditioners switched off to
    determine ambient noise conditions.
    Sound Measurements by Greg Zak
    Greg Zak, a noise technical expert with the IEPA, monitored sound levels on both
    Shelton and Crown properties on June 27, 1996 at around 9.30 p.m. The first location (site 1)
    was outside the second floor bedroom window of the Shelton residence. Exh. 92 at 3. The
    second location (site 2) was on the Crown property at a point approximately 30 feet north of the
    Crown chiller unit. See Attachment to Exh. 92. At the second location, Zak also measured the
    ambient sound, which are the background sound levels with the Crown chiller unit turned off.
    Tr. at 604. Zak stated that the measurements were made in accordance with the Board
    regulations. Tr. at 572. Zak described the acoustic properties of the area as a complex echoic
    field due to the parallel house walls and stockade fence. Tr. at 573-575.
    Sound Measurements by George Kemperman
    George Kemperman, a noise control engineer, was retained by respondent to evaluate the
    noise sources associated with the Crown chiller unit. Kemperman monitored the sound levels
    from the Crown chiller unit on three different occasions. On May 2, 1996, Kemperman recorded
    sound levels from the chiller unit as a part of his investigation of the noise source. Based on
    these measurements, he made recommendations for improving noise control that included two
    different modes of operation: normal operation, with two compressors and three fans operating
    at full speed; and nighttime operation with one compressor and one fan operating full speed.
    Kemperman believed that the recommended operational changes would result in compliance
    with the Board’s nighttime numeric noise emission standards. Tr. at 1507-1510.
    However, Kemperman revised his recommendations after evaluating the sound level
    measurements recorded by Zak on June 27, 1996. Tr. at 1510-1511. In this regard, he stated that
    his earlier projections were much lower than those observed by Zak. Tr. at 1511. Kemperman
    then made the following recommendations: fan speed should be reduced 50 percent during night
    time; the height of the enclosure should be increased above the fan discharge using plywood

    9
    with sound absorptive treatment; and the top opening of the enclosure should be closed so that
    air would be forced to go through the inlet silencer. Tr. at 1511-1512.
    Kemperman measured the sound levels from the Crown chiller unit twice after
    implementation of his recommendations. On August 9, 1996, he measured sound levels at the
    property line at elevations of 8 feet, 12 feet, and 16 feet above the ground. The measurements
    were taken at different elevations in order to account for the line of sight from the top of the
    chiller unit enclosure to the second floor bedroom window of the Shelton residence. Tr. at 1515.
    The measurements were taken at two fan speeds: one at maximum fan speed and one at slightly
    less than half of the maximum speed. Tr. at 1516. Based on his measurements, Kemperman
    concluded that reducing fan speed resulted in the decrease of sound levels by 15 to 20 dB. Exh.
    122.
    Kemperman again measured sound levels at three locations in the vicinity of the Crown
    chiller unit on August 15, 1996. The sound levels were measured four feet above the ground at
    approximately eight feet north of the property line between the Shelton and Crown residences,
    and on the patio on the east side of the Shelton residence. The third location was a second story
    bedroom window over the porch roof of the Shelton residence (14 feet above ground). The
    sound measurements on August 15, 1996, showed significant reduction in sound emission from
    the chiller unit. The sound levels measured in this final sound monitoring event were below the
    Board’s numeric noise emission standards of Section 901.102. Exh. 125.
    Effects of Noise Interference
    In June 1994, when the Crown chiller unit began operating 24 hours per day (Tr. at 375),
    the noise from the chiller unit could be heard in the Sheltons’ kitchen, living room, dining room,
    family room, master bedroom, and the bedroom of their eldest son, David B. Shelton. Tr. at 376-
    377. The noise was loudest on the southern end of the Shelton home second floor, where son
    David B. Shelton’s bedroom was located. Tr. at 377. Susi Shelton testified that the noise was so
    loud that her son could not sleep in his room even with the windows closed and a fan operating
    in his room. Tr. at 377. David B. Shelton testified that the noise was very loud and annoying.
