ILLINOIS POLLUTION CONTROL BOARD 
January 20, 2005 
 
IN THE MATTER OF: 
 ) 
 ) 
SDWA UPDATE, USEPA AMENDMENTS      )      R05-6 
(January 1, 2004 though June 30, 2004,           )      (Identical-in-Substance 
August 25, 2004) 
 )      Rulemaking - Public Water Supply) 
 
Adopted Rule.  Final Order. 
 
OPINION AND ORDER OF THE BOARD (by T.E. Johnson): 
 
The Board today adopts amendments to the Illinois regulations that are “identical in 
substance” to drinking water regulations adopted by the United States Environmental Protection 
Agency (USEPA).  The USEPA rules implement Sections 1412(b), 1414(c), 1417(a), and 
1445(a) of the federal Safe Drinking Water Act (SDWA) (42 U.S.C. §§ 300g-1(a), 300g-3(c), 
300g-6(a), and 300j-4(a) (1994)). 
 
This docket includes federal SDWA amendments that USEPA adopted in the period 
January 1, 2004 though June 30, 2004, and on August 25, 2004.  The amendments approve one 
new analytical method for analysis of total coliforms and 
E. coli
 and three new methods for 
analysis of uranium in drinking water.  Another amendment makes a number of minor 
corrections to various federal rules, including the Long Term 1 Enhanced Surface Water 
Treatment Rule, the Surface Water Treatment Rule, and the Lead and Copper Rule. 
 
Sections 7.2 and 17.5 of the Environmental Protection Act (Act) (415 ILCS 5/7.2 and 
17.5 (2002)) provide for quick adoption by the Board of regulations that are identical in 
substance to federal regulations that USEPA adopts to implement Sections 1412(b), 1414(c), 
1417(a), and 1445(a) of the federal SDWA.  Section 17.5 also provides that Title VII of the Act 
and Section 5 of the Administrative Procedure Act (APA) (5 ILCS 100/5-35 and 5-40 (2002)) do 
not apply to the Board’s adoption of identical-in-substance regulations.  The federal SDWA 
regulations are found at 40 C.F.R. 141 through 143. 
 
A Notice of Proposed Amendments appeared in the October 29, 2004 issue of the 
Illinois 
Register
, at 28 Ill. Reg. 13954.  The Board received three public comments during the public 
comment period, and these are reflected in the adopted amendments.  The Board will 
immediately file the adopted rules with the Office of the Secretary of State. 
 
FEDERAL ACTIONS CONSIDERED IN THIS RULEMAKING
 
This docket includes federal SDWA amendments that USEPA adopted in the period 
January 1, 2004 though June 30, 2004.  Also included are amendments adopted by USEPA on 
August 25, 2004.  The Board included the August 25, 2004 amendments because they directly 
affect amendments undertaken during the period January 1, 2004 though June 30, 2004. 
 
 
 2
The amendments involved in this docket approve one new analytical method for analysis 
of total coliforms and 
E. coli
 and three new methods for analysis of uranium in drinking water.  
Another amendment makes a number of minor corrections to various federal rules, including the 
 Long Term 1 Enhanced Surface Water Treatment Rule, the Surface Water Treatment Rule, and 
the Lead and Copper Rule. 
 
The following briefly summarizes the federal actions considered in this rulemaking. 
 
Docket R05-6:  January 1, 2004 though June 30, 2004 SDWA Amendments
 
USEPA amended the federal SDWA regulations three times during the period January 1, 
2004 though June 30, 2004.  These actions are summarized below: 
 
February 13, 2004 (69 Fed. Reg. 7156) 
USEPA approved an additional analytical method for coliforms and 
E. coli
 in 
drinking water. 
 
June 2, 2004 (69 Fed. Reg. 31008) 
By a direct final rule, USEPA approved three additional analytical methods for 
uranium in drinking water.  (This rule was withdrawn on August 25, 2004, as 
described below.) 
 
June 29, 2004 (69 Fed. Reg. 38850) 
USEPA adopted a number of minor corrections to various rules, including the 
Long Term 1 Enhanced Surface Water Treatment Rule, the Surface Water 
Treatment Rule, and the Lead and Copper Rule. 
 
Two Later SDWA (Drinking Water) Amendments of Interest:  August 25, 2004 
 
When the Board observes an action outside the timeframe of a docket that would require 
expedited consideration in the pending docket, the Board will expedite consideration of those 
amendments.  Federal actions that could warrant expedited consideration include those that 
 directly affect the amendments involved in this docket, those for which compelling reasons 
would warrant consideration as soon as possible, and those for which the Board has received a 
request for expedited consideration. 
 
In the course of ongoing monitoring of federal actions, the Board has identified two 
simultaneous and related USEPA actions since June 30, 2004, that further amend the SDWA 
rules.  Both actions relate directly to the subject matter of the June 2, 2004 amendments that are 
involved in this docket.  Those two actions are described as follows: 
 
August 25, 2004 (69 Fed. Reg. 52176) 
By a final rule, USEPA approved the three additional analytical methods for 
uranium in drinking water that it had approved on June 2, 2004, by a direct final 
rule.  (Note the June 2, 2004 notice of proposed rule at 69 Fed. Reg. 31068.) 
 
 
 3
August 25, 2004 (69 Fed. Reg. 52181) 
In response to adverse public comments, USEPA withdrew its June 2, 2004 direct 
final rule that approved three additional analytical methods for uranium in 
drinking water. 
 
The actions of August 25, 2004, directly affect the subject matter of the June 2, 2004 
amendments.  One August 25, 2004 action nullifies the June 2, 2004 action, and the other 
August 25, 2004 adopts the June 2, 2004 amendments based on the notice of proposed rule 
published on June 2, 2004 in conjunction with the direct final rule.
1
  The ultimate August 25, 
 2004 rule adopted was identical to the direct final rule adopted on June 2, 2004 and withdrawn 
on August 25, 2004. 
 
No Other Federal Actions Having a Direct Impact on the 
Illinois SDWA (Drinking Water) Regulations
 
In addition to the amendments to the federal SDWA regulations, amendments to certain 
other federal regulations occasionally have an effect on the Illinois drinking water rules.  Most 
notably, 35 Ill. Adm. Code 611.102 includes the incorporation of Appendices B and C of 40 
C.F.R. 136 by reference.  These are federal Clean Water Act methods for analysis of 
contaminants in water. 
 
As of the date of this opinion and order, the Board has found no amendments to the 
pertinent segments of 40 C.F.R. 136 in the current update period.  No Board action will be 
required at this time to update the version of 40 C.F.R. 136 incorporated by reference in to 
include the amendments. 
 
Summary Tabulation of the Federal Actions Included in This Docket 
 
February 13, 2004 
(69 Fed. Reg. 7156) 
Additional analytical method for coliforms and 
E. coli
 
in drinking water. 
June 2, 2004 
(69 Fed. Reg. 31008) 
(Direct final rule.)  Approval of three additional 
analytical methods for uranium in drinking water. 
June 29, 2004 
(69 Fed. Reg. 38850) 
Minor corrections to various rules, including the Long 
Term 1 Enhanced Surface Water Treatment Rule, the 
 Surface Water Treatment Rule, and the Lead and 
Copper Rule. 
1
 USEPA uses a direct final rule for actions that it believes will be non-controversial.  USEPA 
simultaneously publishes a notice of proposed amendments and a notice of direct final rule.  The 
direct final rule will take effect about 60 days after publication, unless USEPA publishes a notice 
of withdrawal prior to the effective date.  USEPA will withdraw a direct final rule in response to 
adverse comments filed within 30 days of the date of publication of the rule.  
See, e.g.,
 69 Fed. 
Reg. 31008 (notice of direct final rule); 69 Fed. Reg. 31068 (simultaneous notice of proposed 
rule); 69 Fed. Reg. 52181 (notice of withdrawal of direct final rule). 
 
 4
August 25, 2004 
(69 Fed. Reg. 52176) 
Approval of three additional analytical methods for 
uranium in drinking water.  (The same approved by 
direct final rule on June 2, 2004.) 
August 25, 2004 
(69 Fed. Reg. 52181) 
Withdrawal of the June 2, 2004 direct final rule. 
 
PUBLIC COMMENTS
 
The Board adopted a proposal for public comment in this matter on October 7, 2004.  A 
Notice of Proposed Amendments appeared in the October 29, 2004 issue of the 
Illinois Register
, 
at 28 Ill. Reg. 13954.  The Board received public comments on this proposal for 45 days 
 following its publication, until December 13, 2004.  The Board received the following comments 
during the comment period: 
 
PC 1   E-mail message from JCAR to Erin Conley forwarded to the hearing officer on 
October 27, 2004. 
 
PC 2   E-mail message from JCAR to Erin Conley forwarded to the hearing officer on 
October 28, 2004. 
 
PC 3   Illinois Environmental Protection Agency’s Comments on Proposed SDWA 
Amendments, by Scott Phillips, Manager, Regulatory Section, Division of Legal 
Counsel, Illinois EPA (Agency), dated December 8, 2004 (received December 10, 
2004). 
 
In addition to the public comments received, the Board received a document from JCAR 
entitled “Identical Line Number Version,” which is a copy of the text of the amendments as it 
appeared in the October 29, 2004 
Illinois Register
 notice.  JCAR usually uses highlighting in the 
line-numbered version of proposed amendments to indicate miscellaneous corrections to the text 
of the amendments.  There were no corrections indicated in the line-numbered text for this 
proposal. 
 
In PC 1 and PC 2, JCAR asked questions about the proposal for public comment.  By the 
question in PC 1, JCAR indicated that “Doliform” was misspelled and should have appeared as 
“Coliform” in Section 611.526(f)(9).  The Board has made that correction.  In PC 2, JCAR raised 
a small number of questions relative to the federal corrective amendments of June 29, 2004.  The 
JCAR questions in PC 2 are considered in the segment of this discussion that considers the 
 June 29 corrections. 
 
In PC 3, the Agency points out that the Board deleted too much language from Section 
611.956(d)(2) when incorporating the USEPA corrections to 40 C.F.R. 141.563(b).  The Agency 
comments are considered in the segment of this discussion that considers the June 29, 2004 
federal corrections. 
 
 
 5
DISCUSSION
 
The following discussion begins with a description of the types of deviations the Board 
makes from the literal text of federal regulations in adopting identical-in-substance rules.  It is 
followed by a discussion of the amendments and actions undertaken in direct response to the 
federal actions involved in this proceeding.  This first series of discussions is organized by 
federal subject matter, generally appearing in chronological order of the relevant 
Federal 
Register
 notices involved.  Finally, this discussion closes with a description of the amendments 
and actions that are not directly derived from the federal actions. 
 
Discussion of the Federal Action
 
Newly-Added Analytical Method for Coliforms—Section 611.526 
 
On February 13, 2004 (69 Fed. Reg. 7156), USEPA approved use of the Colitag
®
 
method for monitoring compliance with the total coliforms and 
E. coli
 standards for drinking 
water.  The Colitag
®
 method is a proprietary method available for purchase from CPI 
 International, Inc.  The USEPA action includes the Colitag method among the reference and 
proprietary methods already approved and available for demonstrating compliance with the total 
coliform and 
E. coli
 standards. 
 
The Board incorporated the February 13, 2004 federal amendments without deviation 
from the substance of the federal amendments.  References to the Colitag
®
 method for testing 
total coliforms and 
E. coli
 are added to Section 611.526(c)(10) and (f)(10), respectively.  The 
Board has also added the trademark marking “
®
” to each appearance of the proprietary name 
“Colitag
®
.”  Anyone interested in the substantive aspects of the federal addition of the new 
method should refer to the February 13, 2004 issue of the 
Federal Register
 for further 
information. 
 
The Board requests comment on incorporation of the Colitag
®
 method into the Illinois 
regulations to incorporate the USEPA amendments of February 13, 2004. 
 
Newly-Added Analytical Methods for Uranium—Section 611.720 
 
On June 2, 2004 (69 Fed. Reg. 31008), USEPA adopted a direct final rule approving 
three newly approved analytical methods for monitoring compliance with the uranium standard 
for drinking water.  The methods were inductively coupled plasma-mass spectrometric methods 
in three sources:  the 20th edition of “Standard Methods for the Examination of Water and 
 Wastes,” Method 3125; ASTM Method D5673-03; and Method 200.8 in “Methods for the 
Determination of Metals in Environmental Samples.” 
 
On August 25, 2004 (at 69 Fed. Reg. 52181), USEPA withdrew the June 2, 2004 direct 
final rule in response to a “somewhat ambiguous comment letter.”  69 Fed. Reg. at 52181.  In a 
 
 6
separate notice of final rule, USEPA simultaneously addressed the comment letter and adopted 
amendments substantively identical to those withdrawn.  69 Fed. Reg. 52176 (Aug. 25, 2004).
2
 
The Board incorporated the August 25, 2004 federal amendments without substantive 
deviation.  References to the three newly approved methods for analysis of uranium were added 
to Section 611.720(a)(5).  The only differences between the Illinois amendments and the 
underlying federal amendments are stylistic.  The primary differences relate to differences in the 
format of the respective rules:  the federal rules appear in tabular form, and the corresponding 
Illinois rules appear in the standard paragraph format.  This required the addition of the text from 
federal end note 13 as a Board note appended to subsection (a)(5).  A stylistic difference not 
based on format is the designation of uranium isotopes as “
234
U” and “
238
U,” rather than as “U-
234” and “U-238.”  The table that begins on page 8 of this opinion itemizes all differences 
between the federal and State amendments.  Anyone interested in the substantive aspects of the 
 federal addition of the new method should refer to the August 25, 2004 issue of the 
Federal 
Register
 for further information. 
 
The Board requested comments on incorporation of the uranium methods into the Illinois 
regulations to incorporate the USEPA amendments of August 25, 2004.  The Board received no 
comments on this aspect of the proposed amendments. 
 
Miscellaneous Federal Corrections—Sections 611.231, 611.233, 611.241, 611.242, 611.250, 
611.261, 611.262, 611.301, 611.382, 611.383, 611.532, 611.533, 611.720, 611.732, 611.953, 
611.955, 611.956, and Appendices G and H to Part 611 
 
On June 29, 2004 (69 Fed. Reg. 38850), USEPA adopted a series of corrections to its 
rules.  USEPA described the corrections as clarifying typographic errors, inadvertent omissions, 
editorial errors, and outdated language in various rules.  The rules affected included the 
following: 
 
1.      The Surface Water Treatment Rule (SWTR), adopted by USEPA on 
June 29, 1989 (54 Fed. Reg. 27486), (correcting cross-references); 
 
2.      The Lead and Copper Rule (LCR), adopted by USEPA on June 7, 1991 (at 
56 Fed. Reg. 26460), and corrected on January 12, 2000 (at 65 Fed. Reg. 
1950), (correcting the list of facilities that must receive public education 
brochures in the event of an exceedence of the action level); 
 
3.      The Phase V Rule, adopted by USEPA on July 17, 1992 (at 57 Fed. Reg. 
31776), (clarifying a Best Available Technology for removal of cyanide 
from water) 
 
2
 The effective date is the only difference between the withdrawn rule of June 2, 2004, and that 
adopted on August 25, 2004.  The withdrawn rule would have become effective on August 31, 
2004, and the August 25, 2004 rule became effective on the date of publication. 
 
 7
4.      Bottled Water Requirements (changing the reference to bottled 
requirements to reflect their movement by the Food and Drug 
Administration (FDA) from 20 C.F.R. 103.35 to 21 C.F.R. 165.110 on 
November 13, 1995 (at 60 Fed. Reg. 57076)); 
 
5.      The Information Collection Rule (ICR), adopted by USEPA on May 14, 
1996 (at 61 Fed. Reg. 24345), (removing obsolete references to data 
collected under rules that expired on December 31, 2000); 
 
6.      The Stage 1 Disinfectants and Disinfection Byproducts Rule (Stage 1 D-
DBPR), adopted by USEPA on December 16, 1998 (at 63 Fed. Reg. 
69390), (adding compliance with the maximum residual disinfectant level 
(MRDL) to the compliance requirements; correcting a cross-reference); 
 
7.      The Radionuclides Rule, adopted by USEPA on December 7, 2000 (at 65 
Fed. Reg. 76708), (adding a detection limit for uranium; correcting 
typographic errors; clarifying screening levels); 
 
8.      The Filter Backwash Recycling Rule (FBWR), adopted by USEPA on 
June 8, 2001 (at 66 Fed. Reg. 31086), (correcting cross-references; 
clarifying the public notice requirements); and 
 
9.      The Long Term 1 Enhanced Surface Water Treatment Rule 
(LT1ESWTR), adopted by USEPA on January 14, 2002 (67 Fed. Reg. 
1812), (changing the compliance date from January 14, 2005 to January 1, 
2005; adding clarification that the states may approve more representative 
data sets to avoid disinfection profile monitoring; correcting typographic 
errors, omissions, and cross-references). 
 
The Board incorporated the June 29, 2004 federal amendments without substantive 
deviation.  It was not necessary, however, to make a small number of the federal corrections 
because the Board made the corrections when incorporating the original federal rules into the 
Illinois rules.  The following table indicates the federal provisions affected by the corrections 
and the disposition of the corrections, indicating where applicable the corrections previously 
made by the Board: 
 
40 C.F.R. Provision/Federal 
Rule Affected 
35 Ill. Adm. Code Provision 
 Disposition of Correction 
141.25(c)(1)/Radionuclide Rule 
 611.720(c)(1) 
 Corrected in this docket 
141.26(b)(2)/Radionuclide Rule 
 611.732 
 Corrected in this docket 
141.62(c)/Phase V Rule 
 611.301 
 Corrected in this docket 
141.62(g)/Reference to FDA 
Bottled Water Requirements 
611.301 
 Corrected in this docket 
141.71(a)/SWTR 
 611.231 
 Corrected in this docket 
141.71(c)/SWTR 
 611.233 
 Corrected in this docket 
 141.72(a)/SWTR 
 611.241 
 Corrected in this docket 
 
 8
141.72(b)/SWTR 
 611.242 
 Corrected in this docket 
141.73(a)(1), (a)(2), (b), and 
(c)/SWTR 
611.250 
 Corrected in this docket 
141.73(a)(4)/LT1ESWTR 
 611.250 
 Corrected in this docket 
141.74(b)/SWTR 
 611.532 
 Corrected in this docket 
141.74(c)/SWTR 
 611.533 
 Corrected in this docket 
141.75(a)/SWTR 
 611.261 
 Corrected in this docket 
141.75(b)/SWTR 
 611.262 
 Corrected in this docket 
141.85/LCR 
 611.355 
 USEPA omission not 
adopted in docket R01-7 
141.132/ICR 
 611.382 
 Corrected in this docket 
141.133/Stage 1 D-DBPR 
 611.383 
 Corrected in this docket 
141.170(d)/LT1ESWTR 
 611.740 
 Corrected in docket 
R03-4 
141, Appendix A to Subpart Q/ 
FBWR 
Appendix G to Part 611 
 Corrected in this docket 
141, Appendix B to Subpart Q/ 
LT1ESWTR 
Appendix H to Part 611 
 Corrected in docket 
R03-4 
141.502/LT1ESWTR 
 611.950(c) 
 Corrected in docket 
R03-4 
141.530/LT1ESWTR 
 611.953(a) 
 Corrected in docket 
R03-4 
141.531/LT1ESWTR 
 611.953(b) 
 Corrected in docket 
R03-4 
141.534/LT1ESWTR 
 611.953(e) 
 Corrected in docket 
R03-4 
141.551/LT1ESWTR 
 611.955(b) 
 Corrected in docket 
R03-4 
141.563/LT1ESWTR 
 611.956(d) 
 Partially corrected in 
docket R03-4, completed 
in this docket 
141.570/LT1ESWTR 
 611.957(a) 
 Corrected in docket 
R03-4 
 
The following are the two dockets cited in the above table: 
 
SDWA Update, USEPA Amendments (January 1, 2000 through June 30, 2000; 
LT1ESWTR), R01-7 (Jan. 4, 2001) and  
 
SDWA Update, USEPA Amendments (January 1, 2002 through June 30, 2002; 
LT1ESWTR), R03-4 (Dec. 19, 2002) 
 
The table that begins on page 8 of this opinion itemizes all differences between the 
federal and State amendments.  Anyone interested in the substantive aspects of the federal 
 
 9
addition of the new method should refer to the June 29, 2004 issue of the 
Federal Register
 for 
further information. 
 
The Board requested comments on incorporation of the June 29, 2004 federal corrections 
into the Illinois regulations.  The Board received two comments:  PC 2 from JCAR and PC 3 
from the Agency. 
 
In PC 2, JCAR initially questioned the locations in the Illinois rules of 40 C.F.R. 
141.563(b), (c), and (d).  Those appear as 35 Ill. Adm. Code 611.956(d)(2), (d)(3), and (d)(4), 
respectively.  While these provisions appear in tables in the federal regulations, the Board has 
 codified each in the standard subsection format in the Illinois regulations. 
 
In PC 2, JCAR asked the source of the text added to Section 611.242(c)(2).  That text, 
relating to the use of a certified laboratory for HPC analyses, was derived from 40 C.F.R. 
141.72(b)(3)(ii).  The added text was inadvertently omitted from Section 611.242 in the original 
adoption of that provision in Safe Drinking Water Act Rules, R88-26 (Aug. 9, 1990).  The Board 
used the opportunity of this proceeding to correct the omission. 
 
The language questioned by JCAR in Section 611.242(c)(2) was also inadvertently 
omitted from the original adoption of other provisions in R88-26.  The requirement for use of a 
certified laboratory for HPC analyses was inadvertently omitted from Section 611.241(d)(2) 
(derived from 40 C.F.R. 141.72(a)(4)(ii)), 611.261(b)(8)(G) (derived from 40 C.F.R. 
141.75(a)(2)(viii)(G)), 611.262(b)(3)(G) (derived from 40 C.F.R. 141.75(b)(2)(iii)(G)), and 
611.533(c)(2) (derived from 40 C.F.R. 141.74(c)(3)(ii)).  The Board has restored the language to 
each of these provisions in this proceeding. 
 
JCAR also asked about the use of alternative TTHM and HAA5 data in Section 
611.953(b).  JCAR asked the location of the standards by which the Agency will determine 
whether data are representative.  Section 611.953(b) deems certain data generally acceptable, as 
follows: “samples must have been collected after January 1, 1998, during the month with the 
warmest water temperature, and at the point of maximum residence time in the distribution 
system.”  Thus, USEPA has deemed that recent data which is most likely to indicate TTHM and 
 HAA5 contamination is acceptable (due to an increased reaction rate and time). 
 
The Board believes that no written standard for evaluation of alternative data is 
necessary, since USEPA has indicated the nature of the data sought.  The Agency may accept 
alternative data that is most likely to show TTHM and HAA5 contamination.  The Board 
believes that the determination whether data are representative is an engineering judgment of a 
type routinely made by the Agency.  In response to the JCAR question, however, the Board has 
revised the language of the amendment to Section 611.953(b).  The Board has added a statement 
to Section 611/953(b) that any Agency determination to accept or reject data is to be made by a 
special exception permit.  This will make it clear that a supplier may seek Board review of any 
Agency determination to accept or reject data. 
 
Finally, JCAR asked whether a change is warranted to clarify the federal language added 
to Section 611.953(b).  JCAR asked whether the language should appear as “is representative of 
 
 10
TTHM and HAA5 data” instead of “is representative TTHM and HAA5 data.”  The alternative 
data approved by the Agency must be representative TTHM and HAA5 data, not representative 
of TTHM and HAA5 data.  No change is warranted. 
 
In PC 3, the Agency noted an error in the proposal.  The June 29, 2004 corrections 
deleted the final sentence of 40 C.F.R. 141.563(b).  The Board’s October 7, 2004 proposal for 
public comment inadvertently marked the final two sentences for deletion.  That error is 
 corrected in this opinion and order. 
 
Discussion of Miscellaneous Housekeeping Amendments
 
The tables below list numerous corrections and amendments that are not based on current 
federal amendments.  The first table (beginning immediately below) includes deviations made in 
this Proposal for Public Comment from the verbatim text of the federal amendments.  The 
second table (beginning immediately after Table 1 below) contains corrections and clarifications 
that the Board made in the base text involved in this proposal.  The amendments listed in this 
second table are not directly derived from the current federal amendments.  Some of the entries 
in these tables are discussed further in appropriate segments of the general discussion beginning 
at page 4 of this opinion.  Table 3 (beginning on page 13 below) is a listing of revisions made to 
the text of the amendments from that proposed and set forth in the Board’s opinion and order of 
October 7, 2004.  Table 3 indicates the changes made, as well as the source that suggested each 
of the changes. 
 
Table 1: 
Deviations from the Text of the Federal Amendments 
 
Illinois Section 
 40 C.F.R. Section 
 Revision(s) 
611.301(c) table and 
key 
141.62(c) table and 
key 
Changed “alkaline chlorination” to “ALK 
Cl2” 
611.383(a)(3) 
 141.133(a)(3) 
 Removed the unnecessary semicolon after 
“bromate” that separated elements of a two-
 element series 
611.526(f)(10) 141.21(f)(6)(x) Changed “Colitag
®
” to “Colitag
®
  Test” 
611.720(a)(5) Board 
note 
141.25(a) note 12 to 
the table 
Added the note as a Board note due to 
structural differences; changed “a 0.67 
pCi/μg of uranium conversion factor” to “a 
conversion factor of 0.67 pCi/μg of 
uranium”; changed “U-234” to “
234
U”; 
changed “U-238” to “
238
U” 
 
 11
611.953(b) 
 141.531 
 Changed “your state” to “the Agency”; 
added “by a SEP . . . Section 611.110” as a 
parenthetical offset by commas; added “the 
use of . . . if it determines that the data set 
is” for enhanced clarity; moved “to 
determine these levels” to follow “data set” 
for enhanced clarity; changed the final 
“data set” to “data” 
611.953(e) 
 141.534 
 Changed “use the tables . . . to determine” 
to “the tables . . . must be used to 
determine”; changed “CT99.9” to “CT99.9” 
 
Table2 : 
Board Housekeeping Amendments 
 
Section Source 
 Revision(s) 
611.102(b) “ASTM 
Method D1253-86” 
Board 
 Moved method into appropriate alphabetical order 
611.231(b) Board note 
 Board 
 Updated the 
Code of Federal Regulations
 reference to 
the most recent version available 
611.233 Board note 
 Board 
 Updated the 
Code of Federal Regulations
 reference to 
the most recent version available 
611.241(d)(2) 
 Board 
 Restored the missing federal text “by a certified 
laboratory . . . distribution system” 
611.242(c)(2) 
 Board 
 Restored the missing federal text “by a certified 
laboratory . . . distribution system” 
611.250(a)(1) 
 Board 
 Added the missing parenthetical offset by a comma 
“measured as . . . 611.533(a)” to restore missing federal 
text (twice) 
611.250(b)(1) 
 Board 
 Added the missing parenthetical offset by a comma 
“measured as . . . 611.533(a)” to restore missing federal 
text 
611.250(b)(2) 
 Board 
 Added the missing parenthetical offset by a comma 
“measured as . . . 611.533(a)” to restore missing federal 
text 
611.250(c)(1) 
 Board 
 Added the missing parenthetical offset by a comma 
“measured as . . . 611.533(a)” to restore missing federal 
text 
611.250(c)(2) 
 Board 
 Added the missing parenthetical offset by a comma 
“measured as . . . 611.533(a)” to restore missing federal 
text 
611.261(b)(8)(G) 
 Board 
 Restored the missing federal text “by a certified 
laboratory . . . distribution system” 
611.261 Board note 
 Board 
 Updated the 
Code of Federal Regulations
 reference to 
the most recent version available 
 
 12
Section Source Revision(s) 
611.262(b)(3)(G) 
 Board 
 Restored the missing federal text “by a certified 
laboratory . . . distribution system” 
611.262 Board note 
 Board 
 Updated the 
Code of Federal Regulations
 reference to 
the most recent version available 
611.301(c) key 
 Board 
 Moved “CC corrosion control” into alphabetical order; 
moved “Cl2 oxidation (chlorine)” into alphabetical 
order; moved “ED electrodialysis” into alphabetical 
order; moved “O/F oxidation/filtration” into 
alphabetical order 
611.382 Board note 
 Board 
 Updated the 
Code of Federal Regulations
 reference to 
the most recent version available 
611.383 Board note 
 Board 
 Updated the 
Code of Federal Regulations
 reference to 
the most recent version available 
611.526(c)(9) 
 Board 
 Corrected the spelling “Doliform” to “Coliform” 
611.526(d) 
 Board 
 Moved the ending period after “reserved” inside the 
closing quotation mark 
611.526(f)(2) 
 Board 
 Changed numeric “4” to written “four” 
611.526(f)(3) 
 Board 
 Changed numeric “6-watt” to written “six-watt” 
 611.526(f)(9) 
 JCAR 
 Corrected the spelling “Doliform” to “Coliform” 
611.531 Board note 
 Board 
 Updated the 
Code of Federal Regulations
 reference to 
the most recent version available 
611.532(f)(2) 
 Board 
 Added “that” before “a supplier” for a restrictive 
relative clause; restored “measured as specified . . . this 
Section” as missing federal text offset by a comma as a 
parenthetical 
611.532 Board note 
 Board 
 Updated the 
Code of Federal Regulations
 reference to 
the most recent version available 
611.533(c)(1) 
 Board 
 Changed the cross-reference “611.521 et seq.” to 
“Sections 611.521 through 611.527”; restored 
“measured as specified . . . this Section” as missing 
federal text offset by a comma as a parenthetical 
611.533(c)(2) 
 Board 
 Changed “subsection (c)(1)” to “subsection (c)(1) of 
this Section”; restored the missing federal text “by a 
certified laboratory . . . distribution system” 
611.533 Board note 
 Board 
 Updated the 
Code of Federal Regulations
 reference to 
the most recent version available 
611.720(c)(1) Board 
note 
Board Updated the 
 Code of Federal Regulations
 reference to 
the most recent version available 
611.720(c)(2) Board 
note 
Board Updated the 
 Code of Federal Regulations
 reference to 
the most recent version available 
611.720 Board note 
 Board 
 Updated the 
Code of Federal Regulations
 reference to 
the most recent version available 
611.953 Board note 
 Board 
 Updated the 
Code of Federal Regulations
 reference to 
the most recent version available 
 
 13
Section Source Revision(s) 
611.956 Board note 
 Board 
 Updated the 
Code of Federal Regulations
 reference to 
the most recent version available 
Appendix H, note 4 
 Board 
 Added the abbreviated name for the rule in parentheses 
“(SWTR)”; added the abbreviated name for the rule in 
parentheses “(IESWTR)”; added the abbreviated name 
for the rule in parentheses “(LT1SWTR)” 
Appendix H, note 6 
 Board 
 Removed the rule name “Surface Water Treatment 
Rule” and removed the parentheses from the 
abbreviated name for the rule “SWTR”; removed the 
rule name “Interim Enhanced Surface Water Treatment 
Rule” and removed the parentheses from the 
abbreviated name for the rule  “(IESWTR)”; removed 
the rule name “Long Term 1 Enhanced Surface Water 
Treatment Rule” and added the abbreviated name for 
the rule “(LT1SWTR)”; removed the rule name 
“Surface Water Treatment Rule” and added the 
 abbreviated name for the rule “(SWTR)” 
Appendix H, note 8 
 Board 
 Removed the rule name “Surface Water Treatment 
Rule” and removed the parentheses from the 
abbreviated name for the rule “SWTR”; removed the 
rule name “Interim Enhanced Surface Water Treatment 
Rule” and removed the parentheses from the 
abbreviated name for the rule  “(IESWTR)”; removed 
the rule name “Long Term 1 Enhanced Surface Water 
Treatment Rule” and added the abbreviated name for 
the rule “(LT1SWTR)” 
 
Table 3:
Revisions to the Text of the Proposed Amendments in Final Adoption 
 
Section Revised 
 Source 
 Revision(s) 
611.526(f)(2) 
 Board 
 Changed numeric “4” to written “four” 
611.526(f)(3) 
 Board 
 Changed numeric “6-watt” to written “six-watt” 
611.526(f)(9) 
 JCAR 
 Corrected the spelling “Doliform” to “Coliform” 
611.953(b) Board, 
JCAR 
Added “by a SEP . . . 611.110” as a parenthetical offset 
by commas 
611.956(d)(2) 
 Agency 
 Removed the overstrike to retain the erroneously 
deleted sentence “The self-assessment . . . self-
assessment report.” 
 
