ILLINOIS POLLUTION CONTROL BOARD 
October 2, 1997 
DAVID and SUSI SHELTON, 
Complainants, 
v. 
STEVEN and NANCY CROWN, 
Respondents. 
) 
) 
) 
) 
) 
) 
) 
) 
) 
PCB 96-53 
(Enforcement - Noise) 
JEFFERY R. DIVER AND STEVEN KAISER OF THE JEFF DIVER GROUP APPEARED 
ON BEHALF OF COMPLAINANTS; 
RICHARD R. ELLEDGE AND ROBERT A. CARSON OF GOULD AND RATNER 
APPEARED ON BEHALF OF RESPONDENTS. 
OPINION AND ORDER OF THE BOARD (by G.T. Girard): 
On September 8, 1995, David and Susi Shelton (Sheltons or complainants) filed this 
citizen’s enforcement action (Comp.) concerning an air conditioner owned by Steven and Nancy 
Crown (Crowns or respondents) at the Crowns’ home located at 685 Ardsley Road, Winnetka, 
Cook County, Illinois. This action was filed pursuant to Section 31(b) of the Illinois 
Environmental Protection Act (Act) (415 ILCS 5/31(b) (1994). The Sheltons allege that noise 
from the air conditioner at the Crowns’ home has unreasonably interfered with the enjoyment of 
their lives and property, and, in addition, the air conditioner is in violation of Illinois numeric 
noise standards. The Sheltons claim that the Crowns have therefore violated Section 23 and 24 
of the Act (415 ILCS 5/23, 5/24 (1994)) and Board regulations at 35 Ill. Adm. Code 900.102, 
900.102(a), 900.102(b), and 901.104. The Sheltons request that the Board find that the Crowns 
violated the Act and Board regulations, and order a civil penalty pursuant to Section 42 of the 
Act (415 ILCS 5/42 (1994)). 
Hearings were held in this matter before Board Hearing Officer June Edvenson on July 1, 
July 2, July 12, July 16, July 20, July 21, August 19, and August 20, 1996. Complainants filed 
their post-hearing brief (Comp. Br.) on February 21, 1997. Respondents filed their post-hearing 
brief (Resp. Br.) and a motion to dismiss with prejudice (Mot. Dis.) on May 5, 1997. On May 
19, 1997, complainants filed their reply brief (Reply Br.) and Response to Motion to Dismiss 
(Res. Mot. Dis.). On June 2, 1997, respondents filed a “Motion to Strike” and an exhibit titled 
“Exhibit 1” to the reply brief. The Board denies the motion to strike. The Board also denies the 
motion to dismiss for the reasons discussed in a following section. 
For the reasons discussed below, the Board finds that there is sufficient proof that noise 
from the Crowns’ air conditioner unreasonably interfered with the Sheltons’ enjoyment of their 
lives and property during those times when the air conditioner was operating between September
2
15, 1993, and January 1996. The Board does not find that the air conditioner noise violated the 
Board’s numeric noise standards. The Board finds that no monetary penalty is warranted in this 
case. 
LEGAL FRAMEWORK 
The Sheltons allege that the Crowns have violated Sections 23 and 24 of the Act and the 
Board’s rules at 35 Ill. Adm. Code 900.102, 901.102(a), 901.102(b), and 901.104. Comp. at 2. 
These statutes and regulations prohibit noise pollution in Illinois which exceeds specified 
numeric limits or which produces nuisance noise. The Sheltons allege that noise from the 
Crowns’ air conditioner has violated numeric noise standards and created nuisance noise which 
has unreasonably interfered with the Sheltons’ lives and enjoyment of their property. See 
Ferndale Heights Utilities Co. v. Illinois Pollution Control Board, 44 Ill. App. 3d 967, 358 
N.E.2d 1224, 1228 (1st Dist. 1976). 
Noise violations are defined by Section 23 and 24 of the Act. With regard to nuisance 
noise, the prohibitions in the Act and Board regulations turn on the degree to which the noise 
interferes with a complainant’s normal activities. Section 23 of the Act states: 
The General Assembly finds that excessive noise endangers physical and 
emotional health and well-being, interferes with legitimate business and 
recreational activities, increases construction costs, depresses property values, 
offends the senses, creates public nuisances, and in other respects reduces the 
quality of our environment. It is the purpose of this Title to prevent noise which 
creates a public nuisance. 415 ILCS 5/23 (1996). 