    Tr. at 523. He testified that he could feel vibrations caused by the chiller unit noise if he put his
    head on the window or wall of his bedroom. Tr. at 530-532. The loud noises were produced by
    the cycling of the system on and off, pulsating sound, and the high pitches of the fans. Tr. at
    377. Susi Shelton described the noises as worse at nighttime when they would be awakened by
    the noise. Tr. at 380. She testified that the noise prevented the family from sleeping, leading to
    exhaustion, headaches, stress, and tension in the family. Tr. at 381.
    David Shelton described the chiller unit noise in 1994 as “an extensive, deep, powerful
    drone that penetrated the house. And, it was interspersed with huge sound surges, booms, if you
    will, as different components of the system kicked in and out. At times, particularly in the
    evening, we could also hear higher pitched sound such as a waterfall and hear also beating
    sound, which I’m told were probably different phases of the system going in and out of phase
    with each other.” Tr. at 818. David Shelton said that the chiller unit noise caused family
    impacts such as loss of sleep, his son moving from his room, inability to use their backyard or
    patio, extreme tiredness, depression, anxiety, and short tempers. Tr. at 818-819. The Shelton’s

    10
    son stopped camping in either the front or backyard. Tr. at 528-529. Susi Shelton was unable to
    escape the noise of the chiller unit by going indoors, closing the windows, or turning on either
    music or television. Tr. 388-389. These impacts continued from June through September 1994.
    Tr. at 532, 820. David Shelton hired Mr. Shiner to take the first noise measurements of the
    Crown chiller unit on July 5, 1994. Exh. 56.
    Despite the installation of acoustical panels and discharge cones prior to the 1995 cooling
    season, the Sheltons reported that throughout April, May, and June 1995 the noise from the
    chiller unit created stress and tension in the Shelton family. Tr. at 445-446. Susi Shelton
    testified that she experienced headaches and pains down her neck and across her shoulders. Tr.
    at 445-447. The noise disrupted the Sheltons’ sleep and could be heard in the Sheltons’ kitchen,
    living room, dining room, family room, master bedroom, and throughout the entire second floor
    of their home. Tr. at 443-444. Closing windows and turning on music or television did not
    reduce the level of annoyance caused by the chiller unit. Tr. at 445-445. Son, David B. Shelton,
    testified that after the chiller unit was activated in April 1995, he slept in his bedroom only half
    the time. Tr. 533, 535. He testified that when sleeping in his bedroom, the chiller unit woke him
    when parts clicked on or off, and as a consequence in the morning he felt tired, cranky, lazy, and
    found it difficult to concentrate in school with little sleep. Tr. at 533-534.
    On June 19, 1995, Mr. Shriner again measured noise from the chiller unit in the evening.
    Exh. 60. Mr. Shriner reported that the acoustic housing and removing the discharge cones
    significantly reduced the noise. Exh. 60. After removal of the discharge cones, the Sheltons
    could still hear the low drones, high pitches, and on/off cycle emitted by the chiller unit in their
    home with the windows closed in late June, 1995. The noise was still much worse on the second
    floor. Tr. at 449.
    Throughout July, August, and September 1995, Susi Shelton was able to sleep in her first
    floor bedroom located on the northern end of her home only if the windows were closed, the
    overhead fan was operating, and she used a prescription sleeping additive. Tr. at 459-460.
    David Shelton had difficulty sleeping even when using ear plugs, with a fan operating and the
    windows closed. Tr. at 890. Susi Shelton testified that she was unable to wear her corrective
    contact lens without problems during June, July, and August 1995 because her eyes were dry
    from lack of sleep. Tr. at 460-462. However, Susi Shelton did testify that the removal of the
    discharge cones in June 1995 and an operational adjustment to reduce on-and-off cycling
    resulted in a modest reduction in the chiller unit noise. Tr. at 459. David Shelton also wrote in a
    letter to Steven Crown on June 26, 1995, that “[t]he new enclosure has helped, but it has not
    solved the air conditioner noise problem.” Exh. 41.