ORDER
 
The Board proposes the following amendments for public comment: 
 
 
 14
TITLE 35:  ENVIRONMENTAL PROTECTION 
SUBTITLE F:  PUBLIC WATER SUPPLIES 
 CHAPTER I:  POLLUTION CONTROL BOARD 
 
PART 611 
PRIMARY DRINKING WATER STANDARDS 
 
SUBPART A:  GENERAL 
Section 
611.100        Purpose, Scope, and Applicability 
611.101 Definitions 
611.102        Incorporations by Reference 
611.103 Severability 
611.107        Agency Inspection of PWS Facilities 
611.108        Delegation to Local Government 
611.109 Enforcement 
611.110        Special Exception Permits 
611.111        Relief Equivalent to SDWA Section 1415(a) Variances 
611.112        Relief Equivalent to SDWA Section 1416 Exemptions 
611.113        Alternative Treatment Techniques 
611.114 Siting Requirements 
611.115        Source Water Quantity 
611.120 Effective Dates 
611.121        Maximum Contaminant Levels and Finished Water Quality 
611.125 Fluoridation Requirement 
611.126        Prohibition on Use of Lead 
611.130        Special Requirements for Certain Variances and Adjusted Standards 
611.131       Relief Equivalent to SDWA Section 1415(e) Small System Variance 
611.160       Composite Correction Program 
 
SUBPART B:  FILTRATION AND DISINFECTION 
Section 
611.201        Requiring a Demonstration 
611.202        Procedures for Agency Determinations 
611.211 Filtration Required 
611.212        Groundwater under Direct Influence of Surface Water 
611.213        No Method of HPC Analysis 
611.220 General Requirements 
611.230        Filtration Effective Dates 
 611.231        Source Water Quality Conditions 
611.232 Site-Specific Conditions 
611.233        Treatment Technique Violations 
611.240 Disinfection 
611.241 Unfiltered PWSs 
611.242 Filtered PWSs 
611.250 Filtration 
 
 15
611.261        Unfiltered PWSs:  Reporting and Recordkeeping 
611.262        Filtered PWSs:  Reporting and Recordkeeping 
611.271        Protection during Repair Work 
611.272        Disinfection Following Repair 
611.276 Recycle Provisions 
 
SUBPART C:  USE OF NON-CENTRALIZED TREATMENT DEVICES 
Section 
611.280 Point-of-Entry Devices 
611.290        Use of Point-of-Use Devices or Bottled Water 
 
SUBPART D:  TREATMENT TECHNIQUES 
Section 
611.295 General Requirements 
611.296        Acrylamide and Epichlorohydrin 
611.297 Corrosion Control 
 
SUBPART F:  MAXIMUM CONTAMINANT LEVELS (MCLs) AND 
MAXIMUM RESIDUAL DISINFECTANT LEVELS (MRDLs) 
Section 
611.300        Old MCLs for Inorganic Chemical Contaminants 
611.301        Revised MCLs for Inorganic Chemical Contaminants 
611.310        Old Maximum Contaminant Levels (MCLs) for Organic Chemical Contaminants 
611.311        Revised MCLs for Organic Chemical Contaminants 
611.312        Maximum Contaminant Levels (MCLs) for Disinfection Byproducts (DBPs) 
611.313        Maximum Residual Disinfectant Levels (MRDLs) 
611.320 Turbidity (Repealed) 
611.325 Microbiological Contaminants 
 611.330        Maximum Contaminant Levels for Radionuclides 
611.331        Beta Particle and Photon Radioactivity (Repealed) 
 
SUBPART G:  LEAD AND COPPER 
Section 
611.350 General Requirements 
611.351        Applicability of Corrosion Control 
611.352        Corrosion Control Treatment 
611.353        Source Water Treatment 
611.354        Lead Service Line Replacement 
611.355        Public Education and Supplemental Monitoring 
611.356        Tap Water Monitoring for Lead and Copper 
611.357        Monitoring for Water Quality Parameters 
611.358        Monitoring for Lead and Copper in Source Water 
611.359 Analytical Methods 
611.360 Reporting 
611.361 Recordkeeping 
 
 
 16
SUBPART I:  DISINFECTANT RESIDUALS, DISINFECTION BYPRODUCTS, 
AND DISINFECTION BYPRODUCT PRECURSORS 
Section 
611.380 General Requirements 
611.381 Analytical Requirements 
611.382 Monitoring Requirements 
611.383 Compliance Requirements 
611.384        Reporting and Recordkeeping Requirements 
611.385        Treatment Technique for Control of Disinfection Byproduct (DBP) Precursors 
 
SUBPART K:  GENERAL MONITORING AND ANALYTICAL 
REQUIREMENTS 
Section 
611.480        Alternative Analytical Techniques 
611.490 Certified Laboratories 
611.491        Laboratory Testing Equipment 
611.500 Consecutive PWSs 
611.510        Special Monitoring for Unregulated Contaminants (Repealed) 
 
SUBPART L:  MICROBIOLOGICAL MONITORING AND ANALYTICAL 
REQUIREMENTS 
Section 
611.521        Routine Coliform Monitoring 
611.522        Repeat Coliform Monitoring 
611.523        Invalidation of Total Coliform Samples 
611.524 Sanitary Surveys 
611.525        Fecal Coliform and E. Coli Testing 
611.526 Analytical Methodology 
611.527        Response to Violation 
611.531 Analytical Requirements 
611.532 Unfiltered PWSs 
611.533 Filtered PWSs 
 
SUBPART M:  TURBIDITY MONITORING AND ANALYTICAL 
REQUIREMENTS 
Section 
611.560 Turbidity 
 
SUBPART N:  INORGANIC MONITORING AND ANALYTICAL 
REQUIREMENTS 
Section 
611.591        Violation of a State MCL 
611.592        Frequency of State Monitoring 
611.600 Applicability 
611.601 Monitoring Frequency 
611.602        Asbestos Monitoring Frequency 
 
 17
611.603        Inorganic Monitoring Frequency 
611.604 Nitrate Monitoring 
611.605 Nitrite Monitoring 
611.606 Confirmation Samples 
611.607        More Frequent Monitoring and Confirmation Sampling 
611.608        Additional Optional Monitoring 
611.609 Determining Compliance 
611.610        Inorganic Monitoring Times 
611.611 Inorganic Analysis 
611.612        Monitoring Requirements for Old Inorganic MCLs 
611.630        Special Monitoring for Sodium 
611.631        Special Monitoring for Inorganic Chemicals (Repealed) 
 
SUBPART O:  ORGANIC MONITORING AND ANALYTICAL REQUIREMENTS 
Section 
611.640 Definitions 
611.641 Old MCLs 
611.645        Analytical Methods for Organic Chemical Contaminants 
611.646        Phase I, Phase II, and Phase V Volatile Organic Contaminants 
611.647        Sampling for Phase I Volatile Organic Contaminants (Repealed) 
611.648        Phase II, Phase IIB, and Phase V Synthetic Organic Contaminants 
611.650        Monitoring for 36 Contaminants (Repealed) 
611.657        Analytical Methods for 36 Contaminants (Repealed) 
611.658        Special Monitoring for Organic Chemicals (Repealed) 
 
SUBPART P:  THM MONITORING AND ANALYTICAL REQUIREMENTS 
Section 
611.680        Sampling, Analytical, and other Requirements 
611.683        Reduced Monitoring Frequency (Repealed) 
611.684 Averaging (Repealed) 
611.685 Analytical Methods 
611.686        Modification to System (Repealed) 
611.687        Sampling for THM Potential (Repealed) 
611.688 Applicability Dates (Repealed) 
 
SUBPART Q:  RADIOLOGICAL MONITORING AND ANALYTICAL 
REQUIREMENTS 
Section 
611.720 Analytical Methods 
611.731 Gross Alpha 
611.732        Beta Particle and Photon Radioactivity 
611.733       General Monitoring and Compliance Requirements 
 
 
 18
SUBPART R:  ENHANCED FILTRATION AND DISINFECTION:  SYSTEMS 
THAT SERVE 10,000 OR MORE PEOPLE 
Section 
 611.740 General Requirements 
611.741       Standards for Avoiding Filtration 
611.742       Disinfection Profiling and Benchmarking 
611.743 Filtration 
611.744       Filtration Sampling Requirements 
611.745       Reporting and Recordkeeping Requirements 
 
SUBPART T:  REPORTING AND RECORDKEEPING 
Section 
611.830 Applicability 
611.831        Monthly Operating Report 
611.832        Notice by Agency (Repealed) 
611.833        Cross Connection Reporting 
611.840 Reporting 
611.851        Reporting MCL, MRDL, and other Violations (Repealed) 
611.852        Reporting other Violations (Repealed) 
611.853        Notice to New Billing Units (Repealed) 
611.854        General Content of Public Notice (Repealed) 
611.855        Mandatory Health Effects Language (Repealed) 
611.856 Fluoride Notice (Repealed) 
611.858        Fluoride Secondary Standard (Repealed) 
611.860 Record Maintenance 
611.870        List of 36 Contaminants (Repealed) 
 
SUBPART U:  CONSUMER CONFIDENCE REPORTS 
Section 
611.881        Purpose and Applicability 
611.882 Compliance Dates 
611.883        Content of the Reports 
611.884        Required Additional Health Information 
611.885        Report Delivery and Recordkeeping 
 
SUBPART V:  PUBLIC NOTIFICATION OF DRINKING WATER 
VIOLATIONS 
Section 
611.901       General Public Notification Requirements 
611.902       Tier 1 Public Notice:  Form, Manner, and Frequency of Notice 
 611.903       Tier 2 Public Notice:  Form, Manner, and Frequency of Notice 
611.904       Tier 3 Public Notice:  Form, Manner, and Frequency of Notice 
611.905       Content of the Public Notice 
611.906       Notice to New Billing Units or New Customers 
611.907       Special Notice of the Availability of Unregulated Contaminant Monitoring 
Results 
 
 19
611.908       Special Notice for Exceedence of the Fluoride Secondary Standard 
611.909       Special Notice for Nitrate Exceedences above the MCL by a Non-Community 
Water System 
611.910       Notice by the Agency on Behalf of a PWS 
 
SUBPART X:  ENHANCED FILTRATION AND DISINFECTION--SYSTEMS 
SERVING FEWER THAN 10,000 PEOPLE 
Section 
611.950 General Requirements 
611.951       Finished Water Reservoirs 
611.952       Additional Watershed Control Requirements for Unfiltered Systems 
611.953 Disinfection Profile 
611.954 Disinfection Benchmark 
611.955       Combined Filter Effluent Turbidity Limits 
611.956       Individual Filter Turbidity Requirements 
611.957       Reporting and Recordkeeping Requirements 
 
611.Appendix A       Regulated Contaminants 
611.Appendix B       Percent Inactivation of G. Lamblia Cysts 
611.Appendix C       Common Names of Organic Chemicals 
611.Appendix D       Defined Substrate Method for the Simultaneous Detection of Total Coliforms 
and Eschericia Coli from Drinking Water 
611.Appendix E       Mandatory Lead Public Education Information for Community Water 
 Systems 
611.Appendix F       Mandatory Lead Public Education Information for Non-Transient Non-
Community Water Systems 
611.Appendix G       NPDWR Violations and Situations Requiring Public Notice 
611.Appendix H       Standard Health Effects Language for Public Notification 
611.Appendix I        Acronyms Used in Public Notification Regulation 
611.Table A           Total Coliform Monitoring Frequency 
611.Table B           Fecal or Total Coliform Density Measurements 
611.Table C           Frequency of RDC Measurement 
611.Table D           Number of Lead and Copper Monitoring Sites 
611.Table E           Lead and Copper Monitoring Start Dates 
611.Table F           Number of Water Quality Parameter Sampling Sites 
611.Table G           Summary of Section 611.357 Monitoring Requirements for Water Quality 
Parameters 
611.Table Z           Federal Effective Dates 
 
AUTHORITY:  Implementing Sections 7.2, 17, and 17.5 and authorized by Section 27 of the 
Environmental Protection Act [415 ILCS 5/7.2, 17, 17.5, and 27]. 
 
SOURCE:  Adopted in R88-26 at 14 Ill. Reg. 16517, effective September 20, 1990; amended in 
R90-21 at 14 Ill. Reg. 20448, effective December 11, 1990; amended in R90-13 at 15 Ill. Reg. 1562, 
effective January 22, 1991; amended in R91-3 at 16 Ill. Reg. 19010, effective December 1, 1992; 
amended in R92-3 at 17 Ill. Reg. 7796, effective May 18, 1993; amended in R93-1 at 17 Ill. Reg. 
 
 20
12650, effective July 23, 1993; amended in R94-4 at 18 Ill. Reg. 12291, effective July 28, 1994; 
 amended in R94-23 at 19 Ill. Reg. 8613, effective June 20, 1995; amended in R95-17 at 20 Ill. Reg. 
14493, effective October 22, 1996; amended in R98-2 at 22 Ill. Reg. 5020, effective March 5, 
1998; amended in R99-6 at 23 Ill. Reg. 2756, effective February 17, 1999; amended in R99-12 at 23 
Ill. Reg. 10348, effective August 11, 1999; amended in R00-8 at 23 Ill. Reg. 14715, effective 
December 8, 1999; amended in R00-10 at 24 Ill. Reg. 14226, effective September 11, 2000; 
amended in R01-7 at 25 Ill. Reg. 1329, effective January 11, 2001; amended in R01-20 at 25 Ill. 
Reg. 13611, effective October 9, 2001; amended in R02-5 at 26 Ill. Reg. 3522, effective 
February 22, 2002; amended in R03-4 at 27 Ill. Reg. 1183, effective January 10, 2003; amended 
in R03-15 at 27 Ill. Reg. 16447, effective October 10, 2003; amended in R04-3 at 28 Ill. Reg. 
5269, effective March 10, 2004; amended in R04-13 at 28 Ill. Reg. 12666, effective August 26, 
2004; amended in R05-6 at 29 Ill. Reg. ________, effective ______________________. 
 
SUBPART A:  GENERAL 
 
Section 611.102       Incorporations by Reference 
 
a)      Abbreviations and short-name listing of references.  The following names and 
abbreviated names, presented in alphabetical order, are used in this Part to refer to 
materials incorporated by reference: 
 
“Amco-AEPA-1 Polymer” is available from Advanced Polymer Systems. 
 
“ASTM Method” means a method published by and available from the 
American Society for Testing and Materials (ASTM). 
 
“Colisure Test” means “Colisure Presence/Absence Test for Detection and 
 Identification of Coliform Bacteria and Escherichia Coli in Drinking 
Water,” available from Millipore Corporation, Technical Services 
Department. 
 
“Colitag
®
 Test” means “Colitag
®
  Product as a Test for Detection and 
Identification of Coliforms and E. coli Bacteria in Drinking Water and 
Source Water as Required in National Primary Drinking Water 
Regulations,” available from CPI International. 
 
“Dioxin and Furan Method 1613” means “Tetra- through Octa- 
Chlorinated Dioxins and Furans by Isotope-Dilution HRGC/HRMS,” 
available from NTIS. 
 
“GLI Method 2” means GLI Method 2, “Turbidity,” Nov. 2, 1992, 
available from Great Lakes Instruments, Inc. 
 
“Hach FilterTrak Method 10133” means “Determination of Turbidity by 
Laser Nephelometry,” available from Hach Co. 
 
 
 21
“HASL Procedure Manual” means HASL Procedure Manual, HASL 300, 
available from ERDA Health and Safety Laboratory. 
 
“Kelada 01” means “Kelada Automated Test Methods for Total Cyanide, 
Acid Dissociable Cyanide, And Thiocyanate,” Revision 1.2, August 2001, 
EPA # 821–B–01–009, available from the National Technical Information 
Service (NTIS). 
 
“Membrane Filter Technique using Chromocult Doliform Agar” means 
“Chromocult Coliform Agar Presence/Absence Membrane Filter Test 
Method for Detection and Identification of Coliform Bacteria and 
Escherichia coli in Finished Waters,” available from EMD Chemicals Inc
.
 
 
“NCRP” means “National Council on Radiation Protection.” 
 
“NTIS” means “National Technical Information Service.” 
 
“New Jersey Radium Method” means “Determination of Radium 228 in 
Drinking Water,” available from the New Jersey Department of 
Environmental Protection. 
 
“New York Radium Method” means “Determination of Ra-226 and Ra-
228 (Ra-02),” available from the New York Department of Public Health. 
 
“ONGP-MUG Test” (meaning “minimal medium ortho-nitrophenyl-beta-
d-galactopyranoside-4-methyl-umbelliferyl-beta-d-glucuronide test”), also 
called the “Autoanalysis Colilert System,” is Method 9223, available in 
“Standard Methods for the Examination of Water and Wastewater,” 18th 
ed., from American Public Health Association. 
 
“Palintest Method 1001” means “Method Number 1001,” available from 
Palintest, Ltd. or the Hach Company. 
 
“QuikChem Method 10–204–00–1-X” means “Digestion and distillation 
of total cyanide in drinking and wastewaters using MICRO DIST and 
determination of cyanide by flow injection analysis,” available from 
Lachat Instruments. 
 
“Readycult Coliforms 100 Presence/Absence Test” means “Readycult 
Coliforms 100 Presence/Absence Test for Detection and Identification of 
Coliform Bacteria and Escherichia coli in Finished Waters,” available 
from EMD Chemicals Inc. 
 
“SimPlate Method” means “IDEXX SimPlate TM HPC Test Method for 
Heterotrophs in Water,” available from IDEXX Laboratories, Inc. 
 
 
 22
“Radiochemical Methods” means “Interim Radiochemical Methodology 
for Drinking Water,” available from NTIS. 
 
“Standard Methods” means “Standard Methods for the Examination of 
Water and Wastewater,” available from the American Public Health 
Association or the American Waterworks Association. 
 
“Syngenta AG-625” means “Atrazine in Drinking Water by 
Immunoassay,” February 2001 is available from Syngenta Crop 
Protection, Inc. 
 
“Technical Bulletin 601” means “Technical Bulletin 601, Standard 
Method of Testing for Nitrate in Drinking Water,” July 1994, available 
from Analytical Technology, Inc. 
 
“Technicon Methods” means “Fluoride in Water and Wastewater,” 
available from Bran & Luebbe. 
 
“USDOE Manual” means “EML Procedures Manual,” available from the 
United State Department of Energy. 
 
“USEPA Asbestos Methods-100.1” means Method 100.1, “Analytical 
Method for Determination of Asbestos Fibers in Water,” September 1983, 
available from NTIS. 
 
“USEPA Asbestos Methods-100.2” means Method 100.2, “Determination 
of Asbestos Structures over 10-mm in Length in Drinking Water,” June 
1994, available from NTIS. 
 
“USEPA Environmental Inorganics Methods” means “Methods for the 
Determination of Inorganic Substances in Environmental Samples,” 
August 1993, available from NTIS. 
 
“USEPA Environmental Metals Methods” means “Methods for the 
 Determination of Metals in Environmental Samples,” available from 
NTIS. 
 
“USEPA Inorganic Methods” means “Methods for Chemical Analysis of 
Water and Wastes,” March 1983, available from NTIS. 
 
“USEPA Interim Radiochemical Methods” means “Interim Radiochemical 
Methodology for Drinking Water,” EPA 600/4-75-008 (revised), March 
1976.  Available from NTIS. 
 
“USEPA Organic Methods” means “Methods for the Determination of 
Organic Compounds in Drinking Water,” July 1991, for Methods 502.2, 
 
 23
505, 507, 508, 508A, 515.1, and 531.1; “Methods for the Determination of 
Organic Compounds in Drinking Water--Supplement I,” July 1990, for 
Methods 506, 547, 550, 550.1, and 551; and “Methods for the 
Determination of Organic Compounds in Drinking Water--Supplement 
II,” August 1992, for Methods 515.2, 524.2, 548.1, 549.1, 552.1, and 555, 
available from NTIS.  Methods 504.1, 508.1, and 525.2 are available from 
EPA EMSL; “Methods for the Determination of Organic Compounds” in 
Drinking Water--Supplement II, August 1992, for Method 552.1; “Methods 
for the Determination of Organic Compounds in Drinking Water--
Supplement III,” August 1995, for Methods 502.2, 524.2, 551.1, and 552.2.  
Method 515.4, “Determination of Chlorinated Acids in Drinking Water by 
Liquid-Liquid Microextraction, Derivatization and Fast Gas 
Chromatography with Electron Capture Detection,” Revision 1.0, April 
2000, EPA 815/B–00/001, and Method 531.2, “Measurement of N-
 methylcarbamoyloximes and N-methylcarbamates in Water by Direct 
Aqueous Injection HPLC with Postcolumn Derivatization,” Revision 1.0, 
September 2001, EPA 815/B/01/002, are both available on-line from 
USEPA, Office of Ground Water and Drinking Water. 
 
“USEPA Radioactivity Methods” means “Prescribed Procedures for 
Measurement of Radioactivity in Drinking Water,” EPA 600/4-80-032, 
August 1980.  Available from NTIS. 
 
“USEPA Radiochemical Analyses” means “Radiochemical Analytical 
Procedures for Analysis of Environmental Samples,” March 1979.  
Available from NTIS. 
 
“USEPA Radiochemistry Methods” means “Radiochemistry Procedures 
Manual,” EPA 520/5-84-006, December 1987.  Available from NTIS. 
 
“USEPA Technical Notes” means “Technical Notes on Drinking Water 
Methods,” available from NTIS. 
 
“USGS Methods” means “Methods of Analysis by the U.S. Geological 
Survey National Water Quality Laboratory--Determination of Inorganic 
and Organic Constituents in Water and Fluvial Sediments,” available from 
NTIS and USGS. 
 
“Waters Method B-1011” means “Waters Test Method for the 
Determination of Nitrite/Nitrate in Water Using Single Column Ion 
Chromatography,” available from Waters Corporation, Technical Services 
Division. 
 
b)      The Board incorporates the following publications by reference: 
 
Advanced Polymer Systems, 3696 Haven Avenue, Redwood City, CA 
 
 24
94063 415-366-2626. 
 
Amco-AEPA-1 Polymer.  See 40 CFR 141.22(a) (2003).  Also, as 
referenced in ASTM D1889. 
 
American Public Health Association, 1015 Fifteenth Street NW, 
Washington, DC 20005 800-645-5476. 
 
“Standard Methods for the Examination of Water and 
Wastewater,” 17th Edition, 1989 (referred to as “Standard 
Methods, 17th ed.”). 
 
“Standard Methods for the Examination of Water and 
Wastewater,” 18th Edition, 1992, including “Supplement to the 
18th Edition of Standard Methods for the Examination of Water 
and Wastewater,” 1994 (collectively referred to as “Standard 
Methods, 18th ed.”).  See the methods listed separately for the 
same references under American Waterworks Association. 
 
“Standard Methods for the Examination of Water and 
Wastewater,” 19th Edition, 1995 (referred to as “Standard 
Methods, 19th ed.”). 
 
“Standard Methods for the Examination of Water and 
Wastewater,” 20th Edition, 1998 (referred to as “Standard 
Methods, 20th ed.”). 
 
American Waterworks Association et al., 6666 West Quincy Ave., 
Denver, CO 80235 303-794-7711. 
 
“National Field Evaluation of a Defined Substrate Method for the 
Simultaneous Enumeration of Total Coliforms and Escherichia coli 
for Drinking Water:  Comparison with the Standard Multiple Tube 
Fermentation Method,” S.C. Edberg, M.J. Allen & D.B. Smith, 
Applied Environmental Microbiology, vol. 54, iss. 6, pp 1595-
 1601 (1988). 
 
“Standard Methods for the Examination of Water and 
Wastewater,” 13th Edition, 1971 (referred to as “Standard 
Methods, 13th ed.”). 
 
Method 302, Gross Alpha and Gross Beta Radioactivity in 
Water (Total, Suspended, and Dissolved). 
 
Method 303, Total Radioactive Strontium and Strontium 90 
in Water. 
 
 25
 
Method 304, Radium in Water by Precipitation. 
 
Method 305, Radium 226 by Radon in Water (Soluble, 
Suspended, and Total). 
 
Method 306, Tritium in Water. 
 
“Standard Methods for the Examination of Water and 
Wastewater,” 17th Edition, 1989 (referred to as “Standard 
Methods, 17th ed.”). 
 
Method 7110 B, Gross Alpha and Gross Beta Radioactivity 
in Water (Total, Suspended, and Dissolved). 
 
Method 7500-Cs B, Radioactive Cesium, Precipitation 
Method. 
 
Method 7500-
3
H B, Tritium in Water. 
 
Method 7500-I B, Radioactive Iodine, Precipitation 
Method. 
 
Method 7500-I C, Radioactive Iodine, Ion-Exchange 
Method. 
 
Method 7500-I D, Radioactive Iodine, Distillation Method. 
 
Method 7500-Ra B, Radium in Water by Precipitation. 
 
Method 7500-Ra C, Radium 226 by Radon in Water 
(Soluble, Suspended, and Total). 
 
Method 7500-Ra D, Radium, Sequential Precipitation 
 Method (Proposed). 
 
Method 7500-Sr B, Total Radioactive Strontium and 
Strontium 90 in Water. 
 
Method 7500-U B, Uranium, Radiochemical Method 
(Proposed). 
 
Method 7500-U C, Uranium, Isotopic Method (Proposed). 
 
“Standard Methods for the Examination of Water and 
Wastewater,” 18th Edition, 1992 (referred to as “Standard 
 
 26
Methods, 18th ed.”). 
 
Method 2130 B, Turbidity, Nephelometric Method. 
 
Method 2320 B, Alkalinity, Titration Method. 
 
Method 2510 B, Conductivity, Laboratory Method. 
 
Method 2550, Temperature, Laboratory and Field Methods. 
 
Method 3111 B, Metals by Flame Atomic Absorption 
Spectrometry, Direct Air-Acetylene Flame Method. 
 
Method 3111 D, Metals by Flame Atomic Absorption 
Spectrometry, Direct Nitrous Oxide-Acetylene Flame 
Method. 
 
Method 3112 B, Metals by Cold-Vapor Atomic Absorption 
Spectrometry, Cold-Vapor Atomic Absorption 
Spectrometric Method. 
 
Method 3113 B, Metals by Electrothermal Atomic 
Absorption Spectrometry, Electrothermal Atomic 
Absorption Spectrometric Method. 
 
Method 3114 B, Metals by Hydride Generation/Atomic 
Absorption Spectrometry, Manual Hydride 
Generation/Atomic Absorption Spectrometric Method. 
 
Method 3120 B, Metals by Plasma Emission Spectroscopy, 
Inductively Coupled Plasma (ICP) Method. 
 
Method 3500-Ca D, Calcium, EDTA Titrimetric Method. 
 
Method 3500-Mg E, Magnesium, Calculation Method. 
 
Method 4110 B, Determination of Anions by Ion 
Chromatography, Ion Chromatography with Chemical 
Suppression of Eluent Conductivity. 
 
Method 4500-CN
-
 C, Cyanide, Total Cyanide after 
Distillation. 
 
Method 4500-CN
-
 E, Cyanide, Colorimetric Method. 
 
Method 4500-CN
-
 F, Cyanide, Cyanide-Selective Electrode 
 
 27
Method. 
 
Method 4500-CN
-
 G, Cyanide, Cyanides Amenable to 
Chlorination after Distillation. 
 
Method 4500-Cl D, Chlorine, Amperometric Titration 
Method. 
 
Method 4500-Cl E, Chlorine, Low-Level Amperometric 
Titration Method. 
 
Method 4500-Cl F, Chlorine, DPD Ferrous Titrimetric 
Method. 
 
Method 4500-Cl G, Chlorine, DPD Colorimetric Method. 
 
Method 4500-Cl H, Chlorine, Syringaldazine (FACTS) 
Method. 
 
Method 4500-Cl I, Chlorine, Iodometric Electrode Method. 
 
Method 4500-ClO2 C, Chlorine Dioxide, Amperometric 
Method I. 
 
Method 4500-ClO2 D, Chlorine Dioxide, DPD Method. 
 
Method 4500-ClO2 E, Chlorine Dioxide, Amperometric 
 Method II (Proposed). 
 
Method 4500-F
-
 B, Fluoride, Preliminary Distillation Step. 
 
Method 4500-F
-
 C, Fluoride, Ion-Selective Electrode 
Method. 
 
Method 4500-F
-
 D, Fluoride, SPADNS Method. 
 
Method 4500-F
-
 E, Fluoride, Complexone Method. 
 
Method 4500-H
+
 B, pH Value, Electrometric Method. 
 
Method 4500-NO2
-
 B, Nitrogen (Nitrite), Colorimetric 
Method. 
 
Method 4500-NO3
-
 D, Nitrogen (Nitrate), Nitrate Electrode 
Method. 
 
 
 28
Method 4500-NO3
-
 E, Nitrogen (Nitrate), Cadmium 
Reduction Method. 
 
Method 4500-NO3
-
 F, Nitrogen (Nitrate), Automated 
Cadmium Reduction Method. 
 
Method 4500-O3 B, Ozone (Residual) (Proposed), Indigo 
Colorimetric Method. 
 
Method 4500-P E, Phosphorus, Ascorbic Acid Method. 
 
Method 4500-P F, Phosphorus, Automated Ascorbic Acid 
Reduction Method. 
 
Method 4500-Si D, Silica, Molybdosilicate Method. 
 
