ILLINOIS
    POLLUTION
    CONTROL
    BOARD
    October
    19,
    1978
    CENTRAL
    ILLINOIS
    PUBLIC
    SERVICE
    )
    COMPANY
    (HtJTSOMVILLE
    POWER
    )
    STATION)
    ,
    )
    )
    Petitioner,
    v.
    )
    PCB 78—108
    ENVIRONMENTAL
    PROTECTION
    AGENCY,
    )
    )
    Respondent.
    THOMAS L.
    COCI1R1~N,ATTORNEY AT
    LAW,
    APPEARED
    ON BEHALF OF THE
    PETITIONER.
    WILLIAM 3.
    BARZANO,
    JR., ASSISTANT ATTORNEY
    GENERAL,
    APPEARED
    ON
    BEHALF OF THE RESPONDENT.
    OPINION
    AND
    ORDER OF THE BOARD
    (by Dr. Satchell):
    This matter comes before the Board for a determination
    pursuant to Rule 203(1) (5)
    of Chapter
    3: Water Pollution
    Regulations as to whether the thermal discharges from Central
    Illinois Public Service Company’s
    (CIPS)
    Hutsonville Power
    Station have not caused and cannot be reasonably expected to
    cause significant ecological damage to the receiving waters..
    CIPS filed its original petition in this matter on April 18,
    1973.
    A hearing was held on July 11,
    1978.
    There was no
    public participation in this matter.
    The Environmental Pro-
    tection Agency
    (Agency) has not filed a reconmtendation nor
    did it present any testimony at the hearing.
    All data referred
    to in this opinion are from the Thermal Study prepared for
    CIPS’ Hutsoriville Power Station by R.
    W. Beck and Associates
    pursuant to Procedural Rule 602.
    The Hutsonville generating station
    is located on the Wabash
    River at mile 173.9 near the town of Hutsonville, Illinois
    (p.
    1—1).
    Hutsonville has four units:
    Units
    1 and
    2 are
    peaking units and have a generating capacity of 32 MW each,
    Units
    3 and
    4 are the base load and have a generating capacity
    of
    83MW
    each
    (p. 1-1).
    Total gross station capacity is
    230
    t~w
    (p.
    1-1).
    Wabash river water is used for once—through con-
    denser cooling
    (p.
    2-1).
    Maximum capacity is 401 cfs for all
    four units.
    Water is pumped from the river through condensers
    for each
    unit
    (p.
    2—1).
    Meat is rejected to the cooling water
    from the steam condensers at a rate of 1668 million BTU/hour

    —2—
    at maximum plant generation
    (p.
    2—1).
    The resultant temperature
    rise of the cooling water at maximum flow is 18.4 F.
    Normally
    all cooling water pumps
    (two per unit)
    are operated
    (p.
    2-1).
    During the winter only one pump is used, resulting in higher
    cooling water temperature rise
    (p.
    2—1).
    Across the condensers
    the range of induced temperature rise is
    12 F to 19 F
    (p.
    2-1).
    Both actual and theoretical plume studies were included in
    the Thermal Study as required by Procedural Rule 602(c).
    The
    predominant discharge behavior configuration for typical flows
    is
    a shore—line attached
    plume
    (p.
    3—9).
    For low flow cases,
    fully mixed river conditions with exponential temperature
    decay are utilized in conjunction with the initial plume con-
    ditions from the shore-attached analysis
    (p.
    3-9).
    DATA SUMMARIZED FROM THEORETICAL PLUME STUDIES
    FOR TYPICAL CONDITIONS IN THE WABASH RIVER AT
    THE HUTSONVILLE STATION
    (p.
    4—15)
    Cross—Section
    Surface
    as Percent
    Area
    of Total
    In Acres
    River Flow
    Within
    Within
    Ambient
    River
    Designated
    Designated
    River
    Flow
    Isotherms
    Isotherms
    ~TFM
    Season
    Temp(F)
    in cfs
    3F
    5F
    7F
    3F
    SF
    7F
    (F)
    Winter
    36.5
    11,000
    0.1 ~0.1 0.1
    11
    4
    0.7
    Spring
    53.6
    18,700
    ~.0.140.1
    0.l
    6
    0.4
    Sunixner
    77.0
    7,200
    0.3 ~0.1
    ‘0.1
    16
    9
    1.0
    Fall
    62.6
    4,000
    1.2
    0.2 .~0.1
    29
    19
    8
    1.8
    4~FM
    represents fully—mixed condition.
    Figures based on 100 percent generation
    (230 MW) and condenser
    cooling water flow of 401 cfs, except for winter when flow is
    50 percent.
    31-664