    Ms. Marjorie Julian testified that she was awakened at night by the noise from the Crown
    chiller unit and felt her floor vibrating from the noise. Tr. at 159-160. Ms. Julian and her
    husband, Robert, live just north of the Sheltons’ home at 727 Ardsley Road. Tr. at 126-127. The
    south face of the Julians’ home is approximately 120 to 145 feet from the Crowns’ north
    property line. Tr. at 155.
    MOTION TO DISMISS

    11
    The Crowns filed a motion to dismiss on the grounds that the case is now moot. Mot.
    Dis. at 1. The Crowns assert that the modifications to the chiller unit have reduced the noise
    emissions so that the unit meets both the numeric noise and nuisance noise standards. Mot. Dis.
    at 1. The Crowns maintain that even if the Board finds that the chiller unit emitted noises in
    1995 and 1996 that constituted noise pollution, there is no existing noise pollution and no future
    prospect of noise pollution . Mot. Dis. at 2. Therefore, the complaint should be dismissed with
    prejudice as moot. Mot. Dis. at 2.
    The Sheltons maintain that a Board order is necessary to ensure that the Crowns maintain
    the physical structures and operating protocols necessary to maintain compliance with the Act.
    Res. Mot. Dis. at 1. The Sheltons also cite Section 33 of the Act as a basis for ruling against the
    motion to dismiss: “It shall not be a defense to findings of violations of provisions of the Act or
    Board regulations or a bar to the assessment of civil penalties that the person has come into
    compliance subsequent to the violation...” 415 ILCS 5/33 (1996).
    The Board denies the motion to dismiss. There is ample statutory authority, as noted by
    the Sheltons at Section 33 of the Act (415 ILCS 5/33 (1996)), for the Board to find a violation of
    the Act or Board regulations in cases where compliance has been achieved subsequent to a
    violation. The Board will now discuss the allegations and findings of violation in the sections
    below.
    ARGUMENTS AND ANALYSIS
    The Sheltons have asserted that noise emitted by the Crowns’ chiller unit has violated
    both the numeric noise and nuisance noise regulations of the Board. First, the Board will discuss
    a novel argument raised by the Crowns which asserts that Section 31(b) of the Act (415 ILCS
    5/31(b) (1994)) does not authorize a citizen’s enforcement action with regard to past violations,
    based on conditions or emissions which did not exist and were not threatened when the
    complaint was filed. Resp. Br. at 3. Then, we will present the arguments and discuss the
    allegations concerning numeric noise violations. Finally, we will turn to the nuisance noise
    complaint and the civil penalty issue.
    Citizen’s Enforcement Authority with Regard to Past Violations
    The Crowns assert that because Section 31(b) of the Act (415 ILCS 5/31(b) (1994))
    1
    which provides that a citizen may file “a written complaint ... against any person allegedly
    violating the Act...” is written in the present tense (i.e., violating), a citizen has no authority to
    bring enforcement action for past violations. The Crowns therefore maintain that the Board
    should use its discretionary power under Section 31(b) to dismiss the complaint. The Board does
    not agree with the Crowns, and can find no appellate or Supreme Court decision during the
    Board’s 27 years of existence that agrees with the Crowns’ argument. Therefore, the Board
    reiterates that the Sheltons have authority under Section 31(b) of the Act to bring this citizens
    enforcement action.
    1
    The Board notes that Section 31(b) in the 1994 version of the Illinois Compiled Statutes (415
    ILCS 5/31(b) (1994))
    is now found at Section 31(d) of the Act (415 ILCS 5/31(d) (1996)).

    12
    Numeric Noise Allegations
    The Sheltons argue that the numeric noise limitations set forth at 35 Ill. Adm. Code
    901.102(a) and (b) apply to the Crown chiller unit and were exceeded on July 5, 1994, June 19,
    1995, June 26, 1996, and August 15, 1996. Comp. Br. at 43. The Sheltons maintain that the
    residential exemption from the numeric noise standards (35 Ill. Adm. Code 901.107(a)) does not
    apply since the Crowns’ chiller unit is not a residential unit but rather a commercial unit
    operated in a commercial manner. Comp. Br. at 43-44. In addition, the Sheltons assert that if
    the residential exemption does apply, it should only be applicable after March 1995, when the
    Crowns actually occupied their residence. Comp. Br. at 44.