Method 4500-Si E, Silica, Heteropoly Blue Method. 
 
Method 4500-Si F, Silica, Automated Method for 
 Molybdate-Reactive Silica. 
 
Method 6651, Glyphosate Herbicide (Proposed). 
 
Method 7110 B, Gross Alpha and Beta Radioactivity 
(Total, Suspended, and Dissolved), Evaporation Method for 
Gross Alpha-Beta. 
 
Method 7110 C, Gross Alpha and Beta Radioactivity 
(Total, Suspended, and Dissolved), Coprecipitation Method 
for Gross Alpha Radioactivity in Drinking Water 
(Proposed). 
 
Method 7500-Cs B, Radioactive Cesium, Precipitation 
Method. 
 
Method 7500-
3
H B, Tritium, Liquid Scintillation 
Spectrometric Method. 
 
Method 7500-I B, Radioactive Iodine, Precipitation 
Method. 
 
Method 7500-I C, Radioactive Iodine, Ion-Exchange 
Method. 
 
Method 7500-I D, Radioactive Iodine, Distillation Method. 
 
 
 29
Method 7500-Ra B, Radium, Precipitation Method. 
 
Method 7500-Ra C, Radium, Emanation Method. 
 
Method 7500-Ra D, Radium, Sequential Precipitation 
Method (Proposed). 
 
Method 7500-Sr B, Total Radioactive Strontium and 
Strontium 90, Precipitation Method. 
 
Method 7500-U B, Uranium, Radiochemical Method 
(Proposed). 
 
Method 7500-U C, Uranium, Isotopic Method (Proposed). 
 
Method 9215 B, Heterotrophic Plate Count, Pour Plate 
Method. 
 
Method 9221 A, Multiple-Tube Fermentation Technique 
 for Members of the Coliform Group, Introduction. 
 
Method 9221 B, Multiple-Tube Fermentation Technique 
for Members of the Coliform Group, Standard Total 
Coliform Fermentation Technique. 
 
Method 9221 C, Multiple-Tube Fermentation Technique 
for Members of the Coliform Group, Estimation of 
Bacterial Density. 
 
Method 9221 D, Multiple-Tube Fermentation Technique 
for Members of the Coliform Group, Presence-Absence (P-
A) Coliform Test. 
 
Method 9221 E, Multiple-Tube Fermentation Technique 
for Members of the Coliform Group, Fecal Coliform 
Procedure. 
 
Method 9222 A, Membrane Filter Technique for Members 
of the Coliform Group, Introduction. 
 
Method 9222 B, Membrane Filter Technique for Members 
of the Coliform Group, Standard Total Coliform Membrane 
Filter Procedure. 
 
Method 9222 C, Membrane Filter Technique for Members 
of the Coliform Group, Delayed-Incubation Total Coliform 
 
 30
Procedure. 
 
Method 9222 D, Membrane Filter Technique for Members 
of the Coliform Group, Fecal Coliform Membrane Filter 
Procedure. 
 
Method 9223, Chromogenic Substrate Coliform Test 
(Proposed). 
 
“Supplement to the 18th Edition of Standard Methods for the 
Examination of Water and Wastewater,” American Public Health 
Association, 1994. 
 
Method 6610, Carbamate Pesticide Method. 
 
“Standard Methods for the Examination of Water and 
Wastewater,” 19th Edition, 1995 (referred to as “Standard 
Methods, 19th ed.”). 
 
Method 2130 B, Turbidity, Nephelometric Method. 
 
Method 2320 B, Alkalinity, Titration Method. 
 
Method 2510 B, Conductivity, Laboratory Method. 
 
Method 2550, Temperature, Laboratory, and Field 
Methods. 
 
Method 3111 B, Metals by Flame Atomic Absorption 
Spectrometry, Direct Air-Acetylene Flame Method. 
 
Method 3111 D, Metals by Flame Atomic Absorption 
Spectrometry, Direct Nitrous Oxide-Acetylene Flame 
Method. 
 
Method 3112 B, Metals by Cold-Vapor Atomic Absorption 
Spectrometry, Cold-Vapor Atomic Absorption 
Spectrometric Method. 
 
Method 3113 B, Metals by Electrothermal Atomic 
Absorption Spectrometry, Electrothermal Atomic 
Absorption Spectrometric Method. 
 
Method 3114 B, Metals by Hydride Generation/Atomic 
Absorption Spectrometry, Manual Hydride 
Generation/Atomic Absorption Spectrometric Method. 
 
 31
 
Method 3120 B, Metals by Plasma Emission Spectroscopy, 
Inductively Coupled Plasma (ICP) Method. 
 
Method 3500-Ca D, Calcium, EDTA Titrimetric Method. 
 
Method 3500-Mg E, Magnesium, Calculation Method. 
 
Method 4110 B, Determination of Anions by Ion 
Chromatography, Ion Chromatography with Chemical 
 Suppression of Eluent Conductivity. 
 
Method 4500-Cl D, Chlorine, Amperometric Titration 
Method. 
 
Method 4500-Cl E, Chlorine, Low-Level Amperometric 
Titration Method. 
 
Method 4500-Cl F, Chlorine, DPD Ferrous Titrimetric 
Method. 
 
Method 4500-Cl G, Chlorine, DPD Colorimetric Method. 
 
Method 4500-Cl H, Chlorine, Syringaldazine (FACTS) 
Method. 
 
Method 4500-Cl I, Chlorine, Iodometric Electrode Method. 
 
Method 4500-ClO2 C, Chlorine Dioxide, Amperometric 
Method I. 
 
Method 4500-ClO2 D, Chlorine Dioxide, DPD Method. 
 
Method 4500-ClO2 E, Chlorine Dioxide, Amperometric 
Method II (Proposed). 
 
Method 4500-CN
-
 C, Cyanide, Total Cyanide after 
Distillation. 
 
Method 4500-CN
-
 E, Cyanide, Colorimetric Method. 
 
Method 4500-CN
-
 F, Cyanide, Cyanide-Selective Electrode 
Method. 
 
Method 4500-CN
-
 G, Cyanide, Cyanides Amenable to 
Chlorination after Distillation. 
 
 32
 
Method 4500-F
-
 B, Fluoride, Preliminary Distillation Step. 
 
Method 4500-F
-
 C, Fluoride, Ion-Selective Electrode 
 Method. 
 
Method 4500-F
-
 D, Fluoride, SPADNS Method. 
 
Method 4500-F
-
 E, Fluoride, Complexone Method. 
 
Method 4500-H
+
 B, pH Value, Electrometric Method. 
 
Method 4500-NO2
-
 B, Nitrogen (Nitrite), Colorimetric 
Method. 
 
Method 4500-NO3
-
 D, Nitrogen (Nitrate), Nitrate Electrode 
Method. 
 
Method 4500-NO3
-
 E, Nitrogen (Nitrate), Cadmium 
Reduction Method. 
 
Method 4500-NO3
-
 F, Nitrogen (Nitrate), Automated 
Cadmium Reduction Method. 
 
Method 4500-O3 B, Ozone (Residual) (Proposed), Indigo 
Colorimetric Method. 
 
Method 4500-P E, Phosphorus, Ascorbic Acid Method. 
 
Method 4500-P F, Phosphorus, Automated Ascorbic Acid 
Reduction Method. 
 
Method 4500-Si D, Silica, Molybdosilicate Method. 
 
Method 4500-Si E, Silica, Heteropoly Blue Method. 
 
Method 4500-Si F, Silica, Automated Method for 
Molybdate-Reactive Silica. 
 
Method 5910 B, UV Absorbing Organic Constituents, 
Ultraviolet Absorption Method. 
 
Method 6251 B, Disinfection Byproducts: Haloacetic Acids 
and Trichlorophenol, Micro Liquid-Liquid Extraction Gas 
 Chromatographic Method. 
 
 
 33
Method 6651, Glyphosate Herbicide (Proposed). 
 
Method 7110 B, Gross Alpha and Gross Beta 
Radioactivity, Evaporation Method for Gross Alpha-Beta. 
 
Method 7110 C, Gross Alpha and Beta Radioactivity 
(Total, Suspended, and Dissolved), Coprecipitation Method 
for Gross Alpha Radioactivity in Drinking Water 
(Proposed). 
 
Method 7120 B, Gamma-Emitting Radionuclides, Gamma 
Spectrometric Method. 
 
Method 7500-Cs B, Radioactive Cesium, Precipitation 
Method. 
 
Method 7500-3H B, Tritium, Liquid Scintillation 
Spectrometric Method. 
 
Method 7500-I B, Radioactive Iodine, Precipitation 
Method. 
 
Method 7500-I C, Radioactive Iodine, Ion-Exchange 
Method. 
 
Method 7500-I D, Radioactive Iodine, Distillation Method. 
 
Method 7500-Ra B, Radium, Precipitation Method. 
 
Method 7500-Ra C, Radium, Emanation Method. 
 
Method 7500-Ra D, Radium, Sequential Precipitation 
Method. 
 
Method 7500-Sr B, Total Radiactive Strontium and 
Strontium 90, Precipitation Method. 
 
Method 7500-U B, Uranium, Radiochemical Method. 
 
Method 7500-U C, Uranium, Isotopic Method. 
 
Method 9215 B, Heterotrophic Plate Count, Pour Plate 
Method. 
 
Method 9221 A, Multiple-Tube Fermentation Technique 
 for Members of the Coliform Group, Introduction. 
 
 34
 
Method 9221 B, Multiple-Tube Fermentation Technique 
for Members of the Coliform Group, Standard Total 
Coliform Fermentation Technique. 
 
Method 9221 C, Multiple-Tube Fermentation Technique 
for Members of the Coliform Group, Estimation of 
Bacterial Density. 
 
Method 9221 D, Multiple-Tube Fermentation Technique 
for Members of the Coliform Group, Presence-Absence (P-
A) Coliform Test. 
 
Method 9221 E, Multiple-Tube Fermentation Technique 
for Members of the Coliform Group, Fecal Coliform 
Procedure. 
 
Method 9222 A, Membrane Filter Technique for Members 
of the Coliform Group, Introduction. 
 
Method 9222 B, Membrane Filter Technique for Members 
of the Coliform Group, Standard Total Coliform Membrane 
Filter Procedure. 
 
Method 9222 C, Membrane Filter Technique for Members 
of the Coliform Group, Delayed-Incubation Total Coliform 
Procedure. 
 
Method 9222 D, Membrane Filter Technique for Members 
of the Coliform Group, Fecal Coliform Membrane Filter 
Procedure. 
 
Method 9223, Chromogenic Substrate Coliform Test 
(Proposed). 
 
“Supplement to the 19th Edition of Standard Methods for the 
Examination of Water and Wastewater,” American Public Health 
Association, 1996. 
 
Method 5310 B, TOC, Combustion-Infrared Method. 
 
Method 5310 C, TOC, Persulfate-Ultraviolet Oxidation 
Method. 
 
Method 5310 D, TOC, Wet-Oxidation Method. 
 
 
 35
“Standard Methods for the Examination of Water and 
Wastewater,” 20th Edition, 1998 (referred to as “Standard 
Methods, 20th ed.”). 
 
Method 2130 B, Turbidity, Nephelometric Method. 
 
Method 2320 B, Alkalinity, Titration Method. 
 
Method 2510 B, Conductivity, Laboratory Method. 
 
Method 2550, Temperature, Laboratory, and Field 
Methods. 
 
Method 3120 B, Metals by Plasma Emission Spectroscopy, 
Inductively Coupled Plasma (ICP) Method. 
 
Method 3500-Ca B, Calcium, EDTA Titrimetric Method. 
 
Method 3500-Mg B, Magnesium, EDTA Titrimetric 
Method. 
 
Method 4110 B, Determination of Anions by Ion 
Chromatography, Ion Chromatography with Chemical 
Suppression of Eluent Conductivity. 
 
Method 4500-CN
-
 C, Cyanide, Total Cyanide after 
Distillation. 
 
Method 4500-CN
-
 E, Cyanide, Colorimetric Method. 
 
Method 4500-CN
-
 F, Cyanide, Cyanide-Selective Electrode 
Method. 
 
Method 4500-CN
-
 G, Cyanide, Cyanides Amenable to 
Chlorination after Distillation. 
 
Method 4500-Cl D, Chlorine, Amperometric Titration 
 Method. 
 
Method 4500-Cl E, Chlorine, Low-Level Amperometric 
Titration Method. 
 
Method 4500-Cl F, Chlorine, DPD Ferrous Titrimetric 
Method. 
 
Method 4500-Cl G, Chlorine, DPD Colorimetric Method. 
 
 36
 
Method 4500-Cl H, Chlorine, Syringaldazine (FACTS) 
Method. 
 
Method 4500-Cl I, Chlorine, Iodometric Electrode Method. 
 
Method 4500-ClO2 C, Chlorine Dioxide, Amperometric 
Method I. 
 
Method 4500-ClO2 D, Chlorine Dioxide, DPD Method. 
 
Method 4500-ClO2 E, Chlorine Dioxide, Amperometric 
Method II (Proposed). 
 
Method 4500-F
-
 B, Fluoride, Preliminary Distillation Step. 
 
Method 4500-F
-
 C, Fluoride, Ion-Selective Electrode 
Method. 
 
Method 4500-F
-
 D, Fluoride, SPADNS Method. 
 
Method 4500-F
-
 E, Fluoride, Complexone Method. 
 
Method 4500-H
+
 B, pH Value, Electrometric Method. 
 
Method 4500-NO2
-
 B, Nitrogen (Nitrite), Colorimetric 
Method. 
 
Method 4500-NO3
-
 D, Nitrogen (Nitrate), Nitrate Electrode 
Method. 
 
Method 4500-NO3
-
 E, Nitrogen (Nitrate), Cadmium 
 Reduction Method. 
 
Method 4500-NO3
-
 F, Nitrogen (Nitrate), Automated 
Cadmium Reduction Method. 
 
Method 4500-O3 B, Ozone (Residual) (Proposed), Indigo 
Colorimetric Method. 
 
Method 4500-P E, Phosphorus, Ascorbic Acid Method. 
 
Method 4500-P F, Phosphorus, Automated Ascorbic Acid 
Reduction Method. 
 
Method 4500-Si C, Silica, Molybdosilicate Method. 
 
 37
 
Method 4500-Si D, Silica, Heteropoly Blue Method. 
 
Method 4500-Si E, Silica, Automated Method for 
Molybdate-Reactive Silica. 
 
Method 4500-Cl E, Chlorine (Residual), Low-Level 
Amperometric Titration Method. 
 
Method 4500-Cl F, Chlorine (Residual), DPD Ferrous 
Titrimetric Method. 
 
Method 4500-Cl G, Chlorine (Residual), DPD Colorimetric 
Method. 
 
Method 4500-Cl H, Chlorine (Residual), Syringaldazine 
(FACTS) Method. 
 
Method 4500-Cl I, Chlorine (Residual), Iodometric 
Electrode Technique. 
 
Method 4500-ClO2 D, Chlorine Dioxide, DPD Method. 
 
Method 4500-ClO2 E, Chlorine Dioxide, Amperometric 
Method II. 
 
Method 6651, Glyphosate Herbicide (Proposed). 
 
Method 7110-B, Gross Alpha and Gross Beta 
Radioactivity, Evaporation Method for Gross Alpha-Beta. 
 
Method 7110 C, Gross Alpha and Beta Radioactivity 
 (Total, Suspended, and Dissolved), Coprecipitation Method 
for Gross Alpha Radioactivity in Drinking Water 
(Proposed). 
 
Method 7120-B, Gamma-Emitting Radionuclides, Gamma 
Spectrometric Method. 
 
Method 7500-Cs B, Radioactive Cesium, Precipitation 
Method. 
 
Method 7500-3H B, Tritium, Liquid Scintillation 
Spectrometric Method. 
 
Method 7500-I B, Radioactive Iodine, Precipitation 
 
 38
Method. 
 
Method 7500-I C, Radioactive Iodine, Ion-Exchange 
Method. 
 
Method 7500-I D, Radioactive Iodine, Distillation Method. 
 
Method 7500-Ra B, Radium, Precipitation Method. 
 
Method 7500-Ra C, Radium, Emanation Method. 
 
Method 7500-Sr B, Total Radiactive Strontium and 
Strontium 90, Precipitation Method. 
 
Method 7500-U B, Uranium, Radiochemical Method. 
 
Method 7500-U C, Uranium, Isotopic Method. 
 
Method 9215 B, Heterotrophic Plate Count, Pour Plate 
Method. 
 
Method 9221 A, Multiple-Tube Fermentation Technique 
for Members of the Coliform Group, Introduction. 
 
Method 9221 B, Multiple-Tube Fermentation Technique 
for Members of the Coliform Group, Standard Total 
Coliform Fermentation Technique. 
 
Method 9221 C, Multiple-Tube Fermentation Technique 
for Members of the Coliform Group, Estimation of 
Bacterial Density. 
 
Method 9221 D, Multiple-Tube Fermentation Technique 
for Members of the Coliform Group, Presence-Absence (P-
A) Coliform Test. 
 
Method 9221 E, Multiple-Tube Fermentation Technique 
for Members of the Coliform Group, Fecal Coliform 
Procedure. 
 
Method 9222 A, Membrane Filter Technique for Members 
of the Coliform Group, Introduction. 
 
Method 9222 B, Membrane Filter Technique for Members 
of the Coliform Group, Standard Total Coliform Membrane 
Filter Procedure. 
 
 39
 
Method 9222 C, Membrane Filter Technique for Members 
of the Coliform Group, Delayed-Incubation Total Coliform 
Procedure. 
 
Method 9222 D, Membrane Filter Technique for Members 
of the Coliform Group, Fecal Coliform Membrane Filter 
Procedure. 
 
Method 9223, Chromogenic Substrate Coliform Test 
(Proposed). 
 
Analytical Technology, Inc.  ATI Orion, 529 Main Street, Boston, MA 
02129. 
 
Technical Bulletin 601, “Standard Method of Testing for Nitrate in 
Drinking Water,” July, 1994, PN 221890-001 (referred to as 
“Technical Bulletin 601”). 
 
ASTM.  American Society for Testing and Materials, 100 Barr Harbor 
Drive, West Conshohocken, PA 19428-2959 610-832-9585. 
 
ASTM Method D511-93 A and B, “Standard Test Methods for 
Calcium and Magnesium in Water,” “Test Method A--
Complexometric Titration” & “Test Method B--Atomic 
 Absorption Spectrophotometric,” approved 1993. 
 
ASTM Method D515-88 A, “Standard Test Methods for 
Phosphorus in Water,” “Test Method A--Colorimetric Ascorbic 
Acid Reduction,” approved August 19, 1988. 
 
ASTM Method D859-88, “Standard Test Method for Silica in 
Water,” approved August 19, 1988. 
 
ASTM Method D1067-92 B, “Standard Test Methods for Acidity 
or Alkalinity in Water,” “Test Method B--Electrometric or Color-
Change Titration,” approved May 15, 1992. 
 
ASTM Method D1125-91 A, “Standard Test Methods for 
Electrical Conductivity and Resistivity of Water,” “Test Method 
A--Field and Routine Laboratory Measurement of Static (Non-
Flowing) Samples,” approved June 15, 1991. 
 
ASTM Method D1179-93 B, “Standard Test Methods for Fluoride 
in Water,” “Test Method B--Ion Selective Electrode,” approved 
1993. 
 
 40
 
ASTM Method D1253-86, “Standard Test Method for Residual 
Chlorine in Water,” reapproved 1992. 
 
ASTM Method D1293-84, “Standard Test Methods for pH of 
Water,” “Test Method A--Precise Laboratory Measurement” & 
“Test Method B--Routine or Continuous Measurement,” approved 
October 26, 1984. 
 
ASTM Method D1688-90 A or C, “Standard Test Methods for 
Copper in Water,” “Test Method A--Atomic Absorption, Direct” & 
“Test Method C--Atomic Absorption, Graphite Furnace,” approved 
March 15, 1990. 
 
ASTM Method D2036-91 A or B, “Standard Test Methods for 
 Cyanide in Water,” “Test Method A--Total Cyanides after 
Distillation” & “Test Method B--Cyanides Amenable to 
Chlorination by Difference,” approved September 15, 1991. 
 
ASTM Method D2459-72, “Standard Test Method for Gamma 
Spectrometry in Water,” approved July 28, 1972, discontinued 
1988. 
 
ASTM Method D2460-90, “Standard Test Method for 
Radionuclides of Radium in Water,” approved 1990. 
 
ASTM Method D2907-91, “Standard Test Methods for 
Microquantities of Uranium in Water by Fluorometry,” “Test 
Method A--Direct Fluorometric” & “Test Method B—Extraction,” 
approved June 15, 1991. 
 
ASTM Method D2972-93 B or C, “Standard Test Methods for 
Arsenic in Water,” “Test Method B--Atomic Absorption, Hydride 
Generation” & “Test Method C--Atomic Absorption, Graphite 
Furnace,” approved 1993. 
 
ASTM Method D3223-91, “Standard Test Method for Total 
Mercury in Water,” approved September 23, 1991. 
 
ASTM Method D3454-91, “Standard Test Method for Radium-226 
in Water,” approved 1991. 
 
ASTM Method D3559-90 D, “Standard Test Methods for Lead in 
Water,” “Test Method D--Atomic Absorption, Graphite Furnace,” 
approved August 6, 1990. 
 
 
 41
ASTM Method D3645-93 B, “Standard Test Methods for 
Beryllium in Water,” “Method B--Atomic Absorption, Graphite 
Furnace,” approved 1993. 
 
ASTM Method D3649-91, “Standard Test Method for High-
 Resolution Gamma-Ray Spectrometry of Water,” approved 1991. 
 
ASTM Method D3697-92, “Standard Test Method for Antimony 
in Water,” approved June 15, 1992. 
 
ASTM Method D3859-93 A, “Standard Test Methods for 
Selenium in Water,” “Method A--Atomic Absorption, Hydride 
Method,” approved 1993. 
 
ASTM Method D3867-90 A and B, “Standard Test Methods for 
Nitrite-Nitrate in Water,” “Test Method A--Automated Cadmium 
Reduction” & “Test Method B--Manual Cadmium Reduction,” 
approved January 10, 1990. 
 
ASTM Method D3972-90, “Standard Test Method for Isotopic 
Uranium in Water by Radiochemistry,” approved 1990. 
 
ASTM Method D4107-91, “Standard Test Method for Tritium in 
Drinking Water,” approved 1991. 
 
ASTM Method D4327-91, “Standard Test Method for Anions in 
Water by Ion Chromatography,” approved October 15, 1991. 
 
ASTM Method D4785-88, “Standard Test Method for Low-Level 
Iodine-131 in Water,” approved 1988. 
 
ASTM Method D5174-91, “Standard Test Method for Trace 
Uranium in Water by Pulsed-Laser Phosphorimetry,” approved 
1991. 
 
ASTM Method D5673-03, “Standard Test Method for Elements in 
Water by Inductively Coupled Plasma—Mass Spectrometry,” 
approved 2003. 
 
ASTM Method D 1253-86, “Standard Test Method for Residual 
Chlorine in Water,” reapproved 1992. 
 
Bran & Luebbe, 1025 Busch Parkway, Buffalo Grove, IL 60089. 
 
 “Fluoride in Water and Wastewater,” Industrial Method #129-
71W, December 1972 (referred to as “Technicon Methods:  
 
 42
Method #129-71W”).  See 40 CFR 141.23(k)(1), footnote 11 
(2003). 
 
“Fluoride in Water and Wastewater,” #380-75WE, February 1976 
(referred to as “Technicon Methods:  Method #380-75WE”).  See 
40 CFR 141.23(k)(1), footnote 11 (2003). 
 
CPI International, Inc., 5580 Skylane Blvd. Santa Rosa, CA 95403.  
Telephone:  800-878-7654.  Fax:  707-545-7901.  Internet address:  
www.cpiinternational.com. 
 
“Colitag
®
 Product as a Test for Detection and Identification of 
Coliforms and E. coli Bacteria in Drinking Water and Source 
Water as Required in National Primary Drinking Water 
Regulations,” August 2001. 
 
EMD Chemicals Inc. (an affiliate of Merck KGgA, Darmstadt, Germany), 
480 S. Democrat Road, Gibbstown, NJ 08027–1297.  Telephone:  800-
222–0342.  E-mail:  adellenbusch@emscience.com. 
 
“Chromocult Coliform Agar Presence/Absence Membrane Filter 
Test Method for Detection and Identification of Coliform Bacteria 
and Escherichia coli in Finished Waters,” November 2000, 
Version 1.0
.
 
 
“Readycult Coliforms 100 Presence/Absence Test for Detection 
and Identification of Coliform Bacteria and Escherichia coli in 
Finished Waters,” November 2000, Version 1.0. 
 
ERDA Health and Safety Laboratory, New York, NY. 
 
HASL Procedure Manual, HASL 300, 1973.  See 40 CFR 
141.25(b)(2) (2003). 
 
Great Lakes Instruments, Inc., 8855 North 55th Street, Milwaukee, WI 
53223. 
 
GLI Method 2, “Turbidity,” Nov. 2, 1992. 
 
The Hach Company, P.O. Box 389, Loveland, CO 80539-0389.  Phone:  
800-227-4224. 
 
“Lead in Drinking Water by Differential Pulse Anodic Stripping 
Voltammetry,” Method 1001, August 1999. 
 
“Determination of Turbidity by Laser Nephelometry,” January 
 
 43
2000, Revision 2.0 (referred to as “Hach FilterTrak Method 
10133”). 
 
IDEXX Laboratories, Inc., One IDEXX Drive, Westbrook, Maine 04092.  
Telephone:  800-321–0207. 
 
“IDEXX SimPlate TM HPC Test Method for Heterotrophs in 
Water,” November 2000. 
 
Lachat Instruments, 6645 W. Mill Rd., Milwaukee, WI 53218.  Phone:  
414–358–4200. 
 
“Digestion and distillation of total cyanide in drinking and 
wastewaters using MICRO DIST and determination of cyanide by 
flow injection analysis,” Revision 2.1, November 30, 2000 
(referred to as “QuikChem Method 10-204-00-1-X”). 
 
Millipore Corporation, Technical Services Department, 80 Ashby Road, 
Milford, MA 01730 800-654-5476. 
 
Colisure Presence/Absence Test for Detection and Identification of 
Coliform Bacteria and Escherichia Coli in Drinking Water, 
February 28, 1994 (referred to as “Colisure Test”). 
 
NCRP.  National Council on Radiation Protection, 7910 Woodmont Ave., 
Bethesda, MD 301-657-2652. 
 
“Maximum Permissible Body Burdens and Maximum Permissible 
Concentrations of Radionuclides in Air and in Water for 
Occupational Exposure,” NCRP Report Number 22, June 5, 1959. 
 
NSF.  National Sanitation Foundation International, 3475 Plymouth Road, 
PO Box 130140, Ann Arbor, Michigan 48113-0140, 734-769-8010. 
 
NSF Standard 61, section 9, November 1998. 
 
NTIS.  National Technical Information Service, U.S. Department of 
Commerce, 5285 Port Royal Road, Springfield, VA 22161, 703-487-4600 
or 800-553-6847. 
 
“Interim Radiochemical Methodology for Drinking Water,” EPA 
600/4-75-008 (revised), March 1976 (referred to as “USEPA 
Interim Radiochemical Methods”).  (Pages 1, 4, 6, 9, 13, 16, 24, 
29, 34) 
 
“Kelada Automated Test Methods for Total Cyanide, Acid 
 
 44
Dissociable Cyanide, And Thiocyanate,” Revision 1.2, August 
2001, EPA # 821–B–01–009 (referred to as “Kelada 01”). 
 
“Maximum Permissible Body Burdens and Maximum Permissible 
Concentrations of Radionuclides in Air and in Water for 
Occupational Exposure,” NBS (National Bureau of Standards) 
Handbook 69, as amended August 1963, U.S. Department of 
Commerce. 
 
Method 100.1, “Analytical Method for Determination of Asbestos 
Fibers in Water,” EPA-600/4-83-043, September 1983, Doc. No. 
 PB83-260471 (referred to as “USEPA Asbestos Methods-100.1”). 
 
Method 100.2, “Determination of Asbestos Structures over 10-mm 
in Length in Drinking Water,” EPA-600/4-83-043, June 1994, 
Doc. No. PB94-201902 (referred to as “USEPA Asbestos 
Methods-100.2”). 
 
“Methods for Chemical Analysis of Water and Wastes,” March 
1983, Doc. No. PB84-128677 (referred to as “USEPA Inorganic 
Methods”).  (Methods 150.1, 150.2, and 245.2, which formerly 
appeared in this reference, are available from USEPA EMSL.) 
 
“Methods for the Determination of Inorganic Substances in 
Environmental Samples,” August 1993, PB94-120821 (referred to 
as “USEPA Environmental Inorganic Methods”). 
 
“Methods for the Determination of Metals in Environmental 
Samples,” June 1991, Doc. No. PB91-231498 and “Methods for 
the Determination of Metals in Environmental Samples--
Supplement I,” May 1994, PB95-125472 (referred to as “USEPA 
Environmental Metals Methods”). 
 
“Methods for the Determination of Organic Compounds in 
Drinking Water,” December 1988, revised July 1991, EPA-600/4-
88/039 (referred to as “USEPA Organic Methods”).  (For methods 
502.2, 505, 507, 508, 508A, 515.1, and 531.1.) 
 
“Methods for the Determination of Organic Compounds in 
Drinking Water--Supplement I,” July 1990, EPA/600-4-90-020 
(referred to as “USEPA Organic Methods”).  (For methods 506, 
547, 550, 550.1, and 551.) 
 
“Methods for the Determination of Organic Compounds in 
 Drinking Water--Supplement II,” August 1992, EPA-600/R-92-
129 (referred to as “USEPA Organic Methods”).  (For methods 
 
 45
515.2, 524.2, 548.1, 549.1, 552.1, and 555.) 
 
“Prescribed Procedures for Measurement of Radioactivity in 
Drinking Water,” EPA 600/4-80-032, August 1980 (document 
number PB 80-224744) (referred to as “USEPA Radioactivity 
Methods”).  (Methods 900, 901, 901.1, 902, 903, 903.1, 904, 905, 
906, 908, 908.1) 
 
“Procedures for Radiochemical Analysis of Nuclear Reactor 
Aqueous Solutions,” H.L. Krieger and S. Gold, EPA-R4-73-014, 
May 1973, Doc. No. PB222-154/7BA. 
 
“Radiochemical Analytical Procedures for Analysis of 
Environmental Samples,” March 1979, Doc. No. EMSL LV 
053917 (referred to as “USEPA Radiochemical Analyses”).  
(Pages 1, 19, 33, 65, 87, 92) 
 
“Radiochemistry Procedures Manual,” EPA-520/5-84-006, 
December 1987, Doc. No. PB-84-215581 (referred to as “USEPA 
Radiochemistry Methods”).  (Methods 00-01, 00-02, 00-07, H-02, 
Ra-03, Ra-04, Ra-05, Sr-04) 
 
“Technical Notes on Drinking Water Methods,” EPA-600/R-94-
173, October 1994, Doc. No. PB-104766 (referred to as “USEPA 
Technical Notes”). 
 
