RECEIVED
    CLFR~<’~OFFICE
    POLL~~R~
    JUN
    0 7
    2001
    BEFORE THE ILLINOIS
    L BOARD
    STATE
    OF
    ILLINOIS
    IN
    THE MATTER OF:
    )
    Pollution
    Control Board
    )
    AMENDMENTS TO
    LIVESTOCK
    )
    ROI-28
    WASTE REGULATIONS
    )
    (35
    IL Adm. Code 506)
    )
    COMMENTS OF TERRY FELDMANN.
    P.E
    I
    am a licensed professional engineer (Agricultural Engineer) in the state of Illinois.
    I
    own Feldmann
    & Associates, an Agricultural Engineering and Environmental
    Consulting firm in
    East Peoria,
    IL.
    I am a graduate of the University of Illinois College
    of Engineering with a degree in Agricultural Engineering.
    I
    have been a full time
    consultant to Livestock and Poultry producers full time since 1992.
    I was raised
    on a
    small farm in Madison county Illinois where we raised
    hogs and beef cattle.
    This
    upbringing enables
    me to understand the practical
    side (the real world) of livestock
    production and associated tasks such as construction, maintenance, etc.
    I testified at the 1997 part 506 rule making
    hearing
    in Champaign and actively worked
    with livestock producers in the design of their facilities to follow that rule.
    I consult with
    more livestock facilities about their designs than any other consulting engineer in
    Illinois.
    I am an active member of the American SocietyofAgricultural Engineers and
    serve on both the Swine and Dairy Housing committees.
    Overall the new rules submitted by the Department are a major step toward
    protecting
    the environment and the livestock industry.
    I am sorry that
    I could not make it to one of
    the hearings for this rule making and
    I commend the participants and the board for their
    effort.
    I
    do not own a livestock business and will not be directly impacted by increased
    construction costs.
    However,
    I
    do rely on the livestock industry
    in Illinois for practically
    all of my income
    and therefore directly value its viability.
    I am concerned that certain
    proposed
    provisions are without merit and will only increase costs unnecessarily.
    As a
    result,
    livestock producers will decide to build in other states or countries rather than
    in
    Illinois.
    I
    have the following
    major concerns about the proposed
    rule:
    1.
    There is
    no provision for determining the seasonal high water table in the site
    investigation nor methods.
    Perhaps “seasonalhigh water table”should
    be defined
    as the expected equilibrium elevation of water in an open pit or bore hole This
    requires professional judgement which should be left up to the person responsible
    for certifying the site investigation.
    Since
    it is practically impossible to do a soils

    investigation at the time of the seasonal high water table,
    I suggest reference to the
    USDA definition found
    in the Soil Survey.
    Seasonal
    High Water Table
    is the
    highest level of a saturated zone
    in the soil
    in most years.
    The survey estimates are
    based on the evidence of a saturated
    zone, namely grayish
    color and mottles
    in the
    soil.
    2.
    Section 506.210 requires the use of secondary containment.
    The Act says that a
    lagoon
    shall include a secondary berm, filter strip, grass waterway, or terrace, or
    combination of those if an engineer retained by the registrant with the concurrence
    of the Department, determines that such feature(s) is necessary to ensure against a
    release to non-owned
    land or waters of this state.
    I contend that not all sites and
    lagoon designs
    should be required to have one of these features. The Act certainly
    does not require the use of certain
    combinations of features as specified. The rule
    should allow for use of an engineer’s judgement. If an engineer determines that
    particular site and lagoon does not need one of these features, such feature(s)
    should
    not be required.
    3.
    Section 506.303 proposes an additional 6” rainfall covering the storage structure
    and other drainage areas
    beyond the 2’freeboard.
    I
    contend that the rainfall event
    on the storage structure itself is already accounted for within the 2’freeboard.
    However, a volume for the 25 year-24 hour storm event (which may be more or less
    than 6”) should
    be added for drainage areas other than that of the structures
    surface.
    This is consistent with the guidance documents such as MWPS-18 and
    ASAE
    EP 393.3.
    I propose that the board adopt the ASAE EP393.3 standard as it
    includes all volumes including bedding, wash down volumes, etc. with the 2’
    freeboard provision as explained
    above.
    4.
    Section 506.307
    (b)
    requires that deep bedded systems with an earthen base
    achieve a conductivity equal
    or less than I x 10-7
    centimeters/sec.
    Since these
    housing systems
    use bedding to absorb liquids and are generally roofed and
    protected from precipitation, this permeability requirement is not necessary.
    Solid
    handlinglstorage system not exposed to precipitation should
    be exempt from these
    requirements unless a site investigation indicates
    a vulnerable site due to a karst
    area or shallow ground water or aquifer material.
    5.
    Section 506.310 outlines additional requirements if aquifer material
    is located within
    5’of the proposed
    bottom. The proposed rule requires the installation of perimeter
    drainage tubing.
    Perimeter drainage tubing
    is to be used as outlined
    in MWPS-36
    where the water table
    could rise above the floor (MWPS-36, Fig.
    27).
    In my
    experience with soils investigations half of the sites with aquifer material do not
    have a seasonal
    high water table within close proximity to the floor.
    Many of these
    sites are sand hills or other well, drained soils with relatively deep
    (10’to 20’)water
    tables.
    If the seasonal high water table is not expected to be higher than the tank
    floor elevation, drainage tubing
    is useless.
    However,
    the location or elevation of the
    water table, if it is present within 5’of the planned bottom, should
    be determined