    The Crowns argue that the numeric noise standards Section 901.102 have no application
    in this proceeding. The Crowns contend that Section 901.107(a) exempts the application of the
    numeric standards of Section 910.102 to sound emitted from land used as specified by SLUCM
    Code 100
    2
    , which includes “household units.” 35 Ill. Adm. Code 901.101(a) Appendix B at B-1
    Code 1100. The Crowns assert that characterization of the chiller unit as a commercial unit is
    irrelevant to an applicability determination with regard to the numeric noise standards at Section
    901.107(a). The Crowns maintain that the use of the premises on which the chiller is located
    determines the applicability of Section 901.107(a), since Section 907.107(a) specifically exempts
    “land used as specified in SLUCM Codes 110...,” where SLUCM Code 110 covers “household
    units.” Resp. Br. at 6.
    The Board finds that the Part 901.102 numeric standards do not apply in this case. The
    exemption at Section 901.107(a) and the SLUCM Code 110 (Part 905, Appendix B) indicates
    that the Part 901.102 numeric standards do not apply to sound emitted from land used for
    household units.
    3
    Thus, it appears that the exemption at Section 901.107(a) would apply to
    noise emitted from the Crown chiller unit since the chiller unit is a part of the Crown residence,
    i.e. the “household unit.” The Board is not persuaded by the Sheltons’ argument that the Crown
    residence was a “construction site” from the time the Crowns began operating the chiller unit in
    1994, until the Crowns moved into the structure in March 1995, and therefore was not entitled to
    the residential exemption at Section 901.107. It is clear from the SLUCM definition of
    household unit that the intent to occupy a structure as separate living quarters is the key to this
    operational definition. There is no exception that during the construction phase, a household
    unit intended for occupancy as separate living quarters should be treated as a commercial unit.
    2
    The Board’s regulations adopted the use of the Standard Land Use Coding Manual (SLUCM)
    which
    3
    The term
    can be
    “household
    found at 35
    unit”
    Ill.
    is
    Admdefined
    . Code
    by
    901.101(a)
    the SLUCM
    Appendix
    Code as
    B.
    a house, an apartment, or other
    group of rooms, or a single room that is intended for occupancy as separate living quarters.
    Occupants of “household units” do not live and eat with other persons in the structure (such as
    boarding house), and there is either (1) direct access from the outside or through common hall, or
    (2) there is a kitchen or cooking equipment for exclusive use of the occupants of the unit. The
    occupants may be a family, a group of unrelated persons, or a person living alone. Mobile
    homes...

    13
    Even if the numeric standards were applicable, the review of the sound data indicates that
    the monitoring results cannot be compared with the numeric standards to establish a violation
    since the sound measurements were not obtained in accordance with the Board regulations at
    Section 900.103. Specifically, Section 900.103(b) requires sound measurements to be based
    upon L
    eq
    averaging with a reference time of one hour. The Board has previously found that only
    sound levels measured on the basis of L
    eq
    averaging over a period of one hour and corrected for
    ambient sound can be compared with the allowable octave band sound pressure levels specified
    at 35 Ill. Adm. Code 901.102 to show compliance or non-compliance. Tex v. Coggeshall, PCB
    90-182.
    4
    Even though sound levels in this case appear to be measured on the basis of L
    eq
    averaging, the reference times were significantly less than the required one hour. Therefore,
    even if the Board had not previously found that the residential exemption for the numeric noise
    standards applied in this case, the sound measurements in the record do not appear to be
    sufficient to find a numeric noise violation. However, as discussed further below, the sound
    evidence can still be considered when reviewing the Section 33(c) factors in a nuisance noise
    case. See Discovery South Group, Ltd., v. Pollution Control Board, 275 Ill. App. 3d 547, 559,
    656 N.E. 2d 51, 51(1st Dist. 1995).
    Nuisance Noise Allegations
    The Sheltons argue that the noise from the Crowns’ chiller unit unreasonably interfered
    with the Sheltons’ use and enjoyment of their home during those times when the chiller unit
    operated between September 1993 and August 1996. Comp. Br. at 8-25. The Sheltons maintain
    that the interference was unreasonable because a review of the five factors in Section 33(c) of the
    Act leads to a proposed Board finding against the Crowns for each factor. Comp. Br. at 41.