BOARD NOTE:  USEPA made the following assertion with 
regard to this reference at 40 CFR 141.23(k)(1) and 141.24(e) and 
(n)(11) (2003):  “This document contains other analytical test 
procedures and approved analytical methods that remain available 
 for compliance monitoring until July 1, 1996.” 
 
“Tetra- through Octa-Chlorinated Dioxins and Furans by Isotope 
Dilution HRGC/HRMS,” October 1994, EPA-821-B-94-005 
(referred to as “Dioxin and Furan Method 1613”). 
 
New Jersey Department of Environment, Division of Environmental 
Quality, Bureau of Radiation and Inorganic Analytical Services, 9 Ewing 
Street, Trenton, NJ 08625. 
 
“Determination of Radium 228 in Drinking Water,” August 1990. 
 
New York Department of Health, Radiological Sciences Institute, Center 
for Laboratories and Research, Empire State Plaza, Albany, NY 12201. 
 
“Determination of Ra-226 and Ra-228 (Ra-02),” January 1980, 
 
 46
Revised June 1982. 
 
Palintest, Ltd., 21 Kenton Lands Road, P.O. Box 18395, Erlanger, KY 
800-835-9629. 
 
“Lead in Drinking Water by Differential Pulse Anodic Stripping 
Voltammetry,” Method 1001, August 1999. 
 
Syngenta Crop Protection, Inc., 410 Swing Road, Post Office Box 18300, 
Greensboro, NC 27419.  Telephone:  336-632–6000. 
 
“Atrazine in Drinking Water by Immunoassay,” February 2001 
(referred to as “Syngenta AG-625”). 
 
United States Department of Energy, available at the Environmental 
Measurements Laboratory, U.S. Department of Energy, 376 Hudson 
Street, New York, NY 10014-3621. 
 
“EML Procedures Manual,” 27th Edition, Volume 1, 1990. 
 
United States Environmental Protection Agency, Office of Ground Water 
and Drinking Water, accessible on-line and available by download from 
http://www.epa.gov/safewater/methods/
.
 
 
Method 515.4, “Determination of Chlorinated Acids in Drinking 
Water by Liquid-Liquid Microextraction, Derivatization and Fast 
Gas Chromatography with Electron Capture Detection,” Revision 
1.0, April 2000, EPA 815/B–00/001 (document file name 
“met515_4.pdf”). 
 
Method 531.2, “Measurement of N-methylcarbamoyloximes and 
N-methylcarbamates in Water by Direct Aqueous Injection HPLC 
with Postcolumn Derivatization,” Revision 1.0, September 2001, 
EPA 815/B/01/002 (document file name “met531_2.pdf”). 
 
United States Environmental Protection Agency, EMSL, Cincinnati, OH 
45268 513-569-7586. 
 
“Interim Radiochemical Methodology for Drinking Water,” EPA-
600/4-75-008 (referred to as “Radiochemical Methods”).  
(Revised) March 1976. 
 
“Methods for the Determination of Organic Compounds in 
Finished Drinking Water and Raw Source Water” (referred to as 
“USEPA Organic Methods”).  (For methods 504.1, 508.1, and 
525.2 only.) See NTIS. 
 
 47
 
“Procedures for Radiochemical Analysis of Nuclear Reactor 
Aqueous Solutions.” See NTIS. 
 
USEPA, Science and Technology Branch, Criteria and Standards 
Division, Office of Drinking Water, Washington, D.C.  20460. 
 
“Guidance Manual for Compliance with the Filtration and 
 Disinfection Requirements for Public Water Systems using Surface 
Water Sources,” October 1989. 
 
USGS.  Books and Open-File Reports Section, United States Geological 
Survey, Federal Center, Box 25286, Denver, CO 80225-0425. 
 
Methods available upon request by method number from “Methods 
for Analysis by the U.S. Geological Survey National Water 
Quality Laboratory--Determination of Inorganic and Organic 
Constituents in Water and Fluvial Sediments,” Open File Report 
93-125, 1993, or Book 5, Chapter A-1, “Methods for 
Determination of Inorganic Substances in Water and Fluvial 
Sediments,” 3rd ed., Open-File Report 85-495, 1989, as 
appropriate (referred to as “USGS Methods”). 
 
I-1030-85 
 
I-1062-85 
 
I-1601-85 
 
I-1700-85 
 
I-2598-85 
 
I-2601-90 
 
I-2700-85 
 
I-3300-85 
 
Methods available upon request by method number from “Methods 
for Determination of Radioactive Substances in Water and Fluvial 
Sediments,” Chapter A5 in Book 5 of “Techniques of Water-
Resources Investigations of the United States Geological Survey,” 
1997. 
 
R-1110-76 
 
 48
 
R-1111-76 
 
R-1120-76 
 
R-1140-76 
 
R-1141-76 
 
R-1142-76 
 
R-1160-76 
 
 R-1171-76 
 
R-1180-76 
 
R-1181-76 
 
R-1182-76 
 
Waters Corporation, Technical Services Division, 34 Maple St., Milford, 
MA 01757 800-252-4752. 
 
“Waters Test Method for Determination of Nitrite/Nitrate in Water 
Using Single Column Ion Chromatography,” Method B-1011, 
August 1987 (referred to as “Waters Method B-1011”). 
 
c)      The Board incorporates the following federal regulations by reference: 
 
40 CFR 136, Appendices B and C (2003). 
 
d)      This Part incorporates no later amendments or editions. 
 
(Source:  Amended at 29 Ill. Reg. ________, effective ______________________) 
 
SUBPART B:  FILTRATION AND DISINFECTION 
 
Section 611.231       Source Water Quality Conditions 
 
The Agency must consider the following source water quality conditions in determining whether 
to require filtration pursuant to Section 611.211: 
 
a)      The fecal coliform concentration must be equal to or less than 20/100 ml, or the 
total coliform concentration must be equal to or less than 100/100 ml (measured 
as specified in Section 611.531(a) or (b) and 611.532(a)) in representative 
 
 49
samples of the source water immediately prior to the first or only point of 
disinfectant application in at least 90 percent of the measurements made for the 6 
previous months that the system served water to the public on an ongoing basis.  
 If a system measures both fecal and total coliforms, the fecal coliform criterion, 
but not the total coliform criterion, in this subsection, must be met. 
 
b)      The turbidity level cannot exceed 5 NTU (measured as specified in Section 
611.531(d) 611.531(a) and 611.532(b) in representative samples of the source 
water immediately prior to the first or only point of disinfectant application unless 
the following are true: 
 
1)      The Agency determines that any such event was caused by circumstances 
that were unusual and unpredictable; and 
 
2)      As a result of any such event there have not been more than two events in 
the past 12 months the system served water to the public, or more than 
five events in the past 120 months the system served water to the public, 
in which the turbidity level exceeded 5 NTU.  An “event” is a series of 
consecutive days during which at least one turbidity measurement each 
day exceeds 5 NTU. 
 
BOARD NOTE:  Derived from 40 CFR 141.71(a) (2002) (2003). 
 
c)      Each CWS must take its raw water from the best available source that is 
economically reasonable and technically possible. 
 
BOARD NOTE:  This is an additional State requirement. 
 
d)      Use of recycled sewage treatment plant effluent by a CWS on a routine basis must 
not be permitted. 
 
BOARD NOTE:  This is an additional State requirement. 
 
(Source:  Amended at 29 Ill. Reg. ________, effective ______________________) 
 
Section 611.233       Treatment Technique Violations 
 
a)      A supplier is in violation of a treatment technique requirement if the following is 
true: 
 
1)      Filtration is required because either of the following: 
 
A)      The supplier fails to meet any one of the criteria in Section 
611.231 and 611.232; or 
 
B)      The Agency has determined, pursuant to Section 611.211, that 
 
 50
filtration is required; and 
 
2)      The supplier fails to install filtration by the date specified in Section 
611.230. 
 
b)      A supplier that has not installed filtration is in violation of a treatment technique 
requirement if either of the following is true: 
 
1)      The turbidity level (measured as specified in Section 611.531(d) 
611.531(a) and 611.532(b)) in a representative sample of the source water 
immediately prior to the first or only point of disinfection application 
exceeds 5 NTU; or 
 
2)      The system is identified as a source of a waterborne disease outbreak. 
 
BOARD NOTE:  Derived from 40 CFR 141.71(c) (2002) (2003). 
 
(Source:  Amended at 29 Ill. Reg. ________, effective ______________________) 
 
Section 611.241       Unfiltered PWSs 
 
Each supplier that does not provide filtration treatment must provide disinfection treatment as 
follows: 
 
a)      The disinfection treatment must be sufficient to ensure at least 99.9 percent (3-
 log) inactivation of Giardia lamblia cysts and 99.99 percent (4-log) inactivation of 
viruses, every day the system serves water to the public, except any one day each 
month.  Each day a system serves water to the public, the supplier must calculate 
the CT99.9 value from the system’s treatment parameters using the procedure 
specified in Section 611.532(c) and determine whether this value is sufficient to 
achieve the specified inactivation rates for Giardia lamblia cysts and viruses. 
 
1)      If a system uses a disinfectant other than chlorine, the system may 
demonstrate to the Agency, through the use of an Agency-approved 
protocol for on-site disinfection challenge studies or other information, 
that CT99.9 values other than those specified in Appendix B of this Part, 
Tables 2.1 and 3.1 or other operational parameters are adequate to 
demonstrate that the system is achieving minimum inactivation rates 
required by this subsection. 
 
2)      The demonstration must be made by way of a SEP application pursuant to 
Section 611.110. 
 
b)      The disinfection system must have either of the following: 
 
1)      Redundant components, including an auxiliary power supply with 
 
 51
automatic start-up and alarm to ensure that disinfectant application is 
maintained continuously while water is being delivered to the distribution 
system; or 
 
2) 
 Automatic shut-off of delivery of water to the distribution system 
 whenever there is less than 0.2 mg/
ℓ
 of RDC in the water.  If the Agency 
determines, by a SEP issued pursuant to Section 611.110, that automatic 
shut-off would cause unreasonable risk to health or interfere with fire 
protection, the system must comply with subsection (b)(1). 
 
c) 
 The RDC in the water entering the distribution system, measured as specified in 
Sections 611.531(e) 611.531(b) and 611.532(e), cannot be less than 0.2 mg/
ℓ
 for 
more than 4 hours. 
 
d) 
 RDC in the distribution system. 
 
1) 
 The RDC in the distribution system, measured as total chlorine, combined 
chlorine or chlorine dioxide, as specified in Sections 611.531(e) 
611.531(b) and 611.532(f), cannot be undetectable in more than 5 percent 
of the samples each month for any two consecutive months that the system 
serves water to the public.  Water in the distribution system with HPC less 
than or equal to 500/ml, measured as specified in Section 611.531(c) 
611.531(a), is deemed to have a detectable RDC for purposes of 
determining compliance with this requirement.  Thus, the value “V” in the 
following formula cannot exceed 5 percent in one month, for any two 
consecutive months. 
 
(
)
(
)
 b
 a
e
 d
 c
 100
V
+
+
+
=
  
 
where the terms mean the following: 
 
a = 
 Number of instances where the RDC is measured; 
 
b = 
 Number of instances where the RDC is not measured, but 
HPC is measured; 
 
c = 
 Number of instances where the RDC is measured but not 
detected and no HPC is measured; 
 
d = 
 Number of instances where the RDC is measured but not 
detected, and where the HPC is greater than 500/ml; and 
 
e = 
 Number of instances where the RDC is not measured and 
HPC is greater than 500/ml. 
 
 52
 
2)      Subsection (d)(1) does not apply if the Agency determines, pursuant to 
Section 611.213, that a supplier has no means for having a sample 
analyzed for HPC by a certified laboratory under the requisite time and 
temperature conditions specified by Section 611.531(a) and that the 
supplier is providing adequate disinfection in the distribution system. 
 
BOARD NOTE:  Derived from 40 CFR 141.72(a) (2003). 
 
(Source:  Amended at 29 Ill. Reg. ________, effective ______________________) 
 
Section 611.242       Filtered PWSs 
 
Each supplier that provides filtration treatment must provide disinfection treatment as follows: 
 
a)      The disinfection treatment must be sufficient to ensure that the total treatment 
processes of that system achieve at least 99.9 percent (3-log) inactivation or 
removal of Giardia lamblia cysts and at least 99.99 percent (4-log) inactivation or 
 removal of viruses. 
 
b)      The RDC in the water entering the distribution system, measured as specified in 
Section 611.531(e) 611.531(b) and 611.533(b), cannot be less than 0.2 mg/
ℓ
 for 
more than 4 hours. 
 
c)      RDC in the distribution system. 
 
1)      The RDC in the distribution system, measured as total chlorine, combined 
chlorine, or chlorine dioxide, as specified in Section 611.531(e) 
611.531(b) and 611.533(c), cannot be undetectable in more than 5 percent 
of the samples each month, for any two consecutive months that the 
system serves water to the public.  Water in the distribution system with 
HPC less than or equal to 500/ml, measured as specified in Section 
611.531(c) 611.531(a), is deemed to have a detectable RDC for purposes 
of determining compliance with this requirement.  Thus, the value “V” in 
the following formula cannot exceed 5 percent in one month, for any two 
consecutive months. 
 
V = 100(c + d + e) / (a + b) 
 
where the terms mean the following: 
 
a =     Number of instances where the RDC is measured; 
 
b =     Number of instances where the RDC is not measured, but 
HPC is measured; 
 
 
 53
c =     Number of instances where the RDC is measured but not 
detected and no HPC is measured; 
 
d =     Number of instances where the RDC is measured but not 
detected, and where HPC is greater than 500/ml; and 
 
e =     Number of instances where the RDC is not measured and 
HPC is greater than 500/ml. 
 
2)      Subsection (c)(1) does not apply if the Agency determines, pursuant to 
Section 611.213, that a supplier has no means for having a sample 
analyzed for HPC by a certified laboratory under the requisite time and 
temperature conditions specified by Section 611.531(a) and that the 
supplier is providing adequate disinfection in the distribution system. 
 
BOARD NOTE:  Derived from 40 CFR 141.72(b) (2003). 
 
(Source:  Amended at 29 Ill. Reg. ________, effective ______________________) 
 
Section 611.250       Filtration 
 
A supplier that uses a surface water source or a groundwater source under the direct influence of 
surface water, and does not meet all of the criteria in Sections 611.231 and 611.232 for avoiding 
filtration, must have provided treatment consisting of both disinfection, as specified in Section 
611.242, and filtration treatment that complies with the requirements of subsection (a), (b), (c), 
(d), or (e) by June 29, 1993, or within 18 months after the failure to meet any one of the criteria 
for avoiding filtration in Sections 611.231 and 611.232, whichever is later.  Failure to meet any 
requirement after the date specified in this introductory paragraph is a treatment technique 
violation. 
 
a)      Conventional filtration treatment or direct filtration. 
 
1)      For a system using conventional filtration or direct filtration, the turbidity 
level of representative samples of the system’s filtered water must be less 
than or equal to 0.5 NTU in at least 95 percent of the measurements taken 
each month, measured as specified in Section 611.531(a) and 611.533(a), 
except that if the Agency determines, by a SEP issued pursuant to Section 
611.110, that the system is capable of achieving at least 99.9 percent 
removal or inactivation of Giardia lamblia cysts at some turbidity level 
higher than 0.5 NTU in at least 95 percent of the measurements taken each 
month, the Agency must substitute this higher turbidity limit for that 
system.  However, in no case may the Agency approve a turbidity limit 
that allows more than 1 NTU in more than five percent of the samples 
taken each month, measured as specified in Section 611.531(a) and 
611.533(a). 
 
 
 54
2)      The turbidity level of representative samples of a system’s filtered water 
must at no time exceed 5 NTU. 
 
3)      Beginning January 1, 2001, a supplier serving at least 10,000 or more 
persons must meet the turbidity requirements of Section 611.743(a). 
 
4)      Beginning January 1, 2005, a supplier that serves fewer than 10,000 
people must meet the turbidity requirements in Section 611.955. 
 
b)      Slow sand filtration. 
 
1)      For a system using slow sand filtration, the turbidity level of 
representative samples of the system’s filtered water must be less than or 
equal to 1 NTU in at least 95 percent of the measurements taken each 
 month, measured as specified in Section 611.531(a) and 611.533(a), 
except that if the Agency determines, by a SEP issued pursuant to Section 
611.110, that there is no significant interference with disinfection at a 
higher level, the Agency must substitute the higher turbidity limit for that 
system. 
 
2)      The turbidity level of representative samples of a system’s filtered water 
must at no time exceed 5 NTU, measured as specified in Section 
611.531(a) and 611.533(a). 
 
c)      Diatomaceous earth filtration. 
 
1)      For a system using diatomaceous earth filtration, the turbidity level of 
representative samples of the system’s filtered water must be less than or 
equal to 1 NTU in at least 95 percent of the measurements taken each 
month, measured as specified in Section 611.531(a) and 611.533(a). 
 
2)      The turbidity level of representative samples of a system’s filtered water 
must at no time exceed 5 NTU, measured as specified in Section 
611.531(a) and 611.533(a). 
 
d)      Other filtration technologies.  A supplier may use a filtration technology not listed 
in subsections (a) through (c) if it demonstrates, by a SEP application pursuant to 
Section 611.110, to the Agency, using pilot plant studies or other means, that the 
alternative filtration technology, in combination with disinfection treatment that 
meets the requirements of Section 611.242, consistently achieves 99.9 percent 
removal or inactivation of Giardia lamblia cysts and 99.99 percent removal or 
 inactivation of viruses.  For a supplier that makes this demonstration, the 
requirements of subsection (b) apply.  Beginning January 1, 2002, a supplier 
serving 10,000 or more persons must meet the requirements for other filtration 
technologies in Section 611.743(b).  Beginning January 1, 2005, a supplier that 
serves fewer than 10,000 people must meet the requirements for other filtration 
 
 55
technologies in Section 611.955. 
 
BOARD NOTE:  Derived from 40 CFR 141.73 (2003). 
 
(Source:  Amended at 29 Ill. Reg. ________, effective ______________________) 
 
Section 611.261       Unfiltered PWSs:  Reporting and Recordkeeping 
 
A supplier that uses a surface water source and does not provide filtration treatment must report 
monthly to the Agency the information specified in this Section beginning December 31, 1990, 
unless the Agency has determined that filtration is required, in which case the Agency must, by a 
SEP issued pursuant to Section 611.110, specify alternative reporting requirements, as 
appropriate, until filtration is in place.  A supplier that uses a groundwater source under the 
direct influence of surface water and does not provide filtration treatment must report monthly to 
the Agency the information specified in this Section beginning December 31, 1990, or six 
months after the Agency determines that the groundwater source is under the direct influence of 
surface water, whichever is later, unless the Agency has determined that filtration is required, in 
which case the Agency must, by a SEP issued pursuant to Section 611.110, specify alternative 
 reporting requirements, as appropriate, until filtration is in place. 
 
a)      Source water quality information must be reported to the Agency within ten days 
after the end of each month the system serves water to the public.  Information 
that must be reported includes the following: 
 
1)      The cumulative number of months for which results are reported. 
 
2)      The number of fecal or total coliform samples, whichever are analyzed 
during the month (if a system monitors for both, only fecal coliforms must 
be reported), the dates of sample collection, and the dates when the 
turbidity level exceeded 1 NTU. 
 
3)      The number of samples during the month that had equal to or fewer than 
20/100 ml fecal coliforms or equal to or fewer than 100/100 ml total 
coliforms, whichever are analyzed. 
 
4)      The cumulative number of fecal or total coliform samples, whichever are 
analyzed, during the previous six months the system served water to the 
public. 
 
5)      The cumulative number of samples that had equal to or fewer than 20/100 
ml fecal coliforms or equal to or fewer than 100/100 ml total coliforms, 
whichever are analyzed, during the previous six months the system served 
water to the public. 
 
6)      The percentage of samples that had equal to or fewer than 20/100 ml fecal 
coliforms or equal to or fewer than 100/100 ml total coliforms, whichever 
 
 56
are analyzed, during the previous six months the system served water to 
 the public. 
 
7)      The maximum turbidity level measured during the month, the dates of 
occurrence for any measurements that exceeded 5 NTU and the dates the 
occurrences were reported to the Agency. 
 
8)      For the first 12 months of recordkeeping, the dates and cumulative number 
of events during which the turbidity exceeded 5 NTU, and after one year 
of recordkeeping for turbidity measurements, the dates and cumulative 
number of events during which the turbidity exceeded 5 NTU in the 
previous 12 months the system served water to the public. 
 
9)      For the first 120 months of recordkeeping, the dates and cumulative 
number of events during which the turbidity exceeded 5 NTU, and after 
ten years of recordkeeping for turbidity measurements, the dates and 
cumulative number of events during which the turbidity exceeded 5 NTU 
in the previous 120 months the system served water to the public. 
 
b)      Disinfection information specified in Section 611.532 must be reported to the 
Agency within ten days after the end of each month the system serves water to the 
public.  Information that must be reported includes the following: 
 
1)      For each day, the lowest measurement of RDC in mg/
ℓ
 in water entering 
the distribution system. 
 
2)      The date and duration of each period when the RDC in water entering the 
distribution system fell below 0.2 mg/
ℓ
 and when the Agency was notified 
 of the occurrence. 
 
3)      The daily RDCs (in mg/
ℓ
) and disinfectant contact times (in minutes) used 
for calculating the CT values. 
 
4)      If chlorine is used, the daily measurements of pH of disinfected water 
following each point of chlorine disinfection. 
 
5)      The daily measurements of water temperature in degrees C following each 
point of disinfection. 
 
6)      The daily CTcalc and Ai values for each disinfectant measurement or 
sequence and the sum of all Ai values (B) before or at the first customer. 
 
7)      The daily determination of whether disinfection achieves adequate Giardia 
cyst and virus inactivation, i.e., whether Ai is at least 1.0 or, where 
disinfectants other than chlorine are used, other indicator conditions that 
the Agency, pursuant to Section 611.241(a)(1), determines are 
 
 57
appropriate, are met. 
 
8) 
 The following information on the samples taken in the distribution system 
in conjunction with total coliform monitoring pursuant to Section 611.240 
through 611.242: 
 
A) 
 Number of instances where the RDC is measured; 
 
B) 
 Number of instances where the RDC is not measured but HPC is 
measured; 
 
C) 
 Number of instances where the RDC is measured but not detected 
and no HPC is measured; 
 
D) 
 Number of instances where no RDC is detected and where HPC is 
 greater than 500/ml; 
 
E) 
 Number of instances where the RDC is not measured and HPC is 
greater than 500/ml; 
 
F) 
 For the current and previous month the system served water to the 
public, the value of “V” in the following formula: 
 
(
 )
(
 )
V=
100 c + d + e
a+ b
 
 
where the terms mean the following: 
 
a = 
 Value in subsection (b)(8)(A) of this Section; 
 
b = 
 Value in subsection (b)(8)(B) of this Section; 
 
c = 
 Value in subsection (b)(8)(C) of this Section; 
 
d = 
 Value in subsection (b)(8)(D) of this Section; and 
 
e = 
 Value in subsection (b)(8)(E) of this Section. 
 
G) 
 The requirements of subsections (b)(8)(A) through (b)(8)(F) of this 
Section do not apply if the Agency determines, pursuant to Section 
611.213, that a system has no means for having a sample analyzed 
for HPC by a certified laboratory under the requisite time and 
temperature conditions specified by Section 611.531(a) and that 
the supplier is providing adequate disinfection in the distribution 
system. 
 
 58
 
9)      A system need not report the data listed in subsections (b)(1) and (b)(3) 
through (b)(6) of this Section, if all data listed in subsections (b)(1) 
through (b)(8) of this Section remain on file at the system, and the Agency 
 determines, by a SEP issued pursuant to Section 611.110, that the 
following is true: 
 
A)      The system has submitted to the Agency all the information 
required by subsections (b)(1) through (b)(8) of this Section for at 
least 12 months; and 
 
B)      The Agency has determined that the system is not required to 
provide filtration treatment. 
 
c)      By October 10 of each year, each system must provide to the Agency a report that 
summarizes its compliance with all watershed control program requirements 
specified in Section 611.232(b). 
 
d)      By October 10 of each year, each system must provide to the Agency a report on 
the on-site inspection conducted during that year pursuant to Section 611.232(c), 
unless the on-site inspection was conducted by the Agency.  If the inspection was 
conducted by the Agency, the Agency must provide a copy of its report to the 
supplier. 
 
e)      Reporting health threats. 
 
1)      Each system, upon discovering that a waterborne disease outbreak 
potentially attributable to that water system has occurred, must report that 
occurrence to the Agency as soon as possible, but no later than by the end 
of the next business day. 
 
2)      If at any time the turbidity exceeds 5 NTU, the system must consult with 
the Agency as soon as practical, but no later than 24 hours after the 
exceedence is known, in accordance with the public notification 
requirements under Section 611.903(b)(3). 
 
3)      If at any time the RDC falls below 0.2 mg/
ℓ
 in the water entering the 
distribution system, the system must notify the Agency as soon as 
possible, but no later than by the end of the next business day.  The system 
also must notify the Agency by the end of the next business day whether 
or not the RDC was restored to at least 0.2 mg/
ℓ
 within four hours. 
 
BOARD NOTE:  Derived from 40 CFR 141.75(a) (2002) (2003). 
 
(Source:  Amended at 29 Ill. Reg. ________, effective ______________________) 
 
 
 59
Section 611.262       Filtered PWSs:  Reporting and Recordkeeping 
 
A supplier that uses a surface water source or a groundwater source under the direct influence of 
surface water and provides filtration treatment must report monthly to the Agency the 
information specified in this Section. 
 
a)      Turbidity measurements as required by Section 611.533(a) must be reported 
within ten days after the end of each month the supplier serves water to the 
public.  Information that must be reported includes the following: 
 
1)      The total number of filtered water turbidity measurements taken during 
the month. 
 
2)      The number and percentage of filtered water turbidity measurements taken 
during the month that are less than or equal to the turbidity limits specified 
in Section 611.250 for the filtration technology being used. 
 
3)      The date and value of any turbidity measurements taken during the month 
that exceed 5 NTU. 
 
b)      Disinfection information specified in Section 611.533 must be reported to the 
Agency within ten days after the end of each month the supplier serves water to 
the public.  Information that must be reported includes the following: 
 
1)      For each day, the lowest measurement of RDC in mg/
ℓ
 in water entering 
the distribution system. 
 
2)      The date and duration of each period when the RDC in water entering the 
distribution system fell below 0.2 mg/
ℓ
 and when the Agency was notified 
of the occurrence. 
 
3)      The following information on the samples taken in the distribution system 
in conjunction with total coliform monitoring pursuant to Sections 
611.240 through 611.242: 
 
A)      Number of instances where the RDC is measured; 
 
B)      Number of instances where the RDC is not measured but HPC is 
measured; 
 
C)      Number of instances where the RDC is measured but not detected 
and no HPC is measured; 
 
D)      Number of instances where no RDC is detected and where HPC is 
greater than 500/ml; 
 
 
 60
E) 
 Number of instances where the RDC is not measured and HPC is 
greater than 500/ml; 
 
F) 
 For the current and previous month the supplier serves water to the 
 public,the value of “V” in the following formula: 
 
(
 )
(
 )
V=
1 0 0 c +d +e
a
 b
 +
 
 
where the terms mean the following: 
 
a = 
 Value in subsection (b)(3)(A) of this 
Section; 
 
b = 
 Value in subsection (b)(3)(B) of this 
Section; 
 
c = 
 Value in subsection (b)(3)(C) of this 
Section; 
 
d = 
 Value in subsection (b)(3)(D) of this 
Section; and 
 
e = 
 Value in subsection (b)(3)(E) of this 
Section. 
 
G) 
 Subsections (b)(3)(A) through (b)(3)(F) of this Section do not 
apply if the Agency determines, pursuant to Section 611.213, that a 
supplier has no means for having a sample analyzed for HPC by a 
certified laboratory under the requisite time and temperature 
conditions specified by Section 611.531(a) and that the supplier is 
providing adequate disinfection in the distribution system. 
 
c) 
 Reporting health threats. 
 
1) 
 Each supplier, upon discovering that a waterborne disease outbreak 
potentially attributable to that water system has occurred, must report that 
occurrence to the Agency as soon as possible, but no later than by the end 
of the next business day. 
 
2) 
 If at any time the turbidity exceeds 5 NTU, the supplier must consult with 
 the Agency as soon as practical, but no later than 24 hours after the 
exceedence is known, in accordance with the public notification 
requirements under Section 611.903(b)(3). 
 
 
 61
3)      If at any time the residual falls below 0.2 mg/
ℓ
 in the water entering the 
distribution system, the supplier must notify the Agency as soon as 
possible, but no later than by the end of the next business day. The 
supplier also must notify the Agency by the end of the next business day 
whether or not the residual was restored to at least 0.2 mg/
ℓ
 within four 
hours. 
 
BOARD NOTE:  Derived from 40 CFR 141.75(b) (2002) (2003). 
 
(Source:  Amended at 29 Ill. Reg. ________, effective ______________________) 
 
SUBPART F:  MAXIMUM CONTAMINANT LEVELS (MCLs) AND 
MAXIMUM RESIDUAL DISINFECTANT LEVELS (MRDLs) 
 
Section 611.301       Revised MCLs for Inorganic Chemical Contaminants 
 
a)      This subsection corresponds with 40 CFR 141.62(a), reserved by USEPA.  This 
statement maintains structural consistency with USEPA rules. 
 
b)      The MCLs in the following table apply to CWSs.  Except for fluoride, the MCLs 
also apply to NTNCWSs.  The MCLs for nitrate, nitrite, and total nitrate and 
nitrite also apply to transient non-CWSs. 
 