Section 24 of the Act prohibits noise pollution stating: 
No person shall emit beyond the boundaries of his property any noise that 
unreasonably interferes with the enjoyment of life or with any lawful business or 
activity, so as to violate any regulation or standard adopted by the Board under 
this Act. 415 ILCS 5/24 (1996). 
Thus, under the Act, a noise violation has occurred if the complainant has proven that the 
activity violates any numeric regulation or standard adopted by the Board or if a nuisance noise 
has unreasonably interfered with the complainant’s enjoyment of life or with the pursuit of any 
lawful business or activity. 
In this proceeding, the Sheltons allege that noise emitted by the Crowns’ air conditioner 
violated Board regulations found at 35 Ill. Adm. Code 900.102, 901.102(a), 901.102(b), and 
901.104. The specific language of those Sections provides: 
Section 900.102 Prohibition of Noise Pollution 
No person shall cause or allow the emission of sound beyond the boundaries of 
his property, as property is defined in Section 25 of the Illinois Environmental
3
Protection Act, so as to cause noise pollution in Illinois, or so as to violate any 
provision of this Chapter. 
Section 901.102 Sound Emitted to Class A Land 
a)    
Except as elsewhere in this Part provided, no person shall cause or allow 
the emission of sound during daytime hours from any property-line-noise-
source located on any Class A, B or C land to any receiving Class A land 
which exceeds any allowable octave band sound pressure level specified 
in the following table, when measured at any point within such receiving 
Class A land, provided, however, that no measurement of sound pressure 
levels shall be made less than 25 feet from such property-line-noise-
source. 
Octave Allowable Octave Band Sound Pressure 
Band Levels (dB) of Sound Emitted to any 
Center Receiving Class A Land from 
Frequency         
Class C     
Class B     
Class A 
(Hertz) Land       
Land       
Land 
31.5    
75          
72          
72 
63     
74          
71          
71 
125    
69          
65          
65 
250    
64          
57          
57 
500    
58          
51          
51 
1000   
52          
45          
45 
2000   
47          
39          
39 
4000   
43          
34          
34 
8000   
40          
32          
32 
b)    
Except as elsewhere in this Part provided, no person shall cause or allow 
the emission of sound during nighttime hours from any property-line-
noise-source located on any Class A, B or C land to any receiving Class A 
land which exceeds any allowable octave band sound pressure level 
specified in the following table, when measured at any point within such 
receiving Class A land, provided, however, that no measurement of sound 
pressure levels shall be made less than 25 feet from such property-line-
noise-source.
4
Octave Allowable Octave Band Sound Pressure 
Band Levels (dB) of Sound Emitted to any 
Center Receiving Class A Land from 
Frequency         
Class C     
Class B     
Class A 
(Hertz) Land       
Land       
Land 
31.5    
69          
63          
63 
63     
67          
61          
61 
125    
62          
55          
55 
250    
54          
47          
47 
500    
47          
40          
40 
1000   
41          
35          
35 
2000   
36          
30          
30 
4000   
32          
25          
25 
8000   
32          
25          
25 
Section 901.104 Impulsive Sound 
Except as elsewhere in this Part provided, no person shall cause or allow the 
emission of impulsive sound from any property-line-noise-source located on any 
Class A, B or C land to any receiving Class A or B land which exceeds the 
allowable A-weighted sound levels specified in the following table, when 
measured at any point within such receiving Class A or B land, provided, 
however, that no measurement of sound levels shall be made less than 25 feet 
from such property-line-noise-source. 
Classification of             
Allowable A-weighted Sound Levels in 
Land on which               
Decibels of Impulsive Sound Emitted 
Property-Line-               
to Receiving Class A or B Land 
Noise-Source 
is Located 
Class A Land 
Class B Land    
Daytime       
Nighttime 
Class A Land       
50            
50            
45 
Class B Land       
57            
50            
45 
Class C Land       
61            
56            
46 
The Board has previously determined in nuisance noise proceedings that unreasonable 
interference is more than an ability to distinguish sounds attributable to a particular source. 