    —3—
    With worst-case conditions the isotherm occupies the entire
    river cross-section.
    DATA SUMMARIZED FROM THEORETICAL PLUME STUDIES FOR
    WORST-,CASE CONDITIONS IN THE WABASH RIVER AT THE
    HUTSONVILLE
    STATION
    (p.
    4-17)
    Downs treamn
    Distance in
    Miles
    for
    Heat
    Dissipation
    in
    Ambient
    River
    Designated
    River
    Flow
    XFM
    Percentage
    Season
    Temp(F)
    in cfs
    in Feet
    25
    50
    FM
    (F)
    Winter
    47.3
    1700
    1200
    17
    40
    4.3
    Spring
    69.8
    6100
    1200
    40
    96
    1.2
    Summer
    88
    2900
    1000
    17
    40
    2.5
    Fall
    78.8
    1250
    1000
    7
    16
    5.9
    represents the distance below the discharge where the water
    is essentially fully—mixed
    (less than
    2 F gradient).
    represents
    the
    increase
    in
    temperature
    at
    the
    fully-mixed
    condition.
    Figures are based on 100 percent generation
    (230 MW)
    and
    condenser cooling water flow of 401 cfs, except for winter
    when flow is
    50 percent.
    An assessment of ecological damage was made during the time
    period of April 1973—May 1974
    (p.
    4—1).
    This study included
    the following parameters and components:
    temperature, dissolved
    oxygen,
    chlorine, phytoplankton, zooplankton, benthos and fishes
    (p.
    4-1).
    The study made a number of conclusions.
    During the
    period of 1973—1974,
    a period of relatively normal river flow,
    significant ecological damage did not occur
    (p.
    4—13).
    The
    study
    further states that under typical conditions, with the predicted
    thermal discharges, significant ecological damage is unlikely
    (p.
    4-13).
    Both predicted worst—case conditions and extreme
    worst-case conditions will cause substantial ecological damage
    to the river, even without thermal discharge
    (p.
    4-13).
    Under
    full power generation and with the latter two conditions

    —4—
    significant
    ecological
    damage
    would
    occur
    below
    the
    discharge
    (p.
    4—13,
    4—14).
    PROBABLE
    BIOLOGICAL EFFECTS OF THERMAL DISCHARGE BY
    THE HUTSONVILLE STATION ON THE WABASH RIVER
    UNDER
    WORST-CASE AND EXTREME WORST-CASE
    CONDITIONS
    (p.
    4—18,
    4—19)
    Case and
    Season
    Worst-Case
    Winter
    Physical Conditions
    Ambient
    temp.
    is 47.3 F
    and ~TFM
    is 4.3 F.
    River Flow is 1700 cfs.
    Probable BiolOgical Effects
    A T is sufficient to increase
    biological productivity even
    further.
    Increase in temp-
    erature below plant plus low
    river stage will tend to
    increase fish density for
    many miles below the plant.
    Significant ecological damage
    is unlikely.
    Worst
    Case
    Spring
    Ambient temp.
    is
    69.8 F, and ~T~1.1
    is 1.2 F.
    River Flow
    is 6100 cfs.
    AT not sufficient to cause
    significant chanjes over ~o—
    discharge condition.
    Ambient temp.
    is
    88
    and .~TFMis 2.5 F.
    River Flow is 2900
    cfs.
    Additional
    oxygen
    depletion
    below
    discharge
    is likely.
    Localized areas between dis-
    charge and XFM (1000
    ft)
    will
    experience heat stress.
    Blue—
    green algae will increase.
    Benthic organisms experience
    lethal conditions.
    Fish avoid
    this
    area.
    Below
    Xp~~the4T
    will
    influence
    the
    river
    for
    miles.
    Thermophilic bacteria
    and algae increase even further.
    Benthic community experiences
    increased stress and lethality.
    Fishkill episodes increase.
    Interference with fish
    movements
    including entry to mainstream
    from tributaries,
    is
    likely.
    Significant ecological
    damage
    is likely.
    Worst—Case
    S
    urnmer
    F
    31—666