Contaminant MCL 
 Units 
Antimony 0.006 
 mg/
ℓ
 
Arsenic (effective 
 January 23, 2006) 
0.010 mg/
ℓ
 
Asbestos 7 
 MFL 
Barium 2 
 mg/
ℓ
 
Beryllium 0.004 
 mg/
ℓ
 
Cadmium 0.005 
 mg/
ℓ
 
Chromium 0.1 
 mg/
ℓ
 
Cyanide (as free CN
-
) 0.2 mg/
ℓ
 
Fluoride 4.0 
 mg/
ℓ
 
Mercury 0.002 
 mg/
ℓ
 
Nitrate (as N) 
 10 
 mg/
ℓ
 
Nitrite (as N) 
 1 
 mg/
ℓ
 
Total Nitrate and Nitrite 
(as N) 
10 mg/
ℓ
 
Selenium 0.05 
 mg/
ℓ
 
Thallium 0.002 
 mg/
ℓ
 
 
BOARD NOTE:  See Section 611.300(d) for an elevated nitrate level for 
non-CWSs.  USEPA removed and reserved the MCL for nickel on June 
29, 1995, at 60 Fed. Reg. 33932, as a result of a judicial order in Nickel 
Development Institute v. EPA, No. 92-1407, and Specialty Steel Industry 
 
 62
of the U.S. v. Browner, No. 92-1410 (D.C. Cir. Feb. 23 & Mar. 6, 1995), 
while retaining the contaminant, analytical methodology, and detection 
limit listings for this contaminant. 
 
c)      USEPA has identified the following as BAT for achieving compliance with the 
MCL for the IOCs identified in subsection (b) of this Section, except for fluoride: 
 
Contaminant BATs 
 
  
Antimony C/F 
RO 
 
  
Arsenic 
(BATs for 
As
V
.  Pre-
oxidation 
may be 
required to 
convert As
III
 
to As
V
.) 
AAL 
C/F 
IX 
LIME 
RO 
ED 
O/F (To obtain high removals, the iron to arsenic ratio 
must be at least 20:1) 
 
  
Asbestos C/F 
DDF 
CC 
 
  
Barium IX 
LIME 
RO 
ED 
 
  
Beryllium AA 
C/F 
IX 
LIME 
RO 
 
  
Cadmium C/F 
IX 
LIME 
RO 
 
  
Chromium C/F 
IX 
LIME, BAT for Cr
III
 only 
RO 
 
  
 
 63
Cyanide IX 
RO 
ALK Cl2
 
  
Mercury 
 C/F, BAT only if influent Hg concentrations less than or 
equal to 10 μg/
ℓ
 
GAC 
 LIME, BAT only if influent Hg concentrations less than 
or equal to 10 μg/
ℓ
 
RO, BAT only if influent Hg concentrations less than or 
equal to 10 μg/
ℓ
 
 
  
Nickel IX 
LIME 
RO 
 
  
Nitrate IX 
RO 
ED 
 
  
Nitrite IX 
RO 
 
  
Selenium AAL 
C/F, BAT for Se
IV
 only 
LIME 
RO 
ED 
 
  
Thallium AAL 
IX 
 
Abbreviations 
 
AAL Activated alumina 
ALK Cl2       Alkaline chlorination (pH 
≥
 8.5) 
C/F            Coagulation/filtration (not BAT for a system that 
has fewer than 500 service connections) 
CC Corrosion control 
Cl2 Oxidation (chlorine) 
DDF          Direct and diatomite filtration 
ED Electrodialysis 
GAC          Granular activated carbon 
IX Ion exchange 
LIME Lime softening 
O/F Oxidation/filtration 
 
 64
RO Reverse osmosis 
CC 
 Corrosion control 
ED 
 Electrodialysis 
Cl2 
 Oxidation (chlorine) 
UV Ultraviolet irradiation 
O/F 
 Oxidation/filtration 
 
d)      At 40 CFR 141.62(d) (2003), USEPA identified the following as the affordable 
 technology, treatment technique, or other means available to systems serving 
10,000 persons or fewer for achieving compliance with the maximum 
contaminant level for arsenic: 
 
Small System Compliance Technologies (SSCTs)
1
 for Arsenic
2
Small system compliance technology 
Affordable for listed small system 
categories
3
Activated alumina (centralized) 
 All size categories 
Activated alumina (point-of-use)
4
All size categories 
Coagulation/filtration
5
501-3,300 persons, 3,301-10,000 persons 
Coagulation-assisted microfiltration 
 501-3,300 persons, 3,301-10,000 persons 
Electrodialysis reversal
6
501-3,300 persons, 3,301-10,000 persons 
Enhanced coagulation/filtration 
 All size categories 
Enhanced lime softening (pH> 10.5) 
 All size categories 
Ion exchange 
 All size categories 
Lime softening
5
501-3,300 persons, 3,301-10,000 persons 
Oxidation/filtration
7
All size categories 
Reverse osmosis (centralized)
6
501-3,300 persons, 3,301-10,000 persons 
Reverse osmosis (point-of-use)
4
All size categories 
 
1
    Section 1412(b)(4)(E)(ii) of the federal SDWA (42 USC 300g-1(b)(4)(E)(ii)) 
 specifies that SSCTs must be affordable and technically feasible for a small 
system supplier. 
 
2
    SSCTs for As
V
.  Pre-oxidation may be required to convert As
III
 to As
V
. 
 
3
    The federal SDWA specifies three categories of small system suppliers:  (1) 
those serving 25 or more, but fewer than 501 persons, (2) those serving more 
than 500 but fewer than 3,301 persons, and (3) those serving more than 3,300 
but fewer than 10,001 persons. 
 
4
    When POU or POE devices are used for compliance, programs to ensure 
proper long-term operation, maintenance, and monitoring must be provided by 
the water supplier to ensure adequate performance. 
 
5
    Unlikely to be installed solely for arsenic removal.  May require pH 
adjustment to optimal range if high removals are needed. 
 
 
 65
6
    Technologies reject a large volume of water--may not be appropriate for areas 
where water quantity may be an issue. 
 
7
    To obtain high removals, iron to arsenic ratio must be at least 20:1. 
 
BOARD NOTE:  Derived from 40 CFR 141.62 (2003). 
 
(Source:  Amended at 29 Ill. Reg. ________, effective ______________________) 
 
SUBPART I:  DISINFECTANT RESIDUALS, DISINFECTION BYPRODUCTS, AND 
DISINFECTION BYPRODUCT PRECURSORS 
 
Section 611.382       Monitoring Requirements 
 
a) General requirements. 
 
1)      A supplier must take all samples during normal operating conditions. 
 
2)      A supplier may consider multiple wells drawing water from a single aquifer 
as one treatment plant for determining the minimum number of TTHM and 
HAA5 samples required with Agency approval. 
 
3)      Failure to monitor in accordance with the monitoring plan required under 
subsection (f) of this Section is a monitoring violation. 
 
4)      Where compliance is based on a running annual average of monthly or 
quarterly samples or averages and the supplier’s failure to monitor makes it 
impossible to determine compliance with MCLs or MRDLs, this failure to 
monitor will be treated as a violation for the entire period covered by the 
annual average. 
 
5)      A supplier must use only data collected under the provisions of this Subpart 
I or under the Information Collection Rule (40 CFR 141, Subpart M) to 
qualify for reduced monitoring. 
 
b)      Monitoring requirements for disinfection byproducts (DBPs). 
 
1)      TTHMs and HAA5. 
 
A)      Routine monitoring.  A supplier must monitor at the following 
frequency: 
 
i)       A Subpart B system supplier that serves 10,000 or more 
persons must collect four water samples per quarter per 
treatment plant.  At least 25 percent of all samples collected 
 each quarter must be collected at locations representing 
 
 66
maximum residence time.  The remaining samples may be 
taken at locations representative of at least average 
residence time in the distribution system and representing 
the entire distribution system, taking into account the 
number of persons served, the different sources of water, 
and the different treatment methods. 
 
ii)      A Subpart B system supplier that serves from 500 to 9,999 
persons must collect one water sample per quarter per 
treatment plant.  The samples must be collected from 
locations representing maximum residence time. 
 
iii)     A Subpart B system supplier that serves fewer than 500 
persons must collect one sample per year per treatment 
plant during month of warmest water temperature.  The 
samples must be collected from locations representing 
maximum residence time.  If the sample (or average of 
annual samples, if more than one sample is taken) exceeds 
the MCL, the supplier must increase the monitoring 
frequency to one sample per treatment plant per quarter, 
taken at a point reflecting the maximum residence time in 
the distribution system, until the supplier meets the 
standards in subsection (b)(1)(D) of this Section. 
 
iv)     A supplier that uses only groundwater not under direct 
influence of surface water, which uses chemical 
disinfectant, and which serves 10,000 or more persons must 
collect one water sample per quarter per treatment plant.  
 The samples must be collected from locations representing 
maximum residence time. 
 
v)      A supplier that uses only groundwater not under direct 
influence of surface water, which uses chemical 
disinfectant, and which serves fewer than 10,000 persons 
must collect one sample per year per treatment plant during 
month of warmest water temperature.  The samples must be 
collected from locations representing maximum residence 
time.  If the sample (or average of annual samples, if more 
than one sample is taken) exceeds MCL, the supplier must 
increase monitoring to one sample per treatment plant per 
quarter, taken at a point reflecting the maximum residence 
time in the distribution system, until the supplier meets 
standards in subsection (b)(1)(D) of this Section. 
 
BOARD NOTE:  If a supplier elects to sample more frequently 
than the minimum required, at least 25 percent of all samples 
 
 67
collected each quarter (including those taken in excess of the 
required frequency) must be taken at locations that represent the 
maximum residence time of the water in the distribution system.  
The remaining samples must be taken at locations representative of 
at least average residence time in the distribution system.  For a 
supplier using groundwater not under the direct influence of 
surface water, multiple wells drawing water from a single aquifer 
may be considered one treatment plant for determining the 
minimum number of samples required, with Agency approval. 
 
B)      A supplier may reduce monitoring, except as otherwise provided, in 
accordance with the following: 
 
i)       A Subpart B system supplier that serves 10,000 or more 
persons and which has a source water annual average TOC 
level, before any treatment, of less than or equal to 4.0 
mg/
ℓ
 may reduce monitoring if it has monitored for at least 
one year and its TTHM annual average is less than or equal 
to 0.040 mg/
ℓ
 and HAA5 annual average is less than or 
equal to 0.030 mg/
ℓ
.  The reduced monitoring allowed is a 
minimum of one sample per treatment plant per quarter at a 
distribution system location reflecting maximum residence 
time. 
 
ii)      A Subpart B system supplier that serves from 500 to 9,999 
persons and which has a source water annual average TOC 
level, before any treatment, of less than or equal to 4.0 
mg/
ℓ
 may reduce monitoring if it has monitored at least one 
year and its TTHM annual average is less than or equal to 
0.040 mg/
ℓ
 and HAA5 annual average is less than or equal 
to 0.030 mg/
ℓ
.  The reduced monitoring allowed is a 
minimum of one sample per treatment plant per year at a 
distribution system location reflecting maximum residence 
time during month of warmest water temperature. 
 
BOARD NOTE:  Any Subpart B system supplier serving 
 fewer than 500 persons may not reduce its monitoring to 
less than one sample per treatment plant per year. 
 
iii)     A supplier using only groundwater not under direct 
influence of surface water using chemical disinfectant and 
serving 10,000 or more persons may reduce monitoring if it 
has monitored at least one year and its TTHM annual 
average is less than or equal to 0.040 mg/
ℓ
 and HAA5 
annual average is less than or equal to 0.030 mg/
ℓ
.  The 
reduced monitoring allowed is a minimum of one sample 
 
 68
per treatment plant per year at a distribution system 
location reflecting maximum residence time during month 
of warmest water temperature. 
 
iv)     A supplier using only groundwater not under direct 
influence of surface water using chemical disinfectant and 
serving fewer than 10,000 persons may reduce monitoring 
if it has monitored at least one year and its TTHM annual 
average is less than or equal to 0.040 mg/
ℓ
 and HAA5 
annual average is less than or equal to 0.030 mg/
ℓ
 for two 
consecutive years or TTHM annual average is less than or 
equal to 0.020 mg/
ℓ
 and HAA5 annual average is less than 
or equal to 0.015 mg/
ℓ
 for one year.  The reduced 
monitoring allowed is a minimum of one sample per 
treatment plant per three year monitoring cycle at a 
 distribution system location reflecting maximum residence 
time during month of warmest water temperature, with the 
three-year cycle beginning on January 1 following the 
quarter in which the supplier qualifies for reduced 
monitoring. 
 
C)      A supplier on a reduced monitoring schedule may remain on that 
reduced schedule as long as the average of all samples taken in the 
year (for a supplier that must monitor quarterly) or the result of the 
sample (for a supplier that must monitor no more frequently than 
annually) is no more than 0.060 mg/
ℓ
 and 0.045 mg/
ℓ
 for TTHMs 
and HAA5, respectively.  A supplier that does not meet these levels 
must resume monitoring at the frequency identified in subsection 
(b)(1)(A) of this Section (minimum monitoring frequency column) 
in the quarter immediately following the monitoring period in which 
the supplier exceeds 0.060 mg/
ℓ
 for TTHMs or 0.045 mg/
ℓ
 for 
HAA5.  For a supplier using only groundwater not under the direct 
influence of surface water and serving fewer than 10,000 persons, 
if either the TTHM annual average is greater than 0.080 mg/
ℓ
 or 
the HAA5 annual average is greater than 0.060 mg/
ℓ
, the supplier 
must go to increased monitoring identified in subsection (b)(1)(A) 
of this Section (sample location column) in the quarter 
immediately following the monitoring period in which the supplier 
 exceeds 0.080 mg/
ℓ
 for TTHMs or 0.060 mg/
ℓ
 for HAA5. 
 
D)      A supplier on increased monitoring may return to routine 
monitoring if, after at least one year of monitoring, its TTHM 
annual average is less than or equal to 0.060 mg/
ℓ
 and its HAA5 
annual average is less than or equal to 0.045 mg/
ℓ
. 
 
E)      The Agency may return a supplier to routine monitoring. 
 
 69
 
2)      Chlorite.  A CWS or NTNCWS supplier using chlorine dioxide, for 
disinfection or oxidation, must conduct monitoring for chlorite. 
 
A) Routine monitoring. 
 
i)       Daily monitoring.  A supplier must take daily samples at the 
entrance to the distribution system.  For any daily sample 
that exceeds the chlorite MCL, the supplier must take 
additional samples in the distribution system the following 
day at the locations required by subsection (b)(2)(B) of this 
Section, in addition to the sample required at the entrance to 
the distribution system. 
 
ii)      Monthly monitoring.  A supplier must take a three-sample 
set each month in the distribution system.  The supplier must 
take one sample at each of the following locations:  near the 
first customer, at a location representative of average 
residence time, and at a location reflecting maximum 
residence time in the distribution system.  Any additional 
 routine sampling must be conducted in the same manner (as 
three-sample sets, at the specified locations).  The supplier 
may use the results of additional monitoring conducted under 
subsection (b)(2)(B) of this Section to meet the requirement 
for monitoring in this subsection (b)(2)(A)(ii). 
 
B)      Additional monitoring.  On each day following a routine sample 
monitoring result that exceeds the chlorite MCL at the entrance to 
the distribution system, the supplier must take three chlorite 
distribution system samples at the following locations:  as close to 
the first customer as possible, in a location representative of average 
residence time, and as close to the end of the distribution system as 
possible (reflecting maximum residence time in the distribution 
system). 
 
C) Reduced monitoring. 
 
i)       Chlorite monitoring at the entrance to the distribution system 
required by subsection (b)(2)(A)(i) of this Section may not 
be reduced. 
 
ii)      Chlorite monitoring in the distribution system required by 
subsection (b)(2)(A)(ii) of this Section may be reduced to 
one three-sample set per quarter after one year of monitoring 
where no individual chlorite sample taken in the distribution 
system under subsection (b)(2)(A)(ii) of this Section has 
 
 70
exceeded the chlorite MCL and the supplier has not been 
required to conduct monitoring under subsection (b)(2)(B) of 
this Section.  The supplier may remain on the reduced 
 monitoring schedule until either any of the three individual 
chlorite samples taken quarterly in the distribution system 
under subsection (b)(2)(A)(ii) of this Section exceeds the 
chlorite MCL or the supplier is required to conduct 
monitoring under subsection (b)(2)(B) of this Section, at 
which time the supplier must revert to routine monitoring. 
 
3) Bromate. 
 
A)      Routine monitoring.  A CWS or NTNCWS supplier using ozone, for 
disinfection or oxidation, must take one sample per month for each 
treatment plant in the system using ozone.  A supplier must take 
samples monthly at the entrance to the distribution system while the 
ozonation system is operating under normal conditions. 
 
B)      Reduced monitoring.  A supplier required to analyze for bromate 
may reduce monitoring from monthly to once per quarter, if the 
supplier demonstrates that the average source water bromide 
concentration is less than 0.05 mg/
ℓ
 based upon representative 
monthly bromide measurements for one year.  The supplier may 
remain on reduced bromate monitoring until the running annual 
average source water bromide concentration, computed quarterly, is 
equal to or greater than 0.05 mg/
ℓ
 based upon representative 
monthly measurements.  If the running annual average source water 
bromide concentration is equal to or greater than 0.05 mg/
ℓ
, the 
supplier must resume routine monitoring required by subsection 
 (b)(3)(A) of this Section. 
 
c)      Monitoring requirements for disinfectant residuals. 
 
1)      Chlorine and chloramines. 
 
A)      Routine monitoring.  A CWS or NTNCWS supplier that uses 
chlorine or chloramines must measure the residual disinfectant level 
in the distribution system at the same point in the distribution system 
and at the same time as total coliforms are sampled, as specified in 
Section 611.521.  A Subpart B system supplier may use the results 
of residual disinfectant concentration sampling conducted under 
Section 611.532 for unfiltered systems or Section 611.533 for 
systems that filter, in lieu of taking separate samples. 
 
B)      Reduced monitoring.  Monitoring may not be reduced. 
 
 
 71
2) Chlorine dioxide. 
 
A)      Routine monitoring.  A CWS, an NTNCWS, or a transient non-
CWS supplier that uses chlorine dioxide for disinfection or 
oxidation must take daily samples at the entrance to the distribution 
system.  For any daily sample that exceeds the MRDL, the supplier 
must take samples in the distribution system the following day at the 
locations required by subsection (c)(2)(B) of this Section, in addition 
to the sample required at the entrance to the distribution system. 
 
B)      Additional monitoring.  On each day following a routine sample 
monitoring result that exceeds the MRDL, the supplier must take 
three chlorine dioxide distribution system samples.  If chlorine 
 dioxide or chloramines are used to maintain a disinfectant residual in 
the distribution system, or if chlorine is used to maintain a 
disinfectant residual in the distribution system and there are no 
disinfection addition points after the entrance to the distribution 
system (i.e., no booster chlorination), the supplier must take three 
samples as close to the first customer as possible, at intervals of at 
least six hours.  If chlorine is used to maintain a disinfectant residual 
in the distribution system and there are one or more disinfection 
addition points after the entrance to the distribution system (i.e., 
booster chlorination), the supplier must take one sample at each of 
the following locations:  as close to the first customer as possible, in 
a location representative of average residence time, and as close to 
the end of the distribution system as possible (reflecting maximum 
residence time in the distribution system). 
 
C)      Reduced monitoring.  Monitoring may not be reduced. 
 
d)      Monitoring requirements for disinfection byproduct (DBP) precursors. 
 
1)      Routine monitoring.  A Subpart B system supplier that uses conventional 
filtration treatment (as defined in Section 611.101) must monitor each 
treatment plant for TOC not past the point of combined filter effluent 
turbidity monitoring and representative of the treated water.  A supplier 
required to monitor under this subsection (d)(1) must also monitor for TOC 
in the source water prior to any treatment at the same time as monitoring for 
 TOC in the treated water.  These samples (source water and treated water) 
are referred to as paired samples.  At the same time as the source water 
sample is taken, a system must monitor for alkalinity in the source water 
prior to any treatment.  A supplier must take one paired sample and one 
source water alkalinity sample per month per plant at a time representative 
of normal operating conditions and influent water quality. 
 
2)      Reduced monitoring.  A Subpart B system supplier with an average treated 
 
 72
water TOC of less than 2.0 mg/
ℓ
 for two consecutive years, or less than 1.0 
mg/
ℓ
 for one year, may reduce monitoring for both TOC and alkalinity to 
one paired sample and one source water alkalinity sample per plant per 
quarter.  The supplier must revert to routine monitoring in the month 
following the quarter when the annual average treated water TOC greater 
than or equal to 2.0 mg/
ℓ
. 
 
e)      Bromide.  A supplier required to analyze for bromate may reduce bromate 
monitoring from monthly to once per quarter, if the supplier demonstrates that the 
average source water bromide concentration is less than 0.05 mg/
ℓ
 based upon 
representative monthly measurements for one year.  The supplier must continue 
bromide monitoring to remain on reduced bromate monitoring. 
 
f)       Monitoring plans.  Each supplier required to monitor under this Subpart I must 
 develop and implement a monitoring plan.  The supplier must maintain the plan and 
make it available for inspection by the Agency and the general public no later than 
30 days following the applicable compliance dates in Section 611.380(b).  A 
Subpart B system supplier serving more than 3,300 persons must submit a copy of 
the monitoring plan to the Agency no later than the date of the first report required 
under Section 611.384.  After review, the Agency may require changes in any plan 
elements.  The plan must include at least the following elements: 
 
1)      Specific locations and schedules for collecting samples for any parameters 
included in this Subpart I; 
 
2)      How the supplier will calculate compliance with MCLs, MRDLs, and 
treatment techniques; and 
 
3)      If approved for monitoring as a consecutive system, or if providing water to 
a consecutive system, under the provisions of Section 611.500, the sampling 
plan must reflect the entire distribution system. 
 
BOARD NOTE:  Derived from 40 CFR 141.132 (2002) (2003). 
 
(Source:  Amended at 29 Ill. Reg. ________, effective ______________________) 
 
Section 611.383       Compliance Requirements 
 
a) General requirements. 
 
1)      Where compliance is based on a running annual average of monthly or 
quarterly samples or averages and the supplier fails to monitor for TTHM, 
HAA5, or bromate, this failure to monitor will be treated as a monitoring 
violation for the entire period covered by the annual average.  Where 
 compliance is based on a running annual average of monthly or quarterly 
samples or averages and the supplier’s failure to monitor makes it 
 
 73
impossible to determine compliance with the MRDL for chlorine or 
chloramines, this failure to monitor will be treated as a monitoring violation 
for the entire period covered by the annual average. 
 
2)      All samples taken and analyzed under the provisions of this Subpart I must 
be included in determining compliance, even if that number is greater than 
the minimum required. 
 
3)      If, during the first year of monitoring under Section 611.382, any individual 
quarter’s average will cause the running annual average of that supplier to 
exceed the MCL for total trihalomethanes, haloacetic acids (five), or 
bromate or the MRDL for chlorine or chloramine, the supplier is out of 
compliance at the end of that quarter. 
 
b)      Disinfection byproducts (DBPs). 
 
1)      TTHMs and HAA5. 
 
A)      For a supplier monitoring quarterly, compliance with MCLs in 
Section 611.312 must be based on a running annual arithmetic 
average, computed quarterly, of quarterly arithmetic averages of all 
samples collected by the supplier as prescribed by Section 
611.382(b)(1). 
 
B)      For a supplier monitoring less frequently than quarterly, the supplier 
demonstrates MCL compliance if the average of samples taken that 
year under the provisions of Section 611.382(b)(1) does not exceed 
 the MCLs in Section 611.312.  If the average of these samples 
exceeds the MCL, the supplier must increase monitoring to once per 
quarter per treatment plant, and such a system is not in violation of 
the MCL until it has completed one year of quarterly monitoring, 
unless the result of fewer than four quarters of monitoring will 
cause the running annual average to exceed the MCL, in which 
case the supplier is in violation at the end of that quarter.  A 
supplier required to increase to quarterly monitoring must calculate 
compliance by including the sample that triggered the increased 
monitoring plus the following three quarters of monitoring. 
 
C)      If the running annual arithmetic average of quarterly averages 
covering any consecutive four-quarter period exceeds the MCL, 
the supplier is in violation of the MCL and must notify the public 
pursuant to Subpart V of this Part in addition to reporting to the 
Agency pursuant to Section 611.384. 
 
D)      If a PWS fails to complete four consecutive quarter’s monitoring, 
compliance with the MCL for the last four-quarter compliance 
 
 74
period must be based on an average of the available data. 
 
2)      Bromate.  Compliance must be based on a running annual arithmetic 
average, computed quarterly, of monthly samples (or, for months in which 
the supplier takes more than one sample, the average of all samples taken 
during the month) collected by the supplier, as prescribed by Section 
 611.382(b)(3).  If the average of samples covering any consecutive four-
quarter period exceeds the MCL, the supplier is in violation of the MCL and 
must notify the public pursuant to Subpart V of this Part, in addition to 
reporting to the Agency pursuant to Section 611.384.  If a PWS supplier 
fails to complete 12 consecutive months’ monitoring, compliance with the 
MCL for the last four-quarter compliance period must be based on an 
average of the available data. 
 
3)      Chlorite.  Compliance must be based on an arithmetic average of each three 
sample set taken in the distribution system as prescribed by Section 
611.382(b)(2)(A)(ii) and Section 611.382(b)(2)(B).  If the arithmetic 
average of any three sample set exceeds the MCL, the supplier is in 
violation of the MCL and must notify the public pursuant to Subpart V of 
this Part, in addition to reporting to the Agency pursuant to Section 611.384. 
 
c) Disinfectant residuals. 
 
1)      Chlorine and chloramines. 
 
A)      Compliance must be based on a running annual arithmetic average, 
computed quarterly, of monthly averages of all samples collected by 
the supplier under Section 611.382(c)(1).  If the average of quarterly 
averages covering any consecutive four-quarter period exceeds the 
MRDL, the supplier is in violation of the MRDL and must notify the 
public pursuant to Subpart V of this Part, in addition to reporting to 
the Agency pursuant to Section 611.384. 
 
B)      In cases where a supplier switches between the use of chlorine and 
 chloramines for residual disinfection during the year, compliance 
must be determined by including together all monitoring results of 
both chlorine and chloramines in calculating compliance.  Reports 
submitted pursuant to Section 611.384 must clearly indicate that 
residual disinfectant was analyzed for each sample. 
 
2) Chlorine dioxide. 
 
A)      Acute violations.  Compliance must be based on consecutive daily 
samples collected by the supplier under Section 611.382(c)(2).  If 
any daily sample taken at the entrance to the distribution system 
exceeds the MRDL, and on the following day one (or more) of the 
 
 75
three samples taken in the distribution system exceeds the MRDL, 
the supplier is in violation of the MRDL and must take immediate 
corrective action to lower the level of chlorine dioxide below the 
MRDL and must notify the public pursuant to the procedures for 
acute health risks in Subpart V of this Part, in addition to reporting 
to the Agency pursuant to Section 611.384.  Failure to take samples 
in the distribution system the day following an exceedence of the 
chlorine dioxide MRDL at the entrance to the distribution system 
will also be considered an MRDL violation and the supplier must 
notify the public of the violation in accordance with the provisions 
for acute violations under Subpart V of this Part, in addition to 
reporting to the Agency pursuant to Section 611.384. 
 
B)      Nonacute violations.  Compliance must be based on consecutive 
 daily samples collected by the supplier under Section 611.382(c)(2).  
If any two consecutive daily samples taken at the entrance to the 
distribution system exceed the MRDL and all distribution system 
samples taken are below the MRDL, the supplier is in violation of 
the MRDL and must take corrective action to lower the level of 
chlorine dioxide below the MRDL at the point of sampling and must 
notify the public pursuant to the procedures for nonacute health risks 
in Subpart V of this Part, in addition to reporting to the Agency 
pursuant to Section 611.384.  Failure to monitor at the entrance to 
the distribution system the day following an exceedence of the 
chlorine dioxide MRDL at the entrance to the distribution system is 
also an MRDL violation and the supplier must notify the public of 
the violation in accordance with the provisions for nonacute 
violations under Subpart V of this Part, in addition to reporting to 
the Agency pursuant to Section 611.384. 
 
d)      Disinfection byproduct (DBP) precursors.  Compliance must be determined as 
specified by Section 611.385(c).  A supplier may begin monitoring to determine 
whether Step 1 TOC removals can be met 12 months prior to the compliance date 
for the supplier.  This monitoring is not required and failure to monitor during this 
period is not a violation.  However, any supplier that does not monitor during this 
period, and then determines in the first 12 months after the compliance date that it is 
not able to meet the Step 1 requirements in Section 611.141(b)(2) and must 
 therefore apply for alternate minimum TOC removal (Step 2) requirements, is not 
eligible for retroactive approval of alternate minimum TOC removal (Step 2) 
requirements as allowed pursuant to Section 611.385(b)(3) and is in violation of an 
NPDWR.  A supplier may apply for alternate minimum TOC removal (Step 2) 
requirements any time after the compliance date.  For a supplier required to meet 
Step 1 TOC removals, if the value calculated under Section 611.385(c)(1)(D) is 
less than 1.00, the supplier is in violation of the treatment technique requirements 
and must notify the public pursuant to Subpart V of this Part, in addition to 
reporting to the Agency pursuant to Section 611.384. 
 
 76
 
BOARD NOTE:  Derived from 40 CFR 141.133 (2002) (2003). 
 
(Source:  Amended at 29 Ill. Reg. ________, effective ______________________) 
 
SUBPART L: MICROBIOLOGICAL MONITORING AND ANALYTICAL 
REQUIREMENTS 
 
Section 611.526       Analytical Methodology 
 
a)      The standard sample volume required for total coliform analysis, regardless of 
analytical method used, is 100 m
ℓ
. 
 
b)      Suppliers need only determine the presence or absence of total coliforms; a 
determination of total coliform density is not required. 
 
c)      Suppliers must conduct total coliform analyses in accordance with one of the 
following analytical methods, incorporated by reference in Section 611.102 (the 
time from sample collection to initiation of analysis may not exceed 30 hours, and 
 the supplier is encouraged but not required to hold samples below 10° C during 
transit): 
 
1)      Total Coliform Fermentation Technique, as set forth in Standard Methods, 
18th, 19th, or 20th ed.:  Methods 9221 A and B, as follows: 
 
A)      Lactose broth, as commercially available, may be used in lieu of 
lauryl tryptose broth if the supplier conducts at least 25 parallel 
tests between this medium and lauryl tryptose broth using the 
water normally tested and this comparison demonstrates that the 
false-positive rate and false-negative rate for total coliforms, using 
lactose broth, is less than 10 percent; 
 
B)      If inverted tubes are used to detect gas production, the media 
should cover these tubes at least one-half to two-thirds after the 
sample is added; and 
 
C)      No requirement exists to run the completed phase on 10 percent of 
all total coliform-positive confirmed tubes. 
 
2)      Total Coliform Membrane Filter Technique, as set forth in Standard 
Methods, 18th, 19th, or 20th ed.:  Methods 9222 A, B, and C. 
 
3)      Presence-Absence (P-A) Coliform Test, as set forth in:  Standard 
Methods, 18th, 19th, or 20th ed.:  Method 9221 D, as follows: 
 
A)      No requirement exists to run the completed phase on 10 percent of 
 
 77
all total coliform-positive confirmed tubes; and 
 
B)      Six-times formulation strength may be used if the medium is filter-
sterilized rather than autoclaved. 
 
4)      ONPG-MUG test:  Standard Methods, 18th, 19th, or 20th ed.:  Method 
9223.  (The ONPG-MUG test is also known as the Autoanalysis Colilert 
System). 
 