    Finally, the Sheltons assert that the Board should impose a $30,000 civil penalty. Comp. Br. at
    44.
    The Crowns maintain that this dispute has gone through two basic phases: the pre-
    enclosure phase from fall 1993 to spring 1995, and the post-enclosure phase including summer
    and fall 1995 and early summer of 1996. Resp. Br. at 7. The Crowns argue that the noise
    controversy during the pre-enclosure phase was mediated by Winnetka and led to construction of
    the initial enclosure of the chiller unit in spring 1995. Essentially, the Crowns argue that
    because local authorities attempted to mediate the dispute during the pre-enclosure phase, the
    Board does not have jurisdiction over that time period. Resp. Br. at 7. The Crowns then argue
    that after the acoustic enclosure was in place, the Sheltons did not establish that the chiller unit
    noise unreasonably interfered with the Sheltons’ use or enjoyment of their property. Resp. Br. at
    11. The Crowns maintain that a number of witnesses testified that the acoustic enclosure
    reduced the sound levels emitted by the chiller unit in early summer 1995. Resp. Br. at 11.
    Finally, the Crowns challenged the Sheltons credibility and asserted that the Sheltons’ windows
    air conditioner was noisier than the Crown chiller unit. Resp. Br. at 13.
    4
    The Board has made exception to this precedent only in cases where a party has shown that the
    problem noise at issue is emitted in bursts shorter than one hour, such as discrete songs. See
    Village of Matteson v. World Music Theater
    (February 25, 1993), PCB 90-146, slip. op. 45-46,
    56, 275 Ill. App. 3d 547, 656 N.E. 2d 51 (1st Dist. 1995). Neither of the parties made such a
    demonstration in this case.

    14
    The Board finds that the testimony of the Sheltons clearly demonstrates that the noise
    from the Crowns’ chiller unit interfered with the Sheltons’ lives and use and enjoyment of their
    property. To determine if the interference was “unreasonable” the Board must examine the
    factors enumerated in Section 33(c) of the Act. Before proceeding to discuss the Section 33(c)
    factors, the Board will first address questions raised concerning the appropriate time frame to
    consider in this complaint.
    Appropriate Time Period
    The Crowns raise an apparent jurisdictional challenge to the Board’s authority to find
    nuisance noise violations pursuant to the Act for the “pre-enclosure phase” from fall 1993 to
    spring 1995 because Winnetka was attempting to “mediate” the dispute for that time period. The
    Board reiterates its order of October 5, 1995, which found that this complaint was not
    duplicitous, and therefore directed this matter to hearing. The Sheltons argue that the time
    period of the complaint should include the 1996 cooling season, up until the final enclosure
    adjustments in August 1996. However, the record shows that the Sheltons moved from their
    home in January 1996 and the house has apparently been sold. There is not enough evidence in
    the record to show that noise from the Crowns’ chiller unit interfered with the Sheltons’ lives
    and enjoyment of their property after they moved in January 1996. Therefore, the Board finds
    that the proper time period to consider in the action is from the chiller unit’s first operation in
    September 1993, until the Sheltons moved in January 1996.