Rather, the sounds must objectively affect the complainant’s life or business activities. See 
Kvatsak v. St. Michael’s Lutheran Church, (Aug. 30, 1990) PCB 89-182, 114 PCB 765, 773 
(Kvatsak); 
Kochanski v. Hinsdale Golf Club, (July 13, 1989) PCB 88-16, 1001 PCB 11, 20-21, 
rev’d on other grounds
, 197 Ill. App. 3d 634, 555 N.E.2d 31 (2d Dist. 1990).
5
In determining whether unreasonable interference has occurred under the Act and Board 
rules, the Illinois Supreme Court has directed that the Board must consider the facts of the case 
in light of the factors outlined in Section 33(c) of the Act. Wells Manufacturing Co. v. Pollution 
Control Board, 73 Ill. 2d 226, 232-33, 383 N.E.2d 148, 150-51 (1978), see also Ferndale Heights 
Utilities, 44 Ill. App. 3d at 967-68, 358 N.E.2d at 1228. Those factors as set forth in Section 
33(c) of the Act are as follows: 
(i)      
the character and degree of injury to, or interference with the protection 
of the health, general welfare and physical property of the people; 
(ii)     
the social and economic value of the pollution source; 
(iii)     
the suitability or unsuitability of the pollution source to the area in 
which it is located, including the question of priority of location in the 
area involved; 
(iv)     
the technical practicability and economic reasonableness of reducing or 
eliminating the emissions...resulting from such pollution source; and 
(v)     
any subsequent compliance. 415 ILCS 5/33(c) (1996). 
FACTS 
General Information 
The Sheltons and their three children moved into their home at 707 Ardsley Road, 
Winnetka, Illinois, in 1990. Tr. at 357, 395. In June 1991, the Crowns purchased the property at 
685 Ardsley Road, which lies immediately south of the Sheltons’ home. Tr. at 12, 1267. The 
Crowns’ nearest property line is approximately 28 feet from the nearest wall of the Sheltons’ 
home. Tr. at 364. The neighborhood is quiet, with private streets and individual properties 
larger than one-half acre each. Tr. at 356-357. 
Prior to taking up residence, the Crowns extensively remodeled their home, which 
included removing the existing heating and air conditioning system in the structure. Tr. at 17. 
After remodeling, the finished structure enclosed approximately 18,000 square feet. Stip. No. 1. 
Remodeling began in fall of 1991. Tr. at 14, 366. The Crowns moved into their home in March 
1995. Tr. at 80. 
The Crowns’ new HVAC [heating, ventilation, air conditioning] system was designed 
and installed by Mid/Res, Inc. (Mid/Res), according to specifications established by the 
architect, Mr. Paul Constant. Tr. at 19. On February 12, 1992, Mid/Res provided Mr. Constant 
with an initial proposal for the Crowns’ HVAC system (Exh. 66; Exh. 69; Tr. at 322-323), and 
Mid/Res began installation in spring 1992. Tr. at 194. The HVAC system included a 25-ton 
exterior unit (chiller unit) manufactured by the Trane Corporation (Trane), Model RAUC 25. 
Ex. 73. Trane Model RAUC 25 is used primarily in commercial applications. Tr. at 181. This 
chiller unit consists of two compressors (one ten-ton and one fifteen ton), and three fans. Tr. at
6
17. A Trane Engineering Bulletin published in February 1993 warned that installing commercial 
size equipment near a residential lot line would be a misapplication that increased the likelihood 
of a noise problem. Exh. 43 at III. The Bulletin also warned against locating outdoor HVAC 
equipment in proximity to a sound reflective wall. Exh. 43 at III. The Crowns’ chiller unit was 
located in front of a two-story stone wall of the Crown residence and was about 60 feet from the 
nearest wall of the Shelton residence. Exh. 2, 51; Tr. at 794. The completed HVAC system for 
the Crown home cost approximately $300,000. Stip. No. 1. 
The chiller unit was first tested in September 1993. Tr. at 21, 366-368. When the unit 
was first turned on, the Sheltons called the local police because they thought the noise resembled 
an explosion. Tr. at 367. The Sheltons then called the Crowns who agreed to turn off the unit. 