5)      Colisure Test (Autoanalysis Colilert System).  (The Colisure Test may be 
read after an incubation time of 24 hours.) 
 
BOARD NOTE:  USEPA included the P-A Coliform and Colisure Tests 
for testing finished water under the coliform rule, but did not include them 
for the purposes of the surface water treatment rule, under Section 
611.531, for which quantitation of total coliforms is necessary.  For these 
reasons, USEPA included Standard Methods:  Method 9221 C for the 
surface water treatment rule, but did not include it for the purposes of the 
total coliform rule, under this Section. 
 
6) E*Colite
®
  Test (Charm Sciences, Inc.). 
 
7) m-ColiBlue24
®
  Test (Hatch Company). 
 
8)      Readycult Coliforms 100 Presence/Absence Test. 
 
9)      Membrane Filter Technique using Chromocult Doliform Coliform Agar. 
 
10) Colitag
®
  Test. 
 
d)      This subsection corresponds with 40 CFR 141.21(f)(4), which USEPA has 
marked “reserved.”.  This statement maintains structural consistency with the 
federal regulations. 
 
e)      Suppliers must conduct fecal coliform analysis in accordance with the following 
procedure: 
 
1)      When the MTF Technique or P-A Coliform Test is used to test for total 
 coliforms, shake the lactose-positive presumptive tube or P-A vigorously 
and transfer the growth with a sterile 3-mm loop or sterile applicator stick 
into brilliant green lactose bile broth and EC medium, defined below, to 
determine the presence of total and fecal coliforms, respectively. 
 
2)      For approved methods that use a membrane filter, transfer the total 
coliform-positive culture by one of the following methods:  remove the 
membrane containing the total coliform colonies from the substrate with 
 
 78
sterile forceps and carefully curl and insert the membrane into a tube of 
EC medium; (the laboratory may first remove a small portion of selected 
colonies for verification); swab the entire membrane filter surface with a 
sterile cotton swab and transfer the inoculum to EC medium (do not leave 
the cotton swab in the EC medium); or inoculate individual total coliform-
positive colonies into EC medium.  Gently shake the inoculated tubes of 
EC medium to insure adequate mixing and incubate in a waterbath at 
44.5±0.2° C for 24±2 hours.  Gas production of any amount in the inner 
fermentation tube of the EC medium indicates a positive fecal coliform 
test. 
 
3)      EC medium is described in Standard Methods, 18th ed., 19th ed., and 20th 
ed.:  Method 9221 E. 
 
4)      Suppliers need only determine the presence or absence of fecal coliforms; 
a determination of fecal coliform density is not required. 
 
f)      Suppliers must conduct analysis of E. coli in accordance with one of the 
 following analytical methods, incorporated by reference in Section 611.102: 
 
1)      EC medium supplemented with 50 μg/
ℓ
 of MUG (final concentration).  
EC medium is as described in subsection (e) of this Section.  MUG may 
be added to EC medium before autoclaving.  EC medium supplemented 
with 50 μg/
ℓ
 MUG is commercially available.  At least 10 m
ℓ
 of EC 
medium supplemented with MUG must be used.  The inner inverted 
fermentation tube may be omitted.  The procedure for transferring a total 
coliform-positive culture to EC medium supplemented with MUG is as in 
subsection (e) of this Section for transferring a total coliform-positive 
culture to EC medium.  Observe fluorescence with an ultraviolet light 
(366 nm) in the dark after incubating tube at 44.5±2° C for 24±2 hours; or 
 
2)      Nutrient agar supplemented with 100 μg/
ℓ
 MUG (final concentration), as 
described in Standard Methods, 19th ed. and 20th ed.:  Method 9222 G.  
This test is used to determine if a total coliform-positive sample, as 
determined by the MF technique, contains E. coli.  Alternatively, Standard 
Methods, 18th ed.:  Method 9221 B may be used if the membrane filter 
containing a total coliform-positive colony or colonies is transferred to 
nutrient agar, as described in Method 9221 B (paragraph 3), supplemented 
with 100 μg/
ℓ
 MUG.  If Method 9221 B is used, incubate the agar plate at 
 35° Celsius for 4 four hours, then observe the colony or colonies under 
ultraviolet light (366-nm) in the dark for fluorescence.  If fluorescence is 
visible, E. coli are present. 
 
3)      Minimal Medium ONPG-MUG (MMO-MUG) Test, as set forth in 
Appendix D of this Part.  (The Autoanalysis Colilert System is a MMO-
MUG test.)  If the MMO-MUG test is total coliform positive after a 24-
 
 79
hour incubation, test the medium for fluorescence with a 366-nm 
ultraviolet light (preferably with a 6-watt six-watt lamp) in the dark.  If 
fluorescence is observed, the sample is E. coli-positive.  If fluorescence is 
questionable (cannot be definitively read) after 24 hours incubation, 
incubate the culture for an additional four hours (but not to exceed 28 
hours total), and again test the medium for fluorescence.  The MMO-
MUG test with hepes buffer is the only approved formulation for the 
detection of E. coli. 
 
4)      The Colisure Test (Autoanalysis Colilert System). 
 
5)      The membrane filter method with MI agar. 
 
6) The E*Colite
®
  Test. 
 
7) The m-ColiBlue24
®
  Test. 
 
8)      Readycult Coliforms 100 Presence/Absence Test. 
 
9)      Membrane Filter Technique using Chromocult Doliform Coliform Agar. 
 
10) Colitag
®
  Test. 
 
g)      As an option to the method set forth in subsection (f)(3) of this Section, a supplier 
 with a total coliform-positive, MUG-negative, MMO-MUG test may further 
analyze the culture for the presence of E. coli by transferring a 0.1 m
ℓ
, 28-hour 
MMO-MUG culture to EC medium + MUG with a pipet.  The formulation and 
incubation conditions of the EC medium + MUG, and observation of the results, 
are described in subsection (f)(1) of this Section. 
 
h)      This subsection corresponds with 40 CFR 141.21(f)(8), a central listing of all 
documents incorporated by reference into the federal microbiological analytical 
methods.  The corresponding Illinois incorporations by reference are located at 
Section 611.102.  This statement maintains structural parity with USEPA 
regulations. 
 
BOARD NOTE:  Derived from 40 CFR 141.21(f) (2002) (2003). 
 
(Source:  Amended at 29 Ill. Reg. ________, effective ______________________) 
 
Section 611.532       Unfiltered PWSs 
 
A supplier that uses a surface water source and does not provide filtration treatment must 
monitor, unless the Agency has determined, pursuant to Section 611.211, that filtration is 
required.  If the Agency determines that filtration is required, it must specify alternative 
monitoring requirements, as appropriate, until filtration is in place.  A supplier that uses a 
 
 80
groundwater source under the direct influence of surface water and which does not provide 
filtration treatment must monitor within six months after the Agency has determined, pursuant to 
 Section 611.212, that the groundwater source is under the direct influence of surface water 
unless the Agency has determined that filtration is required, in which case the Agency must 
specify alternative monitoring requirements, as appropriate, until filtration is in place. 
 
a)      Fecal coliform or total coliform density measurements as required by Section 
611.231(a) must be performed on representative source water samples 
immediately prior to the first or only point of disinfectant application.  The 
supplier must sample for fecal or total coliforms at the minimum frequency 
specified in Table B of this Part each week the supplier serves water to the public.  
Also, one fecal or total coliform density measurement must be made every day the 
supplier serves water to the public and the turbidity of the source water exceeds 1 
NTU (these samples count towards the weekly coliform sampling requirement) 
unless the Agency determines that the supplier, for logistical reasons outside the 
supplier’s control cannot have the sample analyzed within 30 hours of collection. 
 
b)      Turbidity measurements as required by Section 611.231(b) must be performed on 
representative grab samples of source water immediately prior to the first or only 
point of disinfectant application every four hours (or more frequently) that the 
supplier serves water to the public.  A supplier may substitute continuous 
turbidity monitoring for grab sample monitoring if it validates the continuous 
measurement for accuracy on a regular basis using a protocol approved by a SEP 
 issued pursuant to Section 611.110. 
 
c)      The total inactivation ratio for each day that the supplier is in operation must be 
determined based on the CT99.9 values in Appendix B of this Part, as appropriate.  
The parameters necessary to determine the total inactivation ratio must be 
monitored as follows: 
 
1)      The temperature of the disinfected water must be measured at least once 
per day at each RDC sampling point. 
 
2)      If the supplier uses chlorine, the pH of the disinfected water must be 
measured at least once per day at each chlorine RDC sampling point. 
 
3)      The disinfectant contact times (“T”) must be determined for each day 
during peak hourly flow. 
 
4)      The RDCs (“C”) of the water before or at the first customer must be 
measured each day during peak hourly flow. 
 
5)      If a supplier uses a disinfectant other than chlorine, the supplier may 
monitor by other methods approved pursuant to Section 611.241(a)(1) and 
(a)(2). 
 
 
 81
d) 
 The total inactivation ratio must be calculated as follows: 
 
1) 
 If the supplier uses only one point of disinfectant application, the supplier 
may determine the total inactivation ratio based on either of the following 
two methods: 
 
A) 
 One inactivation ratio (Ai = CTcalc/CT99.9) is determined before or 
at the first customer during peak hourly flow and, if the Ai is 
greater than 1.0, the 99.9 percent Giardia lamblia inactivation 
requirement has been achieved; or 
 
B) 
 Successive Ai values, representing sequential inactivation ratios, 
are determined between the point of disinfectant application and a 
point before or at the first customer during peak hourly flow.  
Under this alternative, the following method must be used to 
calculate the total inactivation ratio: 
 
i) 
 Determine the following, for each sequence: 
 
Ai = CTcalc/CT99.9
 
ii) 
 Add the Ai values together, as follows: 
 
B = 
∑
(Ai) 
 
iii) 
 If B is greater than 1.0, the 99.9 percent Giardia lamblia 
inactivation requirement has been achieved. 
 
2) 
 If the supplier uses more than one point of disinfectant application before 
or at the first customer, the supplier must determine the CT value of each 
disinfection sequence immediately prior to the next point of disinfectant 
application during peak hourly flow.  The Ai value of each sequence and 
B must be calculated using the method in subsection (d)(1)(B) of this 
Section to determine if the supplier is in compliance with Section 611.241. 
 
3) 
 Although not required, the total percent inactivation (PI) for a supplier 
with one or more points of RDC monitoring may be calculated as follows: 
 
3B
10
100
 100
 PI
−
=
  
 
e) 
 The RDC of the water entering the distribution system must be monitored 
continuously, and the lowest value must be recorded each day, except that if there 
is a failure in the continuous monitoring equipment, grab sampling every four 
hours may be conducted in lieu of continuous monitoring, but for no more than 
five working days following the failure of the equipment, and suppliers serving 
 
 82
3,300 or fewer persons may take grab samples in lieu of providing continuous 
monitoring on an ongoing basis at the frequencies prescribed in Table C of this 
Part.  If at any time the RDC falls below 0.2 mg/
ℓ
 in a system using grab 
sampling in lieu of continuous monitoring, the supplier must take a grab sample 
every four hours until the RDC is equal to or greater than 0.2 mg/
ℓ
. 
 
f)      Points of measurement. 
 
1)      The RDC must be measured at least at the same points in the distribution 
system and at the same time as total coliforms are sampled, as specified in 
Subpart L of this Section, except that the Agency must allow a supplier 
that uses both a surface water source or a groundwater source under direct 
influence of surface water, and a groundwater source to take disinfectant 
residual samples at points other than the total coliform sampling points if 
the Agency determines, by a SEP issued pursuant to Section 611.110, that 
 such points are more representative of treated (disinfected) water quality 
within the distribution system.  HPC may be measured in lieu of RDC. 
 
2)      If the Agency determines, pursuant to Section 611.213, that a supplier has 
no means for having a sample analyzed for HPC, measured as specified in 
subsection (a) of this Section, the requirements of subsection (f)(1) of this 
Section do not apply to that supplier. 
 
BOARD NOTE:  Derived from 40 CFR 141.74(b) (2002) (2003). 
 
(Source:  Amended at 29 Ill. Reg. ________, effective ______________________) 
 
Section 611.533       Filtered PWSs 
 
A supplier that uses a surface water source or a groundwater source under the influence of 
surface water and provides filtration treatment must monitor in accordance with this Section. 
 
a)      Turbidity measurements as required by Section 611.250 must be performed on 
representative samples of the PWS’s filtered water every four hours (or more 
frequently) that the supplier serves water to the public.  A supplier may substitute 
continuous turbidity monitoring for grab sample monitoring if it validates the 
continuous measurement for accuracy on a regular basis using a protocol 
approved by a SEP issued pursuant to Section 611.110.  For any suppliers using 
slow sand filtration or filtration treatment other than conventional treatment, 
direct filtration, or diatomaceous earth filtration, the Agency shall, by special 
exception permit condition, reduce the sampling frequency to once per day if it 
 determines that less frequent monitoring is sufficient to indicate effective 
filtration performance.  For suppliers serving 500 or fewer persons, the Agency 
shall, by a SEP issued pursuant to Section 611.110, reduce the turbidity sampling 
frequency to once per day, regardless of the type of filtration treatment used, if 
the Agency determines that less frequent monitoring is sufficient to indicate 
 
 83
effective filtration performance. 
 
b)      RDC entering distribution system. 
 
1)      Suppliers serving more than 3300 persons.  The RDC of the water entering 
the distribution system must be monitored continuously, and the lowest 
value must be recorded each day, except that, if there is a failure in the 
continuous monitoring equipment, grab sampling every four hours may be 
conducted in lieu of continuous monitoring, but for no more than five 
working days following the failure of the equipment. 
 
2)      Suppliers serving 3,300 or fewer persons may take grab samples in lieu of 
providing continuous monitoring on an ongoing basis at the frequencies 
each day prescribed in Table C.  If at any time the RDC falls below 0.2 
mg/
ℓ
 in a system using grab sampling in lieu of continuous monitoring, 
the supplier must take a grab sample every four hours until RDC is equal 
to or greater than 0.2 mg/
ℓ
. 
 
c)      Points of measurement. 
 
1)      The RDC must be measured at least at the same points in the distribution 
system and at the same time as total coliforms are sampled, as specified in 
Sections 611.521 et seq. through 611.527, except that the Agency must 
allow a supplier that uses both a surface water source or a groundwater 
source under direct influence of surface water, and a groundwater source, 
to take RDC samples at points other than the total coliform sampling 
points if the Agency determines that such points are more representative 
of treated (disinfected) water quality within the distribution system.  HPC, 
measured as specified in Section 611.531(a), may be measured in lieu of 
RDC. 
 
2) Subsection (c)(1) of this Section does not apply if the Agency determines, 
pursuant to Section 611.213(c), that a system has no means for having a 
sample analyzed for HPC by a certified laboratory under the requisite time 
and temperature conditions specified by Section 611.531(a) and that the 
supplier is providing adequate disinfection in the distribution system. 
 
BOARD NOTE:  Derived from 40 CFR 141.74(c) (2002) (2003). 
 
(Source:  Amended at 29 Ill. Reg. ________, effective ______________________) 
 
 
 84
SUBPART Q:  RADIOLOGICAL MONITORING AND ANALYTICAL 
REQUIREMENTS 
 
Section 611.720       Analytical Methods 
 
a)      The methods specified below, incorporated by reference in Section 611.102, are 
to be used to determine compliance with Section 611.330, except in cases where 
alternative methods have been approved in accordance with Section 611.480. 
 
1)      Gross Alpha and Beta. 
 
A) Standard Methods. 
 
i)       Method 302, 13th ed.; or 
 
ii)      Method 7110 B, 17th, 18th, 19th, or 20th ed.; 
 
B)      USEPA Interim Radiochemical Methods:  page 1; 
 
C)      USEPA Radioactivity Methods:  Method 900.0; 
 
D)      USEPA Radiochemical Analyses:  page 1; 
 
E)      USEPA Radiochemistry Methods:  Method 00-01; or 
 
F)      USGS Methods:  Method R-1120-76. 
 
2) Gross Alpha. 
 
A)      Standard Methods, 18th, 19th, or 20th ed.:  Method 7110 C; or 
 
B)      USEPA Radiochemistry Methods:  Method 00-02. 
 
3) Radium-226. 
 
A) ASTM Methods. 
 
i)       Method D2460-90; or 
 
ii) Method D3454-97; 
 
B)      New York Radium Method; 
 
C) Standard Methods. 
 
i)       Method 304, 13th ed.; 
 
 85
 
ii)      Method 305, 13th ed.; 
 
iii)     Method 7500-Ra B, 17th, 18th, 19th, or 20th ed.; or 
 
iv)     Method 7500-Ra C, 17th, 18th, 19th, or 20th ed.; 
 
D)      USDOE Methods:  Method Ra-04; 
 
E)      USEPA Interim Radiochemical Methods:  pages 13 and 16; 
 
F)      USEPA Radioactivity Methods:  Methods 903.0, 903.1; 
 
G)      USEPA Radiochemical Analyses:  page 19; 
 
H)      USEPA Radiochemistry Methods:  Methods Ra-03, Ra-04; or 
 
I) USGS Methods. 
 
i)       Method R-1140-76; or 
 
ii) Method R-1141-76. 
 
4) Radium-228. 
 
A)      Standard Methods, 17th, 18th, 19th, or 20th ed.:  Method 7500-Ra 
D; 
 
B)      New York Radium Method; 
 
C)      USEPA Interim Radiochemical Methods:  page 24; 
 
D)      USEPA Radioactivity Methods:  Method 904.0; 
 
E)      USEPA Radiochemical Analyses:  page 19; 
 
F)      USEPA Radiochemistry Methods:  Method Ra-05; 
 
G)      USGS Methods:  Method R-1142-76; or 
 
H)      New Jersey Radium Method. 
 
5) Uranium. 
 
A)      Standard Methods, 17th, 18th, 19th, or 20th ed.:  Method 7500-U 
C; 
 
 86
 
B)      Standard Methods, 20th ed.:  Method 3125; 
 
BC) ASTM Methods. 
 
i) Method D2907-97; 
 
ii) Method D3972-97; or
 
iii) Method D5174-97; or
 
iv) Method D5673-03; 
 
CD)    USEPA Radioactivity Methods:  Methods 908.0, 908.1; 
 
E)      USEPA Environmental Metals Methods:  Method 200.8; 
 
DF)    USEPA Radiochemical Analyses:  page 33; 
 
EG)    USEPA Radiochemistry Methods:  Method 00-07; 
 
FH)    USDOE Methods:  Method U-02 or U-04; or 
 
GI) USGS Methods. 
 
i) Method R-1180-76; 
 
ii)      Method R-1181-76; or 
 
iii) Method R-1182-76. 
 
BOARD NOTE:  If uranium (U) is determined by mass, a conversion 
factor of 0.67 pCi/μg of uranium must be used.  This conversion factor is 
based on the 1:1 activity ratio of 
234
U and 
238
U that is characteristic of 
naturally occurring uranium. 
 
6) Radioactive Cesium. 
 
A) ASTM Methods. 
 
i)       Method D2459-72; or 
 
ii) Method D3649-91; 
 
B) Standard Methods. 
 
 
 87
i)       Method 7120, 19th or 20th ed.; or 
 
ii)      Method 7500-Cs B, 17th, 18th, 19th, or 20th ed.; 
 
C)      USDOE Methods:  Method 4.5.2.3; 
 
D)      USEPA Interim Radiochemical Methods:  page 4; 
 
E)      USEPA Radioactivity Methods:  Methods 901.0, 901.1; 
 
F)      USEPA Radiochemical Analyses:  page 92; or 
 
G) USGS Methods. 
 
i)       Method R-1110-76; or 
 
ii) Method R-1111-76. 
 
7) Radioactive Iodine. 
 
A) ASTM Methods. 
 
i) D3649-91; or 
 
ii) D4785-93; 
 
B) Standard Methods. 
 
i)       Method 7120, 19th or 20th ed.; 
 
ii)      Method 7500-I B, 17th, 18th, 19th, or 20th ed.; 
 
iii)     Method 7500-I C, 17th, 18th, 19th, or 20th ed.; or 
 
iv)     Method 7500-I D, 17th, 18th, 19th, or 20th ed.; 
 
C)      USDOE Methods:  Method 4.5.2.3; 
 
D)      USEPA Interim Radiochemical Methods:  pages 6, 9; 
 
E)      USEPA Radiochemical Analyses:  page 92; or 
 
F)      USEPA Radioactivity Methods:  Methods 901.1, 902.0. 
 
8)      Radioactive Strontium-89 & 90. 
 
 
 88
A) Standard Methods. 
 
i)       Method 303, 13th ed.; or 
 
ii)      Method 7500-Sr B, 17th, 18th, 19th, or 20th ed.; 
 
B) USDOE Methods. 
 
i)       Method Sr-01; or 
 
ii) Method Sr-02; 
 
C)      USEPA Interim Radiochemical Methods:  page 29; 
 
D)      USEPA Radioactivity Methods:  Method 905.0; 
 
E)      USEPA Radiochemical Analyses:  page 65; 
 
F)      USEPA Radiochemistry Methods:  Method Sr-04; or 
 
G)      USGS Methods:  Method R-1160-76. 
 
9) Tritium. 
 
A)      ASTM Methods:  Method D4107-91; 
 
B) Standard Methods. 
 
i)       Method 306, 13th ed.; or 
 
ii)      Method 7500-3H B, 17th, 18th, 19th, or 20th ed.; 
 
C)      USEPA Interim Radiochemical Methods:  page 34; 
 
D)      USEPA Radioactivity Methods:  Method 906.0; 
 
E)      USEPA Radiochemical Analyses:  page 87; 
 
F)      USEPA Radiochemistry Methods:  Method H-02; or 
 
G)      USGS Methods:  Method R-1171-76. 
 
10) Gamma Emitters. 
 
A) ASTM Methods. 
 
 
 89
i)       Method D3649-91; or 
 
ii) Method D4785-93; 
 
B) Standard Methods. 
 
i)       Method 7120, 19th or 20th ed.; 
 
ii)      Method 7500-Cs B, 17th, 18th, 19th, or 20th ed.; or 
 
iii)     Method 7500-I B, 17th, 18th, 19th, or 20th ed.; 
 
C)      USDOE Method:  Method Ga-01-R; 
 
D)      USEPA Radioactivity Methods:  Methods 901.0, 901.1, or 902.0; 
 
E)      USEPA Radiochemical Analyses:  page 92; or 
 
F)      USGS Methods:  Method R-1110-76. 
 
b)      When the identification and measurement of radionuclides other than those listed 
in subsection (a) of this Section are required, the following methods, incorporated 
by reference in Section 611.102, are to be used, except in cases where alternative 
methods have been approved in accordance with Section 611.480: 
 
1)      “Procedures for Radiochemical Analysis of Nuclear Reactor Aqueous 
Solutions,” available from NTIS. 
 
2)      HASL Procedure Manual, HASL 300, available from ERDA Health and 
Safety Laboratory. 
 
c)      For the purpose of monitoring radioactivity concentrations in drinking water, the 
required sensitivity of the radioanalysis is defined in terms of a detection limit.  
The detection limit must be that concentration which can be counted with a 
 precision of plus or minus 100 percent at the 95 percent confidence level (1.96
σ
, 
where 
σ
 is the standard deviation of the net counting rate of the sample). 
 
1)      To determine compliance with Section 611.330(b), (c), and (e), the 
detection limit must not exceed the concentrations set forth in the 
following table: 
 
Contaminant Detection Limit 
Gross alpha particle 
activity 
3 pCi/
ℓ
 
Radium-226 1 pCi/
ℓ
 
Radium-228 1 pCi/
ℓ
 
 
 90
Uranium 
 None1 μg/
ℓ
 
BOARD NOTE:  Derived from 40 CFR 141.25(c) Table B (2002) (2003). 
 
2)      To determine compliance with Section 611.330(d), the detection limits 
must not exceed the concentrations listed in the following table: 
 
Radionuclide Detection Limit 
Tritium 1,000 
 pCi/
ℓ
 
Strontium-89 10 pCi/
ℓ
 
Strontium-90 2 pCi/
ℓ
 
Iodine-131 1 pCi/
ℓ
 
Cesium-134 10 pCi/
ℓ
 
Gross beta 
 4 pCi/
ℓ
 
Other radionuclides 
 1/10 of applicable limit 
 
BOARD NOTE:  Derived from 40 CFR 141.25(c) Table C (2002) (2003). 
 
d)      To judge compliance with the MCLs listed in Section 611.330, averages of data 
must be used and must be rounded to the same number of significant figures as 
the MCL for the substance in question. 
 
BOARD NOTE:  Derived from 40 CFR 141.25 (2002) (2003). 
 
(Source:  Amended at 29 Ill. Reg. ________, effective ______________________) 
 
Section 611.732       Beta Particle and Photon Radioactivity 
 
Monitoring and compliance requirements for manmade radioactivity.  To determine compliance 
with the maximum contaminant levels in Section 611.330(d) for beta particle and photon 
radioactivity, a supplier must monitor at a frequency as follows: 
 
a)      Effective December 8, 2003, a CWS supplier (either a surface water or 
groundwater supplier) designated by the Agency, by a SEP issued pursuant to 
Section 611.110, as vulnerable must sample for beta particle and photon 
radioactivity.  A supplier must collect quarterly samples for beta emitters and 
annual samples for tritium and strontium-90 at each entry point to the distribution 
system (hereafter called a sampling point), beginning within one quarter after 
being notified by the Agency.  A supplier already designated by the Agency must 
continue to sample until the Agency reviews and either reaffirms or removes the 
designation, by a SEP issued pursuant to Section 611.110. 
 
1)      If the gross beta particle activity minus the naturally occurring potassium-
40 beta particle activity at a sampling point has a running annual average 
(computed quarterly) less than or equal to 50 pCi/
ℓ
 (screening level), the 
Agency may reduce the frequency of monitoring at that sampling point to 
 
 91
once every three years.  A supplier must collect all samples required in 
subsection (a) of this Section during the reduced monitoring period. 
 
2)      For a supplier in the vicinity of a nuclear facility, the Agency may allow 
the CWS supplier to utilize environmental surveillance data collected by 
the nuclear facility in lieu of monitoring at the supplier’s entry points, 
where the Agency determines if such data is applicable to a particular 
water system, by a SEP issued pursuant to Section 611.110.  In the event 
that there is a release from a nuclear facility, a supplier that is using 
surveillance data must begin monitoring at the community water 
supplier’s entry points in accordance with subsection (b)(1) of this 
Section. 
 
b)      Effective December 8, 2003, a CWS supplier (either a surface water or 
groundwater supplier) designated by the Agency, by a SEP issued pursuant to 
Section 611.110, as utilizing waters contaminated by effluents from nuclear 
facilities must sample for beta particle and photon radioactivity.  A supplier must 
collect quarterly samples for beta emitters and iodine-131 and annual samples for 
tritium and strontium-90 at each entry point to the distribution system (hereafter 
called a sampling point), beginning within one quarter after being notified by the 
 Agency.  A supplier already designated by the Agency as a supplier using waters 
contaminated by effluents from nuclear facilities must continue to sample until 
the Agency reviews and either reaffirms or removes the designation, by a SEP 
issued pursuant to Section 611.110. 
 
1)      Quarterly monitoring for gross beta particle activity must be based on the 
analysis of monthly samples or the analysis of a composite of three 
monthly samples. 
 
BOARD NOTE:  In corresponding 40 CFR 141.26(b)(2)(i), USEPA 
recommends the use of a composite of three monthly samples. 
 
2)      For iodine-131, a composite of five consecutive daily samples must be 
analyzed once each quarter.  The Agency may, by a SEP issued pursuant 
to Section 611.110, order more frequent monitoring for iodine-131 where 
it is identified in the finished water. 
 
3)      Annual monitoring for strontium-90 and tritium must be conducted by 
means of the analysis of a composite of four consecutive quarterly 
samples or analysis of four quarterly samples. 
 
BOARD NOTE:  In corresponding 40 CFR 141.26(b)(2)(iii), USEPA 
recommends the analysis of four consecutive quarterly samples. 
 
4)      If the gross beta particle activity minus the naturally occurring potassium-
40 beta particle activity at a sampling point has a running annual average 
 
 92
(computed quarterly) less than or equal to 15 pCi/
ℓ
, the Agency may, by a 
SEP issued pursuant to Section 611.110, reduce the frequency of 
 monitoring at that sampling point to once every three years.  The supplier 
must collect all the same type of samples required in subsection (b) of this 
Section during the reduced monitoring period. 
 
5)      For a supplier in the vicinity of a nuclear facility, the Agency may allow 
the CWS to utilize environmental surveillance data collected by the 
nuclear facility in lieu of monitoring at the system’s entry points, where 
the Agency determines, by a SEP issued pursuant to Section 611.110, that 
such data is applicable to the particular water system.  In the event that 
there is a release from a nuclear facility, a supplier that uses such 
surveillance data must begin monitoring at the CWS’s entry points in 
accordance with subsection (b) of this Section. 
 
c)      Effective December 8, 2003, a CWS supplier designated by the Agency to 
monitor for beta particle and photon radioactivity can not apply to the Agency for 
a waiver from the monitoring frequencies specified in subsection (a) or (b) of this 
Section. 
 
d)      Effective December 8, 2003, a CWS supplier may analyze for naturally occurring 
potassium-40 beta particle activity from the same or equivalent sample used for 
the gross beta particle activity analysis.  A supplier is allowed to subtract the 
potassium-40 beta particle activity value from the total gross beta particle activity 
value to determine if the screening level is exceeded.  The potassium-40 beta 
particle activity must be calculated by multiplying elemental potassium 
concentrations (in mg/
ℓ
) by a factor of 0.82. 
 
e)      Effective December 8, 2003, if the gross beta particle activity minus the naturally 
occurring potassium-40 beta particle activity exceeds the appropriate screening 
level, an analysis of the sample must be performed to identify the major 
radioactive constituents present in the sample and the appropriate doses must be 
calculated and summed to determine compliance with Section 611.330(d)(1), 
using the formula in Section 611.330(d)(2).  Doses must also be calculated and 
combined for measured levels of tritium and strontium to determine compliance. 
 
f)      Effective December 8, 2003, a supplier must monitor monthly at the sampling 
points that exceeds the maximum contaminant level in Section 611.330(d) 
beginning the month after the exceedence occurs.  A supplier must continue 
monthly monitoring until the supplier has established, by a rolling average of 
three monthly samples, that the MCL is being met.  A supplier that establishes 
that the MCL is being met must return to quarterly monitoring until it meets the 
requirements set forth in subsection (a)(2) (a)(1) or (b)(1) (b)(4) of this Section. 
 
g)      Until December 8, 2003, CWSs using surface water sources and serving more 
than 100,000 persons and such other CWSs as the Agency, by a SEP issued 
 
 93
pursuant to Section 611.110, requires must monitor for compliance with Section 
611.331 by analysis of a composite of four consecutive quarterly samples or 
analysis of four quarterly samples.  Compliance with Section 611.331 is assumed 
 without further analysis if the average annual concentration of gross beta particle 
activity is less than 50 pCi/
ℓ
 and if the average annual concentrations of tritium 
and strontium-90 are less than those listed in Section 611.331, provided that if 
both radionuclides are present the sum of their annual dose equivalents to bone 
marrow must not exceed 4 millirem/year. 
 