    Section 33(c)(i): Degree of Injury or Interference
    In assessing the character and degree of injury or interference caused by the noise
    emissions from the Crowns’ chiller unit, the Board looked to whether the noises “substantially
    and frequently interferes with the use and enjoyment of life and property, beyond minor trifling
    annoyance or discomfort.” Kenneth Metivier and Cynthia Metivier v. Douglas Kenyon d/b/a
    Douglas Kenyon, Inc., PCB 92-74 slip op. at 4, (December 16, 1993), citing Kvatsak. Susi and
    David Shelton, and their son David B., all testified that they were unable to sleep due to the
    chiller unit noise, which was a constant feature of their environment during the cooling season
    for the time frame in question. Son David B. Shelton was not able to sleep in his bedroom on the
    second floor facing the Crowns’ residence on numerous occasions when the chiller unit was
    operating. He testified that noise from the Crowns’ chiller unit vibrated the windows and wall of
    his bedroom. All three Sheltons testifying noted increased stress and tension in the family when
    the chiller unit noise was present. In addition, Ms. Julian, the Sheltons’ neighbor to the north,
    further from the Crowns’ residence than the Sheltons, testified that the noise from the Crowns’
    chiller unit awakened her at night and vibrated the floor of her home. Susi Shelton attributed
    several of her medical problems to the noise, but did not introduce any evidence from medical
    personnel into the record. Nevertheless, the record in this proceeding clearly indicates that the
    noise from the Crowns’ chiller unit went beyond mere trifling annoyance to substantially and
    frequently interfere with the Sheltons’ use and enjoyment of their property. The decibel level of
    the sound measurements in this record also support this analysis. Therefore, this 33(c) factor
    supports a Board finding of unreasonable interference.

    15
    Section 33(c)(ii): Social and Economic Value of the Pollution Source
    The record contains little information on the social and economic value of the pollution
    source. The only evidence concerns the necessity of removing humidity from the Crown
    residence to preserve elaborate interior appointments. Therefore, this 33(c) factor neither
    supports nor mitigates a Board finding of unreasonable interference.
    Section 33(c)(iii): Suitability or Priority of Location
    The documents published by the chiller unit manufacturer warned that the 25-ton chiller
    unit may not be suitable in a residential application because of noise emitted by the unit. The
    progression of sound measurements during the pendency of this dispute demonstrate that
    operational modification and a properly designed acoustical enclosure were essential to adapt
    this particular chiller unit to a residential setting. In summary, the Crowns’ chiller unit was
    unsuitable for a residential setting before the operational controls and proper acoustical
    enclosure were in place. Therefore, this 33(c) factor supports a Board finding of unreasonable
    interference.
    Section 33(c)(iv): Technical Practicability and Economic Reasonableness of Reducing
    Emissions
    The record in this case supports a finding that the nuisance noise from the Crown chiller
    unit has been attenuated, therefore the control methods were technically practicable. The record
    does not expressly address economic reasonableness, although some monetary figures are
    available. The total cost of the HVAC system was approximately $300,000. Stip. No. 1. The
    cost of noise control was approximately $20,000. Stip. No. 1. Therefore, the Board finds that
    the seven percent (7%) additional cost of appropriate noise control was reasonable and this
    factor supports finding an unreasonable interference.
    Section 33(c)(v): Subsequent Compliance
    The record indicates that the operational controls and acoustic enclosure have mitigated
    the noise emitted from the Crown chiller unit so that it is no longer produces nuisance noise.
    Therefore, this 33(c) factor mitigates a Board finding of unreasonable interference.
    Nuisance Noise Summary
    A review of all the factors set forth in Section 33(c) of the Act supports a finding that
    noise from the Crowns’ chiller unit was an unreasonable interference in the lives of the Sheltons
    during those times when the chiller unit was operating between September 1993 and January
    1996. The record shows that the effects on the Sheltons’ lives and enjoyment of their property
    went beyond mere annoyance. The record also demonstrates that the potential for noise
    problems in a residential setting with this chiller unit could have been anticipated before
    installation because of printed warnings in the manufacturer’s literature. The nuisance noise
    emissions were mitigated with operational controls and a properly designed acoustical enclosure,
    which added a reasonable seven percent (7%) to the cost of the HVAC system. Therefore, the

    16
    Crowns are found to have violated Section 23 and 24 of the Act because of the nuisance noise
    emissions from their chiller unit during the time period in question.