Tr. at 368. During the next three years the Sheltons and the Crowns had numerous meetings and 
exchanged correspondence over the Sheltons’ objection to the noise level of the chiller unit. Tr. 
at 372, 373, 419, 421, 435, 438, 525-527, 792, 811, 815, 816, 822, 823, 826, 841, 842, 848, 853; 
Exh. 6, 17, 18(a)(b), 19, 21, 22, 40, 41, 43, 45 49, 90, 107. 
The Crowns determined that moving the chiller was not a feasible because major HVAC 
components were already installed. Tr. at 1201, 1320. Mid/Res, Inc. attempted to attenuate the 
noise in fall 1993 and spring 1994 by several methods. Tr. at 222; Exh. 32. Sheets of one-half 
inch thick acoustic material, Armaflex, were applied to the interior of the chiller casing in 
October 1993. Tr. at 218, 621, 628. The chiller was rotated 90 degrees so that the air intake 
pointed east, away from the Sheltons’ house, rather than north toward the Sheltons’ house. Tr. at 
1301; Resp. Br. at 8. Finally, metal “cones” were fabricated for installation over the chiller fans 
(Tr. at 1301, 1303), which Mid/Res considered at the time to be the major noise source. Tr. at 
225. In June 1994, the Crowns initiated 24-hour operation of the chiller unit to protect the 
millwork from humidity and dry out the plaster. Tr. at 79-80. The 24-hour a day operation 
continued through the summer of 1994. Tr. at 80. In June 1994, the Crowns also installed 
wooden fences and shrubbery between the Crown and Shelton properties to reduce the sound. 
Tr. at 398, 1395, 1401. Ms. Marjorie Julian, the Sheltons’ neighbor to the north testified that the 
chiller unit noise was not reduced by the fences and shrubbery. Tr. at 156-157. 
On January 5, 1995, Mr. Shelton wrote a letter to the Village of Winnetka (Winnetka) 
including a petition signed by neighbors who had visited the Sheltons’ home, asking Winnetka, 
pursuant to Winnetka noise ordinance, to order the Crowns to significantly reduce the noise from 
their chiller unit. Exh. 7. Mr. Williams, Winnetka Village Manager, convened a meeting of the 
parties on January 17, 1995. Tr. at 1352. At that meeting, plans to construct an acoustic 
enclosure were discussed. Exh. 35. The acoustic structure constructed by the spring of 1995 
was eight feet high, two feet higher than the chiller, and constructed of acoustic panels. Tr. at 
1131. 
The Crowns again activated the chiller unit in April 1995. Tr. 442, 498. The Sheltons’ 
noise complaints continued through the spring and summer of 1995. Tr. at 443-447. Mr. Allen 
Shiner of Shiner and Associates, acoustical engineers, measured noise from the chiller unit on 
June 19, 1995. Exh. 60. He determined that the discharge cones did not mitigate the sound and 
they were removed. Tr. at 217-221; Exh. 60. After removal of the cones prior to the 1995 
cooling season (Tr. at 501), the Sheltons noticed “a very slight improvement in the sound.” Tr.
7
At 502. However, correspondence about the noise from the chiller unit was exchanged between 
the Sheltons and the Crowns during summer 1995, culminating in the Sheltons’ complaint filed 
before the Board in September 1995. The Sheltons relocated their family to Greenville, Ohio, in 
January 1996. Comp. Br. at 23. The Sheltons apparently sold their home in April or May 1997 
(May 5, 1997, affidavit of Arie Steven Crown). 
In July and August 1996, Mid/Res installed fan motor variable speed controls. Mid/Res 
modified the height and configuration of the chiller unit acoustic shield to include a roof over the 
chiller unit. Tr. at 1534-1535. On August 15, 1996, Shiner and Associates measured sound 
levels at the Shelton property line and residence and found that the modifications resulted in 
significantly reduced noise levels from the chiller unit. Exh. 125, 126, 127. The specific results 
of these final sound measurements are more fully described in the subsection below entitled 
“Sound measurements by George Kemperman.” Greg Zak, a noise expert with the Illinois 
Environmental Protection Agency (IEPA), testified that the final sound mitigation measures 
represented an “elegant solution” to the problem based on his visit to the Crown and Shelton 
properties on August 21, 1996. Tr. at 1477. Greg Zak further testified that based on his personal 
observation and review of the date available, the chiller unit operates in compliance with both 
the nighttime numeric noise standards at Section 901.102(b) and nuisance noise standards. Tr. at 
1477. 