1)      If the gross beta particle activity exceeds 50 pCi/
ℓ
, an analysis of the 
sample must be performed to identify the major radioactive constituents 
present and the appropriate organ and total body doses must be calculated 
to determine compliance with Section 611.331. 
 
2)      If the MCLs are exceeded, the Agency shall, by a SEP issued pursuant to 
Section 611.110, require the supplier to conduct additional monitoring to 
determine the concentration of man-made radioactivity in principal 
watersheds. 
 
3)      The Agency shall, pursuant to subsection (j) of this Section, by a SEP 
issued pursuant to Section 611.110, require suppliers of water utilizing 
only groundwater to monitor for man-made radioactivity. 
 
h)      Until December 8, 2003, CWS suppliers must monitor at least every four years 
following the procedure in subsection (g) of this Section. 
 
i)       Until December 8, 2003, the Agency must, by a SEP issued pursuant to Section 
611.110, require any CWS supplier utilizing waters contaminated by effluents 
from nuclear facilities to initiate quarterly monitoring for gross beta particle and 
 iodine-131 radioactivity and annual monitoring for strontium-90 and tritium. 
 
1)      Quarterly monitoring for gross beta particle activity must be based on the 
analysis of monthly samples or the analysis of a composite of three 
monthly samples.  If the gross beta particle activity in a sample exceeds 15 
pCi/
ℓ
, the same or an equivalent sample must be analyzed for strontium-
89 and cesium-134.  If the gross beta particle activity exceeds 50 pCi/
ℓ
, an 
analysis of the sample must be performed to identify the major radioactive 
constituents present and the appropriate organ and total body doses must 
be calculated to determine compliance with Section 611.331. 
 
2)      For iodine-131, a composite of five consecutive daily samples must be 
analyzed once each quarter.  The Agency shall, by a SEP issued pursuant 
to Section 611.110, require more frequent monitoring when iodine-131 is 
identified in the finished water. 
 
3)      The Agency shall, by a SEP issued pursuant to Section 611.110, require 
 
 94
annual monitoring for strontium-90 and tritium by means of the analysis 
of a composite of four consecutive quarterly samples or analysis of four 
quarterly samples. 
 
4)      The Agency shall, by a SEP issued pursuant to Section 611.110, allow the 
substitution of environmental surveillance data taken in conjunction with a 
nuclear facility for direct monitoring of manmade radioactivity by the 
 supplier where the Agency determines such data is applicable to the CWS. 
 
j)       Until December 8, 2003, if the average annual MCL for man-made radioactivity 
set forth in Section 611.331 is exceeded, the CWS supplier must give notice to the 
Agency and to the public as required by Subpart T.  Monitoring at monthly 
intervals must be continued until the concentration no longer exceeds the MCL or 
until a monitoring schedule as a condition to a variance, adjusted standard, or 
enforcement action becomes effective. 
 
BOARD NOTE:  Subsections (a) through (f) derive from 40 CFR 141.26(b) (2003). 
 
(Source:  Amended at 29 Ill. Reg. ________, effective ______________________) 
 
SUBPART X:  ENHANCED FILTRATION AND DISINFECTION--SYSTEMS 
SERVING FEWER THAN 10,000 PEOPLE 
 
Section 611.953       Disinfection Profile 
 
a)      Applicability.  A disinfection profile is a graphical representation of a system’s 
level of Giardia lamblia or virus inactivation measured during the course of a 
year.  A Subpart B community or non-transient non-community water system that 
serves fewer than 10,000 persons must develop a disinfection profile unless the 
Agency, by a SEP issued pursuant to Section 611.110, determines that a profile is 
unnecessary.  The Agency may approve the use of a more representative data set 
for disinfection profiling than the data set required under subsections (c) through 
(g) of this Section. 
 
b)      Determination that a disinfection profile is not necessary.  The Agency may only 
 determine that a disinfection profile is not necessary if the system’s TTHM and 
HAA5 levels are below 0.064 mg/
ℓ
 and 0.048 mg/
ℓ
, respectively.  To determine 
these levels, TTHM and HAA5 samples must have been collected after January 1, 
1998, during the month with the warmest water temperature, and at the point of 
maximum residence time in the distribution system.  The Agency may, by a SEP 
issued pursuant to Section 611.110, approve the use of a different data set to 
determine these levels if it determines that the data set is representative TTHM 
and HAA5 data. 
 
c)      Development of a disinfection profile.  A disinfection profile consists of the 
following three steps: 
 
 95
 
1)      First, the supplier must collect data for several parameters from the plant, 
as discussed in subsection (d) of this Section, over the course of 12 
months.  If the supplier serves between 500 and 9,999 persons it must 
have begun to collect data no later than July 1, 2003.  If the supplier 
serves fewer than 500 persons, it must begin to collect data no later than 
January 1, 2004. 
 
2)      Second, the supplier must use this data to calculate weekly log 
inactivation as discussed in subsections (e) and (f) of this Section; and 
 
3)      Third, the supplier must use these weekly log inactivations to develop a 
disinfection profile as specified in subsection (g) of this Section. 
 
d)      Data required for a disinfection profile.  A supplier must monitor the following 
 parameters to determine the total log inactivation using the analytical methods in 
Section 611.231, once per week on the same calendar day, over 12 consecutive 
months: 
 
1)      The temperature of the disinfected water at each residual disinfectant 
concentration sampling point during peak hourly flow; 
 
2)      If a supplier uses chlorine, the pH of the disinfected water at each residual 
disinfectant concentration sampling point during peak hourly flow; 
 
3)      The disinfectant contact times (“T”) during peak hourly flow; and 
 
4)      The residual disinfectant concentrations (“C”) of the water before or at the 
first customer and prior to each additional point of disinfection during 
peak hourly flow. 
 
e)      Calculations based on the data collected.  The tables in Appendix B of this Part 
must be used to determine the appropriate CT99.9 value.  The supplier must 
calculate the total inactivation ratio as follows, and multiply the value by 3.0 to 
determine log inactivation of Giardia lamblia: 
 
1)      If the supplier uses only one point of disinfectant application, it must 
determine either of the following: 
 
A)      One inactivation ratio (CTcalc/CT99.9) before or at the first customer 
during peak hourly flow; or 
 
B) Successive CTcalc/CT99.9 values, representing sequential 
inactivation ratios, between the point of disinfectant application 
and a point before or at the first customer during peak hourly flow.  
 Under this alternative, the supplier must calculate the total 
 
 96
inactivation ratio by determining CTcalc/CT99.9 for each sequence 
and then adding the CTcalc/CT99.9 values together to determine 
∑
CTcalc/CT99.9. 
 
2)      If the supplier uses more than one point of disinfectant application before 
the first customer, it must determine the CTcalc/CT99.9 value of each 
disinfection segment immediately prior to the next point of disinfectant 
application, or for the final segment, before or at the first customer, during 
peak hourly flow using the procedure specified in subsection (e)(1)(B) of 
this Section. 
 
f)      Use of chloramines, ozone, or chlorine dioxide as a primary disinfectant.  If a 
supplier uses chloramines, ozone, or chlorine dioxide for primary disinfection, the 
supplier must also calculate the logs of inactivation for viruses and develop an 
additional disinfection profile for viruses using methods approved by the Agency. 
 
g)      Development and maintenance of the disinfection profile in graphic form.  Each 
log inactivation serves as a data point in the supplier’s disinfection profile.  A 
supplier will have obtained 52 measurements (one for every week of the year).  
This will allow the supplier and the Agency the opportunity to evaluate how 
microbial inactivation varied over the course of the year by looking at all 52 
measurements (the supplier’s disinfection profile).  The supplier must retain the 
 disinfection profile data in graphic form, such as a spreadsheet, which must be 
available for review by the Agency as part of a sanitary survey.  The supplier 
must use this data to calculate a benchmark if the supplier is considering changes 
to disinfection practices. 
 
BOARD NOTE:  Derived from 40 CFR 141.530 through 141.536 (2002) (2003). 
 
(Source:  Amended at 29 Ill. Reg. ________, effective ______________________) 
 
Section 611.956       Individual Filter Turbidity Requirements 
 
a)      Applicability.  A Subpart B system supplier that serves fewer than 10,000 persons 
and utilizing conventional filtration or direct filtration must conduct continuous 
monitoring of turbidity for each individual filter in a supplier’s system.  The 
following requirements apply to continuous turbidity monitoring: 
 
1)      Monitoring must be conducted using an approved method in Section 
611.231; 
 
2)      Calibration of turbidimeters must be conducted using procedures specified 
by the manufacturer; 
 
3)      Results of turbidity monitoring must be recorded at least every 15 
minutes; 
 
 97
 
4)      Monthly reporting must be completed according to Section 611.957(a); 
and 
 
5)      Records must be maintained according to Section 611.957(b). 
 
b)      Failure of turbidity monitoring equipment.  If there is a failure in the continuous 
turbidity monitoring equipment, the supplier must conduct grab sampling every 
 four hours in lieu of continuous monitoring until the turbidimeter is back on-line.  
The supplier has 14 days to resume continuous monitoring before a violation is 
incurred. 
 
c)      Special requirements for systems with two or fewer filters.  If a supplier’s system 
only consists of two or fewer filters, the supplier may conduct continuous 
monitoring of combined filter effluent turbidity in lieu of individual filter effluent 
turbidity monitoring.  Continuous monitoring must meet the same requirements 
set forth in subsections (a)(1) through (a)(4) and (b) of this Section. 
 
d)      Follow-up action.  Follow-up action is required according to the following 
requirements: 
 
1)      If the turbidity of an individual filter (or the turbidity of combined filter 
effluent (CFE) for a system with two filters that monitor CFE in lieu of 
individual filters) exceeds 1.0 NTU in two consecutive recordings 15 
minutes apart, the supplier must report to the Agency by the 10th of the 
following month and include the filter numbers, corresponding dates, 
turbidity values that exceeded 1.0 NTU, and the cause (if known) for the 
exceedences. 
 
2)      If a supplier was required to report to the Agency for three months in a 
row and turbidity exceeded 1.0 NTU in two consecutive recordings 15 
minutes apart at the same filter (or CFE for systems with two filters that 
monitor CFE in lieu of individual filters), the supplier must conduct a self-
assessment of the filters within 14 days of the day on which the filter 
 exceeded 1.0 NTU in two consecutive measurements for the third straight 
month, unless a CPE, as specified in subsection (d)(3) of this Section, was 
required.  A supplier that has a system with two filters that monitor CFE in 
lieu of individual filters must conduct a self assessment on both filters.  
The self-assessment must consist of at least the following components:  
assessment of filter performance, development of a filter profile, 
identification and prioritization of factors limiting filter performance, 
assessment of the applicability of corrections, and preparation of a filter 
self-assessment report.  If a self-assessment is required, the date that it was 
triggered and the date that it was completed.
 
3)      If a supplier was required to report to the Agency for two months in a row 
 
 98
and turbidity exceeded 2.0 NTU in two consecutive recordings 15 minutes 
apart at the same filter (or CFE for systems with two filters that monitor 
CFE in lieu of individual filters), the supplier must arrange to have a 
comprehensive performance evaluation (CPE) conducted by the Agency 
or a third party approved by the Agency not later than 60 days following 
the day the filter exceeded 2.0 NTU in two consecutive measurements for 
the second straight month.  If a CPE has been completed by the Agency or 
a third party approved by the Agency within the 12 prior months or the 
system and Agency are jointly participating in an ongoing comprehensive 
technical assistance (CTA) project at the system, a new CPE is not 
 required.  If conducted, a CPE must be completed and submitted to the 
Agency no later than 120 days following the day the filter exceeded 2.0 
NTU in two consecutive measurements for the second straight month. 
 
e)      Special individual filter monitoring for a lime-softening system.  If a supplier’s 
system utilizes lime softening, the supplier may apply to the Agency for 
alternative turbidity exceedence levels for the levels specified in subsection (d) of 
this Section.  The supplier must be able to demonstrate to the Agency that higher 
turbidity levels are due to lime carryover only, and not due to degraded filter 
performance. 
 
BOARD NOTE:  Derived from 40 CFR 141.560 through 141.564 (2002) (2003). 
 
(Source:  Amended at 29 Ill. Reg. ________, effective ______________________) 
 
Section 611.Appendix G      NPDWR Violations and Situations Requiring Public Notice 
 
See note 1 at the end of this Appendix G for an explanation of the Agency’s authority to alter the 
magnitude of a violation from that set forth in the following table. 
 
 MCL/MRDL/TT 
 violations
2
Monitoring & testing 
procedure violations 
Contaminant Tier 
 of 
public 
notice 
required 
Citation Tier of 
public 
notice 
required 
Citation 
 
I. Violations of National Primary Drinking Water Regulations (NPDWR):
3
 
A. Microbiological Contaminants 
1. Total coliform 
 2 
 611.325(a) 
 3 
 611.521-
611.525 
2. Fecal coliform/E. coli 
 1 
 611.325(b) 
4
 1, 3 
 611.525 
3. Turbidity MCL 
 2 
 611.320(a) 
 3 
 611.560 
 
 99
4. Turbidity MCL (average of 
two days’ samples greater than 5 
NTU) 
5
 2, 1 
 611.320(b) 
 3 
 611.560 
5. Turbidity (for TT violations 
resulting from a single 
exceedence of maximum 
allowable turbidity level) 
6
 2, 1 
 611.231(b), 
611.233(b)(1), 
611.250(a)(2), 
611.250(b)(2), 
611.250(c)(2), 
611.250(d), 
611.743(a)(2), 
611.743(b), 
611.955(b)(2) 
3 611.531(a), 
611.532(b), 
611.533(a), 
611.744, 
611.956(a)(1)-
(a)(3), 
611.956(b) 
6. Surface Water Treatment 
Rule violations, other than 
violations resulting from single 
exceedence of max. allowable 
turbidity level (TT) 
2 611.211, 
611.213, 
611.220, 
611.230-
611.233, 
611.240-
611.242, 
611.250 
3 611.531-
611.533 
7. Interim Enhanced Surface 
Water Treatment Rule 
violations, other than violations 
 resulting from single 
exceedence of max. turbidity 
level (TT) 
2 
7
 611.740-
611.743, 
611.950-
611.955 
3 611.742, 
611.744, 
611.953, 
611.954, 
611.956 
8. Filter Backwash Recycling 
Rule violations 
2 611.276(c)
 3 611.276(b), (d)
9. Long Term 1 Enhanced 
Surface Water Treatment Rule 
violations 
2 611.950-
611.955 
3 611.953, 
611.954, 
611.956 
 
B. Inorganic Chemicals (IOCs) 
1. Antimony 
 2 611.301(b) 
 3 611.600, 
611.601, 
611.603 
2. Arsenic 
 2 
10
 611.301(b) 
 3 
9
 611.601, 
611.612(a), 
611.612(b) 
3. Asbestos (fibers greater than 
10 μm) 
2 611.301(b) 
 3 611.600, 
611.601, 
611.602 
4. Barium 
 2 611.301(b) 
 3 611.600, 
611.601, 
611.603 
 
 100
5. Beryllium 
 2 611.301(b) 
 3 611.600, 
611.601, 
611.603 
6. Cadmium 
 2 611.301(b) 
 3 611.600, 
611.601, 
611.603 
7. Chromium (total) 
 2 
 611.301(b) 
 3 
 611.600, 
611.601, 
611.603 
8. Cyanide 
 2 611.301(b) 
 3 611.600, 
611.601, 
611.603 
9. Fluoride 
 2 611.301(b) 
 3 611.600, 
611.601, 
611.603 
10. Mercury (inorganic) 
 2 
 611.301(b) 
 3 
 611.600, 
611.601, 
611.603 
11. Nitrate 
 1 
 611.301(b) 
10
 1, 3 
 611.600, 
611.601, 
611.604, 
611.606 
12. Nitrite 
 1 
 611.301(b) 
10
 1, 3 
 611.600, 
611.601, 
611.605, 
611.606 
13. Total Nitrate and Nitrite 
 1 
 611.301(b) 
 3 
 611.600, 
611.601 
14. Selenium 
 2 611.301(b) 
 3 611.600, 
611.601, 
611.603 
15. Thallium 
 2 611.301(b) 
 3 611.600, 
611.601, 
611.603 
 
C. Lead and Copper Rule (Action Level for lead is 0.015 mg/
ℓ
, for copper is 1.3 mg/
ℓ
) 
1. Lead and Copper Rule (TT) 
 2 
 611.350-
611.355 
3 611.356-
611.359 
 
D. Synthetic Organic Chemicals (SOCs) 
1. 2,4-D 
 2 611.310(c) 
 3 611.648 
2. 2,4,5-TP (silvex) 
 2 
 611.310(c) 
 3 
 611.648 
3. Alachlor 
 2 611.310(c) 
 3 611.648 
4. Atrazine 
 2 611.310(c) 
 3 611.648 
5. Benzo(a)pyrene (PAHs) 
 2 
 611.310(c) 
 3 
 611.648 
 
 101
6. Carbofuran 
 2 611.310(c) 
 3 611.648 
7. Chlordane 
 2 611.310(c) 
 3 611.648 
8. Dalapon 
 2 611.310(c) 
 3 611.648 
9. Di(2-ethylhexyl)adipate 
 2 611.310(c) 
 3 611.648 
10. Di(2-ethylhexyl)phthalate 
 2 611.310(c) 
 3 611.648 
11. Dibromochloropropane 
(DBCP) 
2 611.310(c) 
 3 611.648 
12. Dinoseb 
 2 611.310(c) 
 3 611.648 
13. Dioxin (2,3,7,8-TCDD) 
 2 
 611.310(c) 
 3 
 611.648 
14. Diquat 
 2 611.310(c) 
 3 611.648 
15. Endothall 
 2 611.310(c) 
 3 611.648 
16. Endrin 
 2 611.310(c) 
 3 611.648 
17. Ethylene dibromide 
 2 
 611.310(c) 
 3 
 611.648 
18. Glyphosate 
 2 611.310(c) 
 3 611.648 
19. Heptachlor 
 2 611.310(c) 
 3 611.648 
20. Heptachlor epoxide 
 2 
 611.310(c) 
 3 
 611.648 
21. Hexachlorobenzene 
 2 611.310(c) 
 3 611.648 
22. Hexachlorocyclopentadiene 
 2 611.310(c) 
 3 611.648 
23. Lindane 
 2 611.310(c) 
 3 611.648 
 24. Methoxychlor 
 2 611.310(c) 
 3 611.648 
25. Oxamyl (Vydate) 
 2 
 611.310(c) 
 3 
 611.648 
26. Pentachlorophenol 2 611.310(c) 
 3 611.648 
27. Picloram 
 2 611.310(c) 
 3 611.648 
28. Polychlorinated biphenyls 
(PCBs) 
2 611.310(c) 
 3 611.648 
29. Simazine 
 2 611.310(c) 
 3 611.648 
30. Toxaphene 
 2 611.310(c) 
 3 611.648 
 
E. Volatile Organic Chemicals (VOCs) 
1. Benzene 
 2 611.310(a) 
 3 611.646 
2. Carbon tetrachloride 
 2 
 611.310(a) 
 3 
 611.646 
3. Chlorobenzene 
(monochlorobenzene) 
2 611.310(a) 
 3 611.646 
4. o-Dichlorobenzene  2 611.310(a) 
 3 611.646 
5. p-Dichlorobenzene  2 611.310(a) 
 3 611.646 
6. 1,2-Dichloroethane  2 611.310(a) 
 3 611.646 
7. 1,1-Dichloroethylene 
 2 611.310(a) 
 3 611.646 
8. cis-1,2-Dichloroethylene 
 2 611.310(a) 
 3 611.646 
9. trans-1,2-Dichloroethylene 
 2 611.310(a) 
 3 611.646 
10. Dichloromethane 
 2 611.310(a) 
 3 611.646 
11. 1,2-Dichloropropane 
 2 611.310(a) 
 3 611.646 
12. Ethylbenzene 
 2 611.310(a) 
 3 611.646 
13. Styrene 
 2 611.310(a) 
 3 611.646 
14. Tetrachloroethylene 
 2 611.310(a) 
 3 611.646 
 
 102
15. Toluene 
 2 611.310(a) 
 3 611.646 
16. 1,2,4-Trichlorobenzene 
 2 611.310(a) 
 3 611.646 
17. 1,1,1-Trichloroethane 
 2 611.310(a) 
 3 611.646 
18. 1,1,2-Trichloroethane 
 2 611.310(a) 
 3 611.646 
19. Trichloroethylene  2 611.310(a) 
 3 611.646 
20. Vinyl chloride 
 2 
 611.310(a) 
 3 
 611.646 
21. Xylenes (total) 
 2 
 611.310(a) 
 3 
 611.646 
 
F. Radioactive Contaminants 
1. Beta/photon emitters 
 2 
 611.330(d) 
 3 
 611.720(a), 
611.732 
2. Alpha emitters 
 2 
 611.330(c) 
 3 
 611.720(a), 
611.731 
3. Combined radium (226 & 
228) 
2 611.330(b) 
 3 611.720(a), 
611.731 
4. Uranium 
 2 611.330(e) 
 3 611.720(a), 
611.731 
 
G. Disinfection Byproducts (DBPs), Byproduct Precursors, Disinfectant Residuals.  Where 
disinfection is used in the treatment of drinking water, disinfectants combine with organic and 
inorganic matter present in water to form chemicals called disinfection byproducts (DBPs).  
USEPA sets standards for controlling the levels of disinfectants and DBPs in drinking water, 
including trihalomethanes (THMs) and haloacetic acids (HAAs).
13
1. Total trihalomethanes 
 (TTHMs) 
2 611.312(a) 
 3 611.382(a)-(b) 
2. Haloacetic Acids (HAA5) 
 2 
 611.312(a) 
 3 
 611.382(a)-(b) 
3. Bromate 
 2 611.312(a) 
 3 611.382(a)-(b) 
4. Chlorite 
 2 611.312(a) 
 3 611.382(a)-(b) 
5. Chlorine (MRDL) 
 2 
 611.313(a) 
 3 
 611.382(a), (c) 
6. Chloramine (MRDL) 
 2 
 611.313(a) 
 3 
 611.382(a), (c) 
7. Chlorine dioxide (MRDL), 
where any two consecutive daily 
samples at entrance to 
distribution system only are 
above MRDL 
2 611.313(a), 
611.383(c)(3) 
2 
15
, 3 
 611.382(a), (c), 
611.383(c)(2) 
8. Chlorine dioxide (MRDL), 
where samples in distribution 
system the next day are also 
above MRDL 
16
 1 
 611.313(a), 
611.383(c)(3) 
1 611.382(a), (c), 
611.383(c)(2) 
9. Control of DBP precursors--
TOC (TT) 
2 611.385(a)-(b) 
 3 611.382(a), (d) 
10. Benchmarking and 
disinfection profiling 
N/A N/A 
 3 
 611.742, 
611.953, 
611.954 
 
 103
11. Development of monitoring 
plan 
N/A N/A 
 3 
 611.382(f) 
 
H. Other Treatment Techniques 
1. Acrylamide (TT) 
 2 
 611.296 
 N/A 
 N/A 
2. Epichlorohydrin (TT) 
 2 
 611.296 
 N/A 
 N/A 
 
II. Unregulated Contaminant Monitoring: 
17
A. Unregulated contaminants 
 N/A 
 N/A 
 3 
 611.510 
B. Nickel 
 N/A 
 N/A 
 3 
 611.603, 
611.611 
 
III. Public Notification for Relief Equivalent to a SDWA section 1415 Variance or a section 
1416 Exemption. 
A. Operation under relief 
equivalent to a SDWA section 
1415 variance or a section 1416 
exemption 
3 
18
 1415, 1416 
 N/A 
 N/A 
B. Violation of conditions of 
relief equivalent to a SDWA 
section 1415 variance or a 
section 1416 exemption 
2 1415, 1416, 
19
 
611.111, 
611.112 
N/A N/A 
 
IV. Other Situations Requiring Public Notification. 
A. Fluoride secondary 
maximum contaminant level 
(SMCL) exceedence 
3 611.858 
 N/A 
 N/A 
B. Exceedence of nitrate MCL 
for a non-CWS supplier, as 
allowed by the Agency 
1 611.300(d) 
 N/A 
 N/A 
C. Availability of unregulated 
contaminant monitoring data 
3 611.510 
 N/A 
 N/A 
D. Waterborne disease outbreak 
 1 
 611.101, 
611.233(b)(2) 
N/A N/A 
E. Other waterborne 
emergency
20
1 N/A 
 N/A 
 N/A 
F. Other situations as 
determined by the Agency by a 
SEP issued pursuant to Section 
611.110 
1, 2, 3 
 N/A 
 N/A 
 N/A 
 
Appendix G--Endnotes 
 
1. Violations and other situations not listed in this table (e.g., reporting violations and failure to 
prepare Consumer Confidence Reports) do not require notice, unless otherwise determined by 
 
 104
the Agency by a SEP issued pursuant to Section 611.110.  The Agency may, by a SEP issued 
pursuant to Section 611.110, further require a more stringent public notice tier (e.g., Tier 1 
instead of Tier 2 or Tier 2 instead of Tier 3) for specific violations and situations listed in this 
Appendix, as authorized under Sections 611.902(a) and 611.903(a). 
 
2. Definition of the abbreviations used:  “MCL” means maximum contaminant level, “MRDL” 
means maximum residual disinfectant level, and “TT” means treatment technique. 
 
3. The term “violations of National Primary Drinking Water Regulations (NPDWR)” is used 
here to include violations of MCL, MRDL, treatment technique, monitoring, and testing 
procedure requirements. 
 
4. Failure to test for fecal coliform or E. coli is a Tier 1 violation if testing is not done after any 
repeat sample tests positive for coliform.  All other total coliform monitoring and testing 
 procedure violations are Tier 3 violations. 
 
5. A supplier that violates the turbidity MCL of 5 NTU based on an average of measurements 
over two consecutive days must consult with the Agency within 24 hours after learning of the 
violation.  Based on this consultation, the Agency may subsequently decide to issue a SEP 
pursuant to Section 611.110 that elevates the violation to a Tier 1 violation.  If a supplier is 
unable to make contact with the Agency in the 24-hour period, the violation is automatically 
elevated to a Tier 1 violation. 
 
6. A supplier with a treatment technique violation involving a single exceedence of a maximum 
turbidity limit under the Surface Water Treatment Rule (SWTR), the Interim Enhanced Surface 
Water Treatment Rule (IESWTR), or the Long Term 1 Enhanced Surface Water Treatment Rule 
are required to consult with the Agency within 24 hours after learning of the violation.  Based on 
this consultation, the Agency may subsequently decide to issue a SEP pursuant to Section 
611.110 that elevates the violation to a Tier 1 violation.  If a supplier is unable to make contact 
with the Agency in the 24-hour period, the violation is automatically elevated to a Tier 1 
violation. 
 
7. The Surface Water Treatment Rule (SWTR) remains in effect for a supplier serving at least 
10,000 persons; the Interim Enhanced Surface Water Treatment Rule adds additional 
requirements and does not in many cases supercede the SWTR. 
 
8. The arsenic MCL citations are effective January 23, 2006.  Until then, the citations are 
 Sections 611.330(b) and 611.612(c). 
 
9. The arsenic Tier 3 violation MCL citations are effective January 23, 2006.  Until then, the 
citations are Sections 611.100, 611.101, and 611.612. 
 
10. Failure to take a confirmation sample within 24 hours for nitrate or nitrite after an initial 
sample exceeds the MCL is a Tier 1 violation. Other monitoring violations for nitrate are Tier 3. 
 
11. This endnote 11 corresponds with the endnote to the table in Appendix A to Subpart Q of 40 
 
 105
CFR 141 (2003), which stated a past effective date.  This statement maintains structural 
consistency with the federal regulations. 
 
12. This endnote 12 corresponds with the endnote to the table in Appendix A to Subpart Q of 40 
CFR 141 (2003), which stated a past effective date.  This statement maintains structural 
consistency with the federal regulations. 
 
13. A Subpart B community or non-transient non-community system supplier must comply with 
new DBP MCLs, disinfectant MRDLs, and related monitoring requirements.  A Subpart B 
transient non-community system supplier serving 10,000 or more persons that uses chlorine 
dioxide as a disinfectant or oxidant or a Subpart B transient non-community system supplier that 
serves fewer than 10,000 persons, which uses only groundwater not under the direct influence of 
surface water, and which uses chlorine dioxide as a disinfectant or oxidant must comply with the 
chlorine dioxide MRDL. 
 
14. This endnote 14 corresponds with the endnote to the table in Appendix A to Subpart Q of 40 
 CFR 141 (2003), which stated a past effective date.  This statement maintains structural 
consistency with the federal regulations. 
 
15. Failure to monitor for chlorine dioxide at the entrance to the distribution system the day after 
exceeding the MRDL at the entrance to the distribution system is a Tier 2 violation. 
 
16. If any daily sample taken at the entrance to the distribution system exceeds the MRDL for 
chlorine dioxide and one or more samples taken in the distribution system the next day exceed 
the MRDL, Tier 1 notification is required.  A failure to take the required samples in the 
distribution system after the MRDL is exceeded at the entry point also triggers Tier 1 
notification. 
 
17. Some water suppliers must monitor for certain unregulated contaminants listed in Section 
611.510. 
 
18. This citation refers to sections 1415 and 1416 of the federal Safe Drinking Water Act. 
sections 1415 and 1416 require that “a schedule prescribed . . . for a public water system granted 
relief equivalent to a SDWA section 1415 variance or a section 1416 exemption must require 
compliance by the system . . ..” 
 
19. In addition to sections 1415 and 1416 of the federal Safe Drinking Water Act, 40 CFR 
142.307 specifies the items and schedule milestones that must be included in relief equivalent to 
a SDWA section 1415 small system variance.  In granting any form of relief from an NPDWR, 
the Board will consider all applicable federal requirements for and limitations on the State’s 
ability to grant relief consistent with federal law. 
 
20. Other waterborne emergencies require a Tier 1 public notice under Section 611.902(a) for 
situations that do not meet the definition of a waterborne disease outbreak given in Section 
611.101, but which still have the potential to have serious adverse effects on health as a result of 
short-term exposure.  These could include outbreaks not related to treatment deficiencies, as well 
 
 106
as situations that have the potential to cause outbreaks, such as failures or significant interruption 
in water treatment processes, natural disasters that disrupt the water supply or distribution 
system, chemical spills, or unexpected loading of possible pathogens into the source water. 
 
BOARD NOTE:  Derived from Appendix A to Subpart Q to 40 CFR 141 (2003). 
 