    CIVIL PENALTY
    In determing the appropriate civil penalty, the Board considers the factors set forth in
    Section 33(c) and Section 42(h) of the Act. See People v. Berniece Kershaw and Darwin Dale
    Kershaw d/b/a Kershaw Mobile Home Park, PCB 92-164 (April 20, 1994). The Board must bear
    in mind that no formulae exist, and all facts and circumstances must be reviewed. Kershaw, at
    14.
    The Board has stated that the statutory maximum penalty “is a natural or logical
    benchmark from which to begin considering factors in aggravation and mitigation of the penalty
    amounts” IEPA v. Allen Barry, individually and d/b/a Allen Barry Livestock, PCB 88-71, 111
    PCB 11 at 72 (May 10, 1990). The formula for calculating the maximum penalty is contained in
    Section 42(a) and (b) of the Act (415 ILCS 5/42(a) and (b) (1994)). Section 42(a) provides for a
    civil penalty not to exceed $50,000 for violating a provision of the Act or Board regulations, and
    an additional civil penalty not to exceed $10,000 for each day during which the violation
    continues.
    Section 42(h) of the Act states that “[i]n determining the appropriate civil penalty to be
    imposed, the Board is authorized to consider any matters of record in mitigation or aggravation
    of penalty, including but not limited to the following factors: (1) the duration and gravity of the
    violation; (2) the presence or absence of due diligence on the part of the violator in attempting to
    comply with the requirements of this Act and regulations there under or to secure relief
    therefrom as provided by this Act; (3) any economic benefits accrued by the violator because of
    delay in compliance with requirements; (4) the amount of monetary penalty which will serve to
    deter further violations by the violator and to otherwise aid in enhancing voluntary compliance
    wit this Act by the violator and other persons similarly subject to the Act; and (5) the number,
    proximity in time, and gravity of previously adjudicated violations of this Act by the violator.”
    The Sheltons argue that the Board could order a maximum penalty of $3,050,000 based
    on Section 42(a) of the Act. Comp. Br. at 46. The Sheltons maintain that based on their review
    of the 42(h) factors, a civil penalty of $30,000 should be levied by the Board in this case. Comp.
    Br. at 45-46. The Crowns argue that in view of all the eventually successful measures taken to
    control sounds emitted by the chiller unit, no civil penalty is warranted. Resp. Br. at 17.
    After careful review of the Section 42(h) factors, as indicated in the remainder of this
    paragraph, and Section 33(c) factors discussed above, the Board finds that no civil penalty is
    warranted in this case. The record indicates that the duration and gravity of the violation
    supports a civil penalty. Section 42(h)(1). However, Board consideration of the other four
    factors does not support a civil penalty. The Board is concerned that mitigation of the nuisance
    noise took two full cooling seasons (see due diligence, Section 42(h)(2)), however, the record
    also shows that the Crowns continually experimented with noise control measures during that
    time. There is nothing in the record to indicate that the Crowns received economic benefits from
    noncompliance. Section 42(h)(3). The Crowns are presently in compliance, so no monetary

    17
    penalty is necessary to enhance compliance. Section 42(h)(4). Finally, there is nothing in the
    record to indicate that the Crowns have any previously adjudicated violations of the Act. 415
    ILCS 5/42(h)(5).
    ORDER
    The Board finds that the Crowns have violated Section 23 and 24 of the Illinois
    Environmental Protection Act in relation to the nuisance noise emitted by the chiller unit on their
    property at 685 Ardsley Road, Winnetka, Cook County, Illinois, during the times when the
    chiller unit operated between September 1993 and January 1996. The Board finds that no civil
    penalty is warranted in this case.
    This docket is closed.
    IT IS SO ORDERED.
    Section 41 of the Environmental Protection Act (415 ILCS 5/41 (1996)) provides for the
    appeal of final Board orders to the Illinois Appellate Court within 35 days of service of this
    order. Illinois Supreme Court Rule 335 establishes such filing requirements. See 145 Ill. 2d R.
    335; see also 35 Ill. Adm. Code 101.246, Motions for Reconsideration.
    I, Dorothy M. Gunn, Clerk of the Illinois Pollution Control Board, hereby certify that the
    above opinion and order was adopted on the 2nd day of October 1997, by a vote of 7-0.