    and design provisions for adequate protection should
    be provided by an engineer
    with concurrence of the Department.
    6.
    Inspection/monitoring of perimeter drain tubing
    is a good
    idea, but quarterly
    sampling
    is
    not. Most water tables are seasonally high causing flow from the
    drainage tubing for brief periods in the spring.
    Furthermore,
    it gives no opportunity
    for determining the quality of up gradient water which may flow below a manure
    storage structure.
    Producers can however, monitor the flow from the tubing during
    the season that
    it flows.
    They can simply collect a sample
    in a jar and inspect it
    visually for turbidity and odor.
    7.
    The proposed rule calls for drainage tubing to be installed
    1’below the bottom of
    the footings.
    This is excessive and costly.
    In most cases installing the tube so that
    the bottom of the tube is at the same elevation as the bottom of the footing is
    sufficient.
    This always makes
    the top of the tube below the top of the manure
    storage floor to prevent the water table from being higher than the floor as shown in
    MWPS-36. Tubes should however, either drain to a free outlet (daylight) or provide
    sufficient slope when connected to other subsurface conduits.
    8.
    Section
    13 (b) of the Livestock Management Facilities Act specifically requires
    designs to follow ASAE 393.3 or future updates.
    In the proposed rules section
    506.310(b) specifies minimum thicknesses of floors and walls.
    As listed in EP393.3
    section 6.1.1.3.1, if no wheel loads are expected, 4” floors are adequate.
    The 5”
    thickness is required for tanks with wheel loads.
    Requiring a minimum 8”thick walls
    should
    not be specified as EP393.3 specifies the loading
    and that the design
    be
    based
    on ACI-318 (Building Code Requirements for Structural Concrete).
    These
    minimums may actually hinder the design
    process with engineers.
    For example, a
    producer
    reads this minimum and thinks that is what is needed.
    If a wall
    is taller or
    soil
    load is greater, the wall
    may need to be thicker.
    Now the engineer has a harder
    job to convince the producer that a thicker wall
    is needed because he believes that
    8” is adequate.
    On the other hand,
    a shorter waIl (<4’)that is only a few feet tall
    need not be 8”thick and provides negligible additional protection.
    Designs should take into account site specific data including the soil type, depth to
    ground water,
    etc.
    Design professionals should use their judgement with
    concurrence of the Department to determine what is necessary to prevent seepage
    of stored liquid. For example,
    in the case of a concrete structure, a designer might
    choose a more limiting Z-check of <115 kips/in rather than <145 kips/in to control
    flexure crack widths.
    Site specific data (rather than assuming 3000 psf) for soil
    bearing strength should be required for footing design
    in areas of shallow aquifer
    material or karst areas.
    This is very important to prevent seepage.
    In fact, even more important than
    the design itself might be a good Quality
    Assurance/Quality Control (QNQC)
    plan.
    I suggest that these plans be developed
    as part of the overall design and submitted to the Department for their review for

    facilities located
    in a karst area.
    The degree of detail should
    be left to the design
    engineer with concurrence of the Department.
    Regular inspection and maintenance
    should also be considered.
    With regard to testimony of Dan Heacock of IEPA,
    I have the following concerns:
    1.
    The number of soil borings in
    a karst
    area should
    be determined
    by the engineer or
    geologist based
    on judgement and existing geologic information.
    A specific number
    of boring should
    not be specified. Although, if they deem
    it necessary to protect the
    environment, the Department may require additional borings, sampling, or tests.
    Minimum depth of at least one boring is important to specify as stated
    in the
    proposed
    rule.
    2.
    Requiring a storage facility for perimeter drain tiles is not feasible.
    Storage facilities
    constructed according to the proposed
    rules are meant to be liquid tight and
    therefore are not likely to contaminate perimeter drain tiles.
    However, if it
    is
    determined
    that a facility does have seepage to a tile, the liquid must be captured,
    properly treated and/or disposed as required by the Environmental Protection Act.
    An
    important provision of the proposed
    rule is section 506.106 which provides for
    design alternative, modifications, and waivers.
    This allows for engineering judgement
    to be used.
    More explanation of these comments and details can be found
    in a paper that Mark
    Armstrong,
    P.E. and
    I wrote for the proceeding of the 1999 Livestock Waste
    Management Conference held at the
    University of Illinois.
    Thank you for considering these comments.
    Sincerely,
    Terry Feldmann,
    P.E.
    Feldmann
    & Associates
    1191
    Carolyn Court
    East Peoria,
    IL 61611
    309-699-6962 ph

    Back to top