(Source:  Amended at 29 Ill. Reg. ________, effective ______________________) 
 
Section 611.Appendix H      Standard Health Effects Language for Public Notification 
 
Contaminant MCLG
1
 
mg/
ℓ
 
MCL
2
 mg/
ℓ
 
 Standard health effects language 
for public notification 
National Primary Drinking Water Regulations (NPDWR): 
A. Microbiological Contaminants 
1a. Total coliform 
 Zero 
 See footnote 
3 
Coliforms are bacteria that are 
naturally present in the 
environment and are used as an 
indicator that other, potentially-
 harmful, bacteria may be present. 
Coliforms were found in more 
samples than allowed and this was 
a warning of potential problems. 
1b. Fecal coliform/E. coli 
 Zero 
 Zero 
 Fecal coliforms and E. coli are 
bacteria whose presence indicates 
that the water may be contaminated 
with human or animal wastes. 
Microbes in these wastes can cause 
short-term effects, such as diarrhea, 
cramps, nausea, headaches, or other 
symptoms. They may pose a 
special health risk for infants, 
young children, some of the 
elderly, and people with severely 
compromised immune systems. 
2a. Turbidity (MCL) 
4
None 1 NTU
5
/ 
5 NTU 
Turbidity has no health effects. 
However, turbidity can interfere 
with disinfection and provide a 
medium for microbial growth. 
Turbidity may indicate the 
presence of disease-causing 
organisms. These organisms 
include bacteria, viruses, and 
parasites that can cause symptoms 
such as nausea, cramps, diarrhea, 
and associated headaches. 
 
 107
2b. Turbidity (SWTR TT) 
 None 
 TT
7
Turbidity has no health effects. 
However,
6
 turbidity can interfere 
with disinfection and provide a 
medium for microbial growth. 
 Turbidity may indicate the 
presence of disease-causing 
organisms. These organisms 
include bacteria, viruses, and 
parasites that can cause symptoms 
such as nausea, cramps, diarrhea, 
and associated headaches. 
2c. Turbidity (IESWTR TT 
and LT1ESWTR TT) 
None 
 TT 
 Turbidity has no health effects. 
However,
8
 turbidity can interfere 
with disinfection and provide a 
medium for microbial growth. 
Turbidity may indicate the 
presence of disease-causing 
organisms. These organisms 
include bacteria, viruses, and 
parasites that can cause symptoms 
such as nausea, cramps, diarrhea, 
and associated headaches. 
B. Surface Water Treatment Rule (SWTR), Interim Enhanced Surface Water Treatment Rule 
(IESWTR), Long Term 1 Enhanced Surface Water Treatment Rule (LT1ESWTR), and Filter 
Backwash Recycling Rule (FBRR) violations: 
3. Giardia lamblia 
(SWTR/IESWTR/ 
LT1ESWTR) 
Zero TT
10
Inadequately treated water may 
contain disease-causing organisms. 
These organisms include bacteria, 
viruses, and parasites that can 
cause symptoms such as nausea, 
cramps, diarrhea, and associated 
headaches. 
4. Viruses 
(SWTR/IESWTR/ 
LT1ESWTR) 
 
  
 Inadequately treated water may 
contain disease-causing organisms. 
 These organisms include bacteria, 
viruses, and parasites that can 
cause symptoms such as nausea, 
cramps, diarrhea, and associated 
headaches. 
 
 108
5. Heterotrophic plate count 
(HPC) bacteria
9
 
(SWTR/IESWTR/ 
LT1ESWTR) 
 
  
 Inadequately treated water may 
contain disease-causing organisms. 
These organisms include bacteria, 
viruses, and parasites that can 
cause symptoms such as nausea, 
cramps, diarrhea, and associated 
headaches. 
6. Legionella 
(SWTR/IESWTR/ 
LT1ESWTR) 
 
  
 Inadequately treated water may 
contain disease-causing organisms. 
These organisms include bacteria, 
viruses, and parasites that can 
cause symptoms such as nausea, 
cramps, diarrhea, and associated 
headaches. 
7. Cryptosporidium 
(IESWTR/FBRR/ 
LT1ESWTR) 
 
  
 Inadequately treated water may 
contain disease-causing organisms. 
These organisms include bacteria, 
viruses, and parasites that can 
cause symptoms such as nausea, 
cramps, diarrhea, and associated 
headaches. 
C. Inorganic Chemicals (IOCs) 
8. Antimony 
 0.006 
 0.006 
 Some people who drink water 
containing antimony well in excess 
of the MCL over many years could 
 experience increases in blood 
cholesterol and decreases in blood 
sugar. 
9. Arsenic
11
0 
 0.010 
 Some people who drink water 
containing arsenic in excess of the 
MCL over many years could 
experience skin damage or 
problems with their circulatory 
system, and may have an increased 
risk of getting cancer. 
10. Asbestos (10 μm) 
 7 MFL
12
7 MFL 
 Some people who drink water 
containing asbestos in excess of the 
MCL over many years may have an 
increased risk of developing benign 
intestinal polyps. 
11. Barium 
 2 
 2 
 Some people who drink water 
containing barium in excess of the 
MCL over many years could 
experience an increase in their 
blood pressure. 
 
 109
12. Beryllium 
 0.004 
 0.004 
 Some people who drink water 
containing beryllium well in excess 
of the MCL over many years could 
develop intestinal lesions. 
13. Cadmium 
 0.005 
 0.005 
 Some people who drink water 
containing cadmium in excess of 
the MCL over many years could 
experience kidney damage. 
14. Chromium (total) 
 0.1 
 0.1 
 Some people who use water 
containing chromium well in 
excess of the MCL over many 
years could experience allergic 
 dermatitis. 
15. Cyanide 
 0.2 
 0.2 
 Some people who drink water 
containing cyanide well in excess 
of the MCL over many years could 
experience nerve damage or 
problems with their thyroid. 
16. Fluoride 
 4.0 
 4.0 
 Some people who drink water 
containing fluoride in excess of the 
MCL over many years could get 
bone disease, including pain and 
tenderness of the bones. Fluoride in 
drinking water at half the MCL or 
more may cause mottling of 
children’s teeth, usually in children 
less than nine years old. Mottling, 
also known as dental fluorosis, may 
include brown staining or pitting of 
the teeth, and occurs only in 
developing teeth before they erupt 
from the gums. 
17. Mercury (inorganic) 
 0.002 
 0.002 
 Some people who drink water 
containing inorganic mercury well 
in excess of the MCL over many 
years could experience kidney 
damage. 
18. Nitrate 
 10 
 10 
 Infants below the age of six months 
who drink water containing nitrate 
in excess of the MCL could 
become seriously ill and, if 
untreated, may die. Symptoms 
include shortness of breath and 
blue baby syndrome. 
 
 110
19. Nitrite 
 1 
 1 
 Infants below the age of six months 
who drink water containing nitrite 
in excess of the MCL could 
become seriously ill and, if 
untreated, may die. Symptoms 
include shortness of breath and 
blue baby syndrome. 
20. Total Nitrate and Nitrite 
 10 
 10 
 Infants below the age of six months 
who drink water containing nitrate 
and nitrite in excess of the MCL 
could become seriously ill and, if 
untreated, may die. Symptoms 
include shortness of breath and 
blue baby syndrome. 
21. Selenium 
 0.05 
 0.05 
 Selenium is an essential nutrient. 
However, some people who drink 
water containing selenium in 
excess of the MCL over many 
years could experience hair or 
fingernail losses, numbness in 
fingers or toes, or problems with 
their circulation. 
22. Thallium 
 0.0005 
 0.002 
 Some people who drink water 
containing thallium in excess of the 
MCL over many years could 
experience hair loss, changes in 
their blood, or problems with their 
kidneys, intestines, or liver. 
D. Lead and Copper Rule 
23. Lead 
 Zero 
 TT
13
Infants and children who drink 
water containing lead in excess of 
the action level could experience 
delays in their physical or mental 
development. Children could show 
slight deficits in attention span and 
learning abilities. Adults who drink 
this water over many years could 
 develop kidney problems or high 
blood pressure. 
 
 111
24. Copper 
 1.3 
 TT
14
Copper is an essential nutrient, but 
some people who drink water 
containing copper in excess of the 
action level over a relatively short 
amount of time could experience 
gastrointestinal distress. Some 
people who drink water containing 
copper in excess of the action level 
over many years could suffer liver 
or kidney damage.  People with 
Wilson’s Disease should consult 
their personal doctor. 
E. Synthetic Organic Chemicals (SOCs) 
25. 2,4-D 
 0.07 
 0.07 
 Some people who drink water 
containing the weed killer 2,4-D 
well in excess of the MCL over 
many years could experience 
problems with their kidneys, liver, 
or adrenal glands. 
26. 2,4,5-TP (silvex) 
 0.05 
 0.05 
 Some people who drink water 
containing silvex in excess of the 
MCL over many years could 
experience liver problems. 
27. Alachlor 
 Zero 
 0.002 
 Some people who drink water 
containing alachlor in excess of the 
MCL over many years could have 
problems with their eyes, liver, 
kidneys, or spleen, or experience 
anemia, and may have an increased 
risk of getting cancer. 
28. Atrazine 
 0.003 
 0.003 
 Some people who drink water 
containing atrazine well in excess 
of the MCL over many years could 
experience problems with their 
cardiovascular system or 
reproductive difficulties. 
29. Benzo(a)pyrene 
(PAHs). 
Zero 
 0.0002 
 Some people who drink water 
containing benzo(a)pyrene in 
excess of the MCL over many 
years may experience reproductive 
difficulties and may have an 
increased risk of getting cancer. 
 
 112
30. Carbofuran 
 0.04 
 0.04 
 Some people who drink water 
containing carbofuran in excess of 
the MCL over many years could 
experience problems with their 
blood, or nervous or reproductive 
systems. 
31. Chlordane 
 Zero 
 0.002 
 Some people who drink water 
containing chlordane in excess of 
the MCL over many years could 
experience problems with their 
liver or nervous system, and may 
have an increased risk of getting 
cancer. 
32. Dalapon 
 0.2 
 0.2 
 Some people who drink water 
containing dalapon well in excess 
of the MCL over many years could 
experience minor kidney changes. 
33. Di(2-ethylhexyl)adipate 
 0.4 
 0.4 
 Some people who drink water 
containing di(2-ethylhexyl)adipate 
well in excess of the MCL over 
many years could experience toxic 
 effects, such as weight loss, liver 
enlargement, or possible 
reproductive difficulties. 
34. Di(2-ethylhexyl)-
phthalate 
Zero 
 0.006 
 Some people who drink water 
containing di(2-
ethylhexyl)phthalate well in excess 
of the MCL over many years may 
have problems with their liver or 
experience reproductive 
difficulties, and they may have an 
increased risk of getting cancer. 
35. Dibromochloropropane 
(DBCP) 
Zero 
 0.0002 
 Some people who drink water 
containing DBCP in excess of the 
MCL over many years could 
experience reproductive difficulties 
and may have an increased risk of 
getting cancer. 
36. Dinoseb 
 0.007 
 0.007 
 Some people who drink water 
containing dinoseb well in excess 
of the MCL over many years could 
experience reproductive 
difficulties. 
 
 113
37. Dioxin (2,3,7,8-TCDD) 
 Zero 
 3 x 10
-8
Some people who drink water 
containing dioxin in excess of the 
MCL over many years could 
experience reproductive difficulties 
and may have an increased risk of 
getting cancer. 
38. Diquat 
 0.02 
 0.02 
 Some people who drink water 
containing diquat in excess of the 
MCL over many years could get 
cataracts. 
39. Endothall 
 0.1 
 0.1 
 Some people who drink water 
containing endothall in excess of 
the MCL over many years could 
experience problems with their 
stomach or intestines. 
40. Endrin 
 0.002 
 0.002 
 Some people who drink water 
containing endrin in excess of the 
MCL over many years could 
experience liver problems. 
41. Ethylene dibromide 
 Zero 
 0.00005 
 Some people who drink water 
containing ethylene dibromide in 
excess of the MCL over many 
years could experience problems 
with their liver, stomach, 
reproductive system, or kidneys, 
and may have an increased risk of 
getting cancer. 
42. Glyphosate 
 0.7 
 0.7 
 Some people who drink water 
containing glyphosate in excess of 
the MCL over many years could 
experience problems with their 
kidneys or reproductive difficulties.
43. Heptachlor 
 Zero 
 0.0004 
 Some people who drink water 
containing heptachlor in excess of 
the MCL over many years could 
experience liver damage and may 
have an increased risk of getting 
cancer. 
44. Heptachlor epoxide 
 Zero 
 0.0002 
 Some people who drink water 
containing heptachlor epoxide in 
excess of the MCL over many 
years could experience liver 
damage, and may have an increased 
 risk of getting cancer. 
 
 114
45. Hexachlorobenzene 
 Zero 
 0.001 
 Some people who drink water 
containing hexachlorobenzene in 
excess of the MCL over many 
years could experience problems 
with their liver or kidneys, or 
adverse reproductive effects, and 
may have an increased risk of 
getting cancer. 
46. Hexachlorocyclopenta-
diene 
0.05 
 0.05 
 Some people who drink water 
containing 
hexachlorocyclopentadiene well in 
excess of the MCL over many 
years could experience problems 
with their kidneys or stomach. 
47. Lindane 
 0.0002 
 0.0002 
 Some people who drink water 
containing lindane in excess of the 
MCL over many years could 
experience problems with their 
kidneys or liver. 
48. Methoxychlor 
 0.04 
 0.04 
 Some people who drink water 
containing methoxychlor in excess 
of the MCL over many years could 
experience reproductive 
difficulties. 
49. Oxamyl (Vydate) 
 0.2 
 0.2 
 Some people who drink water 
containing oxamyl in excess of the 
MCL over many years could 
experience slight nervous system 
effects. 
50. Pentachlorophenol 
 Zero 
 0.001 
 Some people who drink water 
containing pentachlorophenol in 
excess of the MCL over many 
 years could experience problems 
with their liver or kidneys, and may 
have an increased risk of getting 
cancer. 
51. Picloram 
 0.5 
 0.5 
 Some people who drink water 
containing picloram in excess of 
the MCL over many years could 
experience problems with their 
liver. 
 
 115
52. Polychlorinated 
biphenyls (PCBs) 
Zero 
 0.0005 
 Some people who drink water 
containing PCBs in excess of the 
MCL over many years could 
experience changes in their skin, 
problems with their thymus gland, 
immune deficiencies, or 
reproductive or nervous system 
difficulties, and may have an 
increased risk of getting cancer. 
53. Simazine 
 0.004 
 0.004 
 Some people who drink water 
containing simazine in excess of 
the MCL over many years could 
experience problems with their 
blood. 
54. Toxaphene 
 Zero 
 0.003 
 Some people who drink water 
containing toxaphene in excess of 
the MCL over many years could 
have problems with their kidneys, 
liver, or thyroid, and may have an 
increased risk of getting cancer. 
F. Volatile Organic Chemicals (VOCs) 
55. Benzene 
 Zero 
 0.005 
 Some people who drink water 
containing benzene in excess of the 
MCL over many years could 
 experience anemia or a decrease in 
blood platelets, and may have an 
increased risk of getting cancer. 
56. Carbon tetrachloride 
 Zero 
 0.005 
 Some people who drink water 
containing carbon tetrachloride in 
excess of the MCL over many 
years could experience problems 
with their liver and may have an 
increased risk of getting cancer. 
57. Chlorobenzene 
(monochlorobenzene) 
0.1 
 0.1 
 Some people who drink water 
containing chlorobenzene in excess 
of the MCL over many years could 
experience problems with their 
liver or kidneys. 
58. o-Dichlorobenzene 
 0.6 
 0.6 
 Some people who drink water 
containing o-dichlorobenzene well 
in excess of the MCL over many 
years could experience problems 
with their liver, kidneys, or 
circulatory systems. 
 
 116
59. p-Dichlorobenzene 
 0.075 
 0.075 
 Some people who drink water 
containing p-dichlorobenzene in 
excess of the MCL over many 
years could experience anemia, 
damage to their liver, kidneys, or 
spleen, or changes in their blood. 
60. 1,2-Dichloroethane 
 Zero 
 0.005 
 Some people who drink water 
containing 1,2-dichloroethane in 
excess of the MCL over many 
years may have an increased risk of 
getting cancer. 
61. 1,1-Dichloroethylene 
 0.007 
 0.007 
 Some people who drink water 
containing 1,1-dichloroethylene in 
excess of the MCL over many 
years could experience problems 
with their liver. 
62. cis-1,2-
Dichloroethylene 
0.07 
 0.07 
 Some people who drink water 
containing cis-1,2-dichloroethylene 
in excess of the MCL over many 
years could experience problems 
with their liver. 
63. trans-1,2-
Dichloroethylene 
0.1 
 0.1 
 Some people who drink water 
containing trans-1,2-
dichloroethylene well in excess of 
the MCL over many years could 
experience problems with their 
liver. 
64. Dichloromethane 
 Zero 
 0.005 
 Some people who drink water 
containing dichloromethane in 
excess of the MCL over many 
years could have liver problems 
and may have an increased risk of 
getting cancer. 
65. 1,2-Dichloropropane 
 Zero 
 0.005 
 Some people who drink water 
containing 1,2-dichloropropane in 
excess of the MCL over many 
years may have an increased risk of 
getting cancer. 
66. Ethylbenzene 
 0.7 
 0.7 
 Some people who drink water 
containing ethylbenzene well in 
excess of the MCL over many 
years could experience problems 
with their liver or kidneys. 
 
 117
67. Styrene 
 0.1 
 0.1 
 Some people who drink water 
containing styrene well in excess of 
the MCL over many years could 
have problems with their liver, 
kidneys, or circulatory system. 
68. Tetrachloroethylene 
 Zero 
 0.005 
 Some people who drink water 
containing tetrachloroethylene in 
excess of the MCL over many 
years could have problems with 
their liver, and may have an 
increased risk of getting cancer. 
69. Toluene 
 1 
 1 
 Some people who drink water 
containing toluene well in excess of 
the MCL over many years could 
have problems with their nervous 
system, kidneys, or liver. 
70. 1,2,4-Trichlorobenzene 
 0.07 
 0.07 
 Some people who drink water 
containing 1,2,4-trichlorobenzene 
well in excess of the MCL over 
many years could experience 
changes in their adrenal glands. 
71. 1,1,1-Trichloroethane 
 0.2 
 0.2 
 Some people who drink water 
containing 1,1,1-trichloroethane in 
excess of the MCL over many 
years could experience problems 
with their liver, nervous system, or 
circulatory system. 
72. 1,1,2-Trichloroethane 
 0.003 
 0.005 
 Some people who drink water 
containing 1,1,2-trichloroethane 
well in excess of the MCL over 
many years could have problems 
with their liver, kidneys, or 
 immune systems. 
73. Trichloroethylene 
 Zero 
 0.005 
 Some people who drink water 
containing trichloroethylene in 
excess of the MCL over many 
years could experience problems 
with their liver and may have an 
increased risk of getting cancer. 
74. Vinyl chloride 
 Zero 
 0.002 
 Some people who drink water 
containing vinyl chloride in excess 
of the MCL over many years may 
have an increased risk of getting 
cancer. 
 
 118
75. Xylenes (total) 
 10 
 10 
 Some people who drink water 
containing xylenes in excess of the 
MCL over many years could 
experience damage to their nervous 
system. 
G. Radioactive Contaminants 
76. Beta/photon emitters 
 Zero 
 4 mrem/yr
15
Certain minerals are radioactive 
and may emit forms of radiation 
known as photons and beta 
radiation. Some people who drink 
water containing beta and photon 
emitters in excess of the MCL over 
many years may have an increased 
risk of getting cancer. 
77. Alpha emitters 
 Zero 
 15 pCi/
ℓ
16
Certain minerals are radioactive 
and may emit a form of radiation 
known as alpha radiation. Some 
people who drink water containing 
alpha emitters in excess of the 
 MCL over many years may have an 
increased risk of getting cancer. 
78. Combined radium (226 
& 228) 
Zero 5 pCi/
ℓ
 
 Some people who drink water 
containing radium 226 or 228 in 
excess of the MCL over many 
years may have an increased risk of 
getting cancer. 
79. Uranium 
 Zero 
 30 
µ
g/
ℓ
 
 Some people who drink water 
containing uranium in excess of the 
MCL over many years may have an 
increased risk of getting cancer and 
kidney toxicity. 
H. Disinfection Byproducts (DBPs), Byproduct Precursors, and Disinfectant Residuals:  Where 
disinfection is used in the treatment of drinking water, disinfectants combine with organic and 
inorganic matter present in water to form chemicals called disinfection byproducts (DBPs).  
USEPA sets standards for controlling the levels of disinfectants and DBPs in drinking water, 
including trihalomethanes (THMs) and haloacetic acids (HAA5)
18
80. Total trihalomethanes 
(TTHMs) 
N/A 0.080
20
Some people who drink water 
containing trihalomethanes in 
excess of the MCL over many 
years may experience problems 
with their liver, kidneys, or central 
nervous system, and may have an 
increased risk of getting cancer. 
 
 119
81. Haloacetic Acids 
 (HAA5) 
N/A 0.060
21
Some people who drink water 
containing haloacetic acids in 
excess of the MCL over many 
years may have an increased risk of 
getting cancer. 
82. Bromate 
 Zero 
 0.010 
 Some people who drink water 
containing bromate in excess of the 
MCL over many years may have an 
increased risk of getting cancer. 
83. Chlorite 
 0.08 
 1.0 
 Some infants and young children 
who drink water containing chlorite 
in excess of the MCL could 
experience nervous system effects. 
Similar effects may occur in fetuses 
of pregnant women who drink 
water containing chlorite in excess 
of the MCL. Some people may 
experience anemia. 
84. Chlorine 
 4 
(MRDLG)
22
4.0 
(MRDL)
23
Some people who use water 
containing chlorine well in excess 
of the MRDL could experience 
irritating effects to their eyes and 
nose. Some people who drink water 
containing chlorine well in excess 
of the MRDL could experience 
stomach discomfort. 
85. Chloramines 
 4 (MRDLG)
 4.0 (MRDL)
 Some people who use water 
containing chloramines well in 
excess of the MRDL could 
experience irritating effects to their 
eyes and nose. Some people who 
drink water containing chloramines 
 well in excess of the MRDL could 
experience stomach discomfort or 
anemia. 
85a. Chlorine dioxide, 
where any two consecutive 
daily samples taken at the 
entrance to the distribution 
system are above the 
MRDL 
0.8 
(MRDLG) 
0.8 (MRDL)
 Some infants and young children 
who drink water containing 
chlorine dioxide in excess of the 
MRDL could experience nervous 
system effects.  Similar effects may 
occur in fetuses of pregnant women 
who drink water containing 
chlorine dioxide in excess of the 
MRDL. Some people may 
experience anemia. 
 
 120
 
  
  
 Add for public notification only: 
The chlorine dioxide violations 
reported today are the result of 
exceedences at the treatment 
facility only, not within the 
distribution system that delivers 
water to consumers. Continued 
compliance with chlorine dioxide 
levels within the distribution 
system minimizes the potential risk 
of these violations to consumers. 
86a. Chlorine dioxide, 
where one or more 
distribution system samples 
are above the MRDL 
0.8 
(MRDLG) 
0.8 (MRDL)
 Some infants and young children 
who drink water containing 
chlorine dioxide in excess of the 
MRDL could experience nervous 
system effects. Similar effects may 
 occur in fetuses of pregnant women 
who drink water containing 
chlorine dioxide in excess of the 
MRDL. Some people may 
experience anemia. 
 
  
  
 Add for public notification only: 
The chlorine dioxide violations 
reported today include exceedences 
of the USEPA standard within the 
distribution system that delivers 
water to consumers. Violations of 
the chlorine dioxide standard 
within the distribution system may 
harm human health based on short-
term exposures. Certain groups, 
including fetuses, infants, and 
young children, may be especially 
susceptible to nervous system 
effects from excessive chlorine 
dioxide exposure. 
 
 121
87. Control of DBP 
precursors (TOC) 
None 
 TT 
 Total organic carbon (TOC) has no 
health effects.  However, total 
organic carbon provides a medium 
for the formation of disinfection 
byproducts. These byproducts 
include trihalomethanes (THMs) 
and haloacetic acids (HAAs). 
Drinking water containing these 
byproducts in excess of the MCL 
may lead to adverse health effects, 
liver or kidney problems, or 
nervous system effects, and may 
lead to an increased risk of getting 
cancer. 
I. Other Treatment Techniques: 
88. Acrylamide 
 Zero 
 TT 
 Some people who drink water 
containing high levels of 
acrylamide over a long period of 
time could have problems with 
their nervous system or blood, and 
may have an increased risk of 
getting cancer. 
89. Epichlorohydrin 
 Zero 
 TT 
 Some people who drink water 
containing high levels of 
epichlorohydrin over a long period 
of time could experience stomach 
problems, and may have an 
increased risk of getting cancer. 
 
Appendix H--Endnotes 
 
1. “MCLG” means maximum contaminant level goal. 
 
2. “MCL” means maximum contaminant level. 
 
3. For a water supplier analyzing at least 40 samples per month, no more than 5.0 percent of the 
monthly samples may be positive for total coliforms.  For a supplier analyzing fewer than 40 
samples per month, no more than one sample per month may be positive for total coliforms. 
 
4. There are various regulations that set turbidity standards for different types of systems, 
including Section 611.320, the 1989 Surface Water Treatment Rule (SWTR), the 1998 Interim 
Enhanced Surface Water Treatment Rule (IESWTR), and the 2002 Long Term 1 Enhanced 
Surface Water Treatment Rule (LT1ESWTR).  The MCL for the monthly turbidity average is 1 
NTU; the MCL for the 2-day average is 5 NTU for a supplier that is required to filter but has not 
yet installed filtration (Section 611.320). 
 
 
 122
5. “NTU” means nephelometric turbidity unit. 
 
6. There are various regulations that set turbidity standards for different types of systems, 
including Section 611.320, the 1989 Surface Water Treatment Rule (SWTR), the 1998 Interim 
Enhanced Surface Water Treatment Rule (IESWTR), and the 2002 Long Term 1 Enhanced 
Surface Water Treatment Rule LT1ESWTR.  A supplier subject to the Surface Water Treatment 
Rule SWTR (both filtered and unfiltered) may not exceed 5 NTU.  In addition, in filtered 
systems, 95 percent of samples each month must not exceed 0.5 NTU in systems using 
conventional or direct filtration and must not exceed 1 NTU in systems using slow sand or 
diatomaceous earth filtration or other filtration technologies approved by the Agency. 
 
7. “TT” means treatment technique. 
 
8. There are various regulations that set turbidity standards for different types of systems, 
including Section 611.320, the 1989 Surface Water Treatment Rule (SWTR), the 1998 Interim 
Enhanced Surface Water Treatment Rule (IESWTR), and the 2002 Long Term 1 Enhanced 
Surface Water Treatment Rule LT1ESWTR.  For a supplier subject to the IESWTR (systems 
serving at least 10,000 people, using surface water or groundwater under the direct influence of 
surface water), that use conventional filtration or direct filtration, the turbidity level of a 
system’s combined filter effluent may not exceed 0.3 NTU in at least 95 percent of monthly 
measurements, and the turbidity level of a system’s combined filter effluent must not exceed 1 
NTU at any time.  A supplier subject to the IESWTR using technologies other than conventional, 
 direct, slow sand, or diatomaceous earth filtration must meet turbidity limits set by the Agency.  
For a supplier subject to the LT1ESWTR (a supplier that serves fewer than 10,000 people, using 
surface water or groundwater under the direct influence of surface water) that uses conventional 
filtration or direct filtration, after January 1, 2005, the turbidity level of the supplier’s combined 
filter effluent may not exceed 0.3 NTU in at least 95 percent of monthly measurements, and the 
turbidity level of the supplier’s combined filter effluent must not exceed 1 NTU at any time.  A 
supplier subject to the LT1ESWTR using technologies other than conventional, direct, slow 
sand, or diatomaceous earth filtration must meet turbidity limits set by the Agency. 
 
9. The bacteria detected by heterotrophic plate count (HPC) are not necessarily harmful. HPC is 
simply an alternative method of determining disinfectant residual levels.  The number of such 
bacteria is an indicator of whether there is enough disinfectant in the distribution system. 
 
10. SWTR, IESWTR, and LT1ESWTR treatment technique violations that involve turbidity 
exceedences may use the health effects language for turbidity instead. 
 
11. These arsenic values are effective January 23, 2006.  Until then, the MCL is 0.05 mg/
ℓ
 and 
there is no MCLG. 
 
12. Millions of fibers per liter. 
 
13. Action Level = 0.015 mg/
ℓ
. 
 
14. Action Level = 1.3 mg/
ℓ
. 
 
 123
 
15. Millirems per year. 
 
16. Picocuries per liter. 
 
17. This endnote 17 corresponds with the endnote to the table in Appendix B to Subpart Q of 40 
CFR 141 (2003), which stated a past effective date.  This statement maintains structural 
consistency with the federal regulations. 
 
18. A surface water system supplier or a groundwater system supplier under the direct influence 
of surface water is regulated under Subpart B of this Part.  A Supbart B community water system 
supplier or a non-transient non-community system supplier that serves 10,000 or more persons 
must comply with DBP MCLs and disinfectant maximum residual disinfectant levels (MRDLs).  
All other community and non-transient non-community system suppliers must meet the MCLs 
and MRDLs beginning January 1, 2004.  Subpart B transient non-community system suppliers 
serving 10,000 or more persons and using chlorine dioxide as a disinfectant or oxidant must 
comply with the chlorine dioxide MRDL.  Subpart B transient non-community system suppliers 
serving fewer than 10,000 persons and systems using only groundwater not under the direct 
influence of surface water and using chlorine dioxide as a disinfectant or oxidant must comply 
with the chlorine dioxide MRDL beginning January 1, 2004. 
 
19. This endnote 19 corresponds with the endnote to the table in Appendix B to Subpart Q of 40 
CFR 141 (2003), which expired by its own terms on January 1, 2004.  This statement maintains 
structural consistency with the federal regulations. 
 
20. The MCL for total trihalomethanes is the sum of the concentrations of the individual 
trihalomethanes. 
 
21. The MCL for haloacetic acids is the sum of the concentrations of the individual haloacetic 
acids. 
 
22. “MRDLG” means maximum residual disinfectant level goal. 
 
23. “MRDL” means maximum residual disinfectant level. 
 
BOARD NOTE:  Derived from Appendix B to Subpart Q to 40 CFR 141 (2003). 
 
(Source:  Amended at 29 Ill. Reg. ________, effective ______________________) 
 
I, Dorothy M. Gunn, Clerk of the Illinois Pollution Control Board, certify that the Board 
adopted the above opinion and order on January 20, 2005, by a vote of 5-0. 
 
Dorothy M. Gunn, Clerk 
Illinois Pollution Control Board