    —5—
    PROBABLE
    BIOLOGICAL EFFECTS
    TABLE
    (Continued)
    Caso
    and
    Season
    Worst-Case
    Fall
    Physical
    Conditions
    Ambient
    tempt
    is
    78.8
    F,
    and
    4&TFM
    is 5.9 F.
    River
    Flow
    is
    1250
    cfs.
    Probable Biological Effects
    Effects depend on timing.
    Thermal discharge in early
    fall will probably stress
    biota;
    higher temperature
    in late fall will increase
    biological
    productivity
    even
    further.
    Growth of juvenile
    fish
    will
    be influenced by4T.
    Strain on carrying capacity
    of river may be exacerbated.
    Fishkills possible in early
    fall.
    Blockage of fish
    movements not likely.
    Extreme
    Worst—Case
    Condition
    Ambient
    temp.
    is
    90
    F,
    and~FM
    is
    5.9
    F.
    River
    Flow
    is 1250 cfs.
    Further oxygen
    depletion
    below
    discharge
    is
    likely.
    Severe thermal stress and
    lethal effects on all trophic
    levels
    for
    considerable
    dis-
    tance
    below
    discharge.
    Ex-
    tensive growths of thermo-
    philic bacteria and algae.
    Blue—green algae become
    dominant.
    Fishkills become
    common occurrence.
    Inter-
    ference with fish movements
    occurs
    for
    many
    miles.
    Significant
    ecological
    damage
    is highly probable.
    These are highly infrequent occurrences
    (p.
    4-14).
    The history
    of plant generation indicates that full power generation on a
    daily average basis occurs infrequently
    (p.
    4-14).
    Consequently,
    the
    combined
    events
    of
    river
    flow,
    ambient
    temperature
    and
    thermal
    discharges
    which
    could
    cause
    significant
    ecological
    damage
    are
    highly
    improbable
    (p.
    4-14)
    31—667

    —6-
    SELECTED
    DATA
    ON
    THE
    PROBABLE
    JOINT
    OCCURRENCE
    OF
    VARIOUS
    COMBINATIONS
    OF
    FLOW
    AND TEMPERATURE
    AT
    THE
    RIVERTON
    STATION
    ON
    THE
    WABASH
    RIVER
    (p.
    4-2 0)
    Total
    Number
    of
    Flow
    (cfs)
    Temp.
    F
    (C)
    Days/lO
    Years
    Comments
    Equal to or
    88
    (31)
    5•3
    £.~TFMis 2.5 or
    less
    than
    3000
    90
    (32)
    1.8
    more.
    2900
    88
    (31)
    About 5.3
    This is the worst—
    case summer con-
    dition; ~TF~.1is
    2.5
    F.
    Equal to or
    88
    (31)
    0.9
    ~TFM
    is 3.7 or
    less
    than
    2000
    90
    (32)
    0.1
    more.
    Equal to or
    88
    (31)
    0.3
    ~TFM
    is
    4.9
    or
    less than 1500
    90
    (32)
    0.1
    more.
    1250
    90
    (32)
    ~0.l
    This is the ex-
    treme worst-case;
    ~TFM
    is 5.9 F.
    The
    Board
    notes
    that
    the
    above
    table
    indicates
    that
    CIPS
    has
    the
    potential
    to
    cause
    a
    violationof
    Rule
    203(i)
    (4)
    of
    Chapter
    3.
    Thus
    it
    would
    be
    required
    to
    derate
    its
    Hutsoriville
    Power
    Station
    whenever the thermal discharge would raise the Wabash River
    temperature above the permitted maximum temperatures.
    The Agency made no effort to contest these conclusions and
    no recommendation was made.
    The Board is satisfied that the
    possibility
    of
    ecological
    damage
    due
    to
    the
    thermal
    discharge
    is
    sufficiently
    remote
    so
    as
    not
    to
    be
    “reasonably
    expected”.
    The Board finds that the thermal ~discharges from CIPS Hutsonville
    Power Station have not caused and cannot reasonably be expected
    to cause significant ecological damage to receiving waters.
    Petitioner has, therefore, satisfied the requirements of
    Rule 203(i) (5)
    of Chapter
    3.
    This Opinion constitutes the Board’s findings of fact and
    conclusions
    of
    law
    in
    this
    matter.
    31—668

    —7—
    ORDER
    it
    is
    the
    Order
    of
    the
    Pollution
    Control
    Board
    that
    the
    Petitioner has complied with Rule
    203(i)
    (5)
    of
    Chapter
    3:
    Water Pollution Regulations by demonstrating that its thermal
    discharges
    from
    its
    Hutsonville
    Power
    Station
    have
    not
    caused
    and
    cannot
    be
    reasonably
    expected
    to
    cause
    significant
    ecological damage to receiving waters.
    I, Christan L.
    Moffett, Clerk of the Illinois Pollution
    Control
    Board,
    hereby
    ce~tify
    the
    above
    Opnion
    and
    Order
    were adopted or~the ___________day of
    _____________,
    1978
    by a vote of
    Sj_~
    Illinois Polluti
    :ontro.
    Board
    31—669

    Back to top