Sound Monitoring Data 
Sound emanating from the Crown chiller unit was measured on seven different occasions 
between July 1994 and August 1996 by Allen Shiner (7-5-94 & 6-19-95), George Kemperman 
(5-2-96, 8-9-96 & 8-15-96), Greg Zak (6-27-96), and Robert Elfering (8-15-96). A brief 
summary of the sound monitoring data obtained on each of the seven monitoring events is 
presented below. 
Sound Measurements by Allen Shiner and Robert Elfering 
Shiner and Associates, acoustical engineers, were retained by both the complainants and 
the respondents to monitor sound levels in the vicinity of the Crown chiller unit. Shiner’s 
engineers measured sound levels on three occasions. On the first two occasions, Allen Shiner 
monitored sound levels emanating from the Crown chiller unit on behalf of the complainants. 
On July 5, 1994, Shiner measured the sound levels from the Shelton’s property within 20 feet of 
Shelton’s south property line. Shiner stated that the instrumentation was established in 
accordance with the Board regulations. Tr. at 293. Based on a comparison of the measured 
sound levels with the allowable octave band sound pressure levels specified under the numeric 
noise standards at 35 Ill. Adm. Code 901.102, Shiner concluded that the Crown chiller unit 
exceeded the allowable levels at all frequencies during the night hours of operation. Exh. 56. 
The sound levels from the Crown chiller unit were again measured by Shiner on June 19, 
1995, after installation of the acoustical housing. Exh. 60. The sound levels were measured 
under different operating conditions to assess the sound-reducing effectiveness of the discharge 
cones and the acoustical housing placed on the chiller unit. Again, Shiner testified that the 
measurements were made in accordance with applicable Board regulations. Tr. at. 302. Shiner
8
concluded that the sound levels exceeded the Board’s nighttime standards at all frequencies, 
except for the sound level at octave band center frequency of 250 Hz. Tr. at 318. 
On August 15, 1996, Robert Elfering, an engineer with Shiner and Associates, measured 
sound levels from the Crown chiller unit on behalf of the respondents. Exh. 124, 125. Elfering 
measured sound levels at five locations: near the fence (property line) between the Shelton and 
Crown residences; on the Shelton patio opposite the Shelton window air conditioner; near the 
fence, 50 feet north-east of the Crown chiller unit; on the roof of the enclosed porch; and on the 
edge of the Crown driveway, opposite the Crown chiller unit. The sound levels were measured 
at different operating conditions, which included: the Crown chiller unit operating in nighttime 
mode with the Shelton air conditioner switched on and off; the Crown chiller unit operating in 
day time mode at 60 Hz (fan at full speed) with Shelton air conditioner switched off; the Crown 
chiller unit operating in day time mode at 20 Hz (fan speed at 33% of full speed) with the 
Shelton air conditioner off; and with both Crown and Shelton air conditioners switched off to 
determine ambient noise conditions. 
Sound Measurements by Greg Zak 
Greg Zak, a noise technical expert with the IEPA, monitored sound levels on both 
Shelton and Crown properties on June 27, 1996 at around 9.30 p.m. The first location (site 1) 
was outside the second floor bedroom window of the Shelton residence. Exh. 92 at 3. The 
second location (site 2) was on the Crown property at a point approximately 30 feet north of the 
Crown chiller unit. See Attachment to Exh. 92. At the second location, Zak also measured the 
ambient sound, which are the background sound levels with the Crown chiller unit turned off. 
Tr. at 604. Zak stated that the measurements were made in accordance with the Board 
regulations. Tr. at 572. Zak described the acoustic properties of the area as a complex echoic 
field due to the parallel house walls and stockade fence. Tr. at 573-575. 
Sound Measurements by George Kemperman 
George Kemperman, a noise control engineer, was retained by respondent to evaluate the 
noise sources associated with the Crown chiller unit. Kemperman monitored the sound levels 
from the Crown chiller unit on three different occasions. On May 2, 1996, Kemperman recorded 
sound levels from the chiller unit as a part of his investigation of the noise source. Based on 
these measurements, he made recommendations for improving noise control that included two 
different modes of operation: normal operation, with two compressors and three fans operating 
at full speed; and nighttime operation with one compressor and one fan operating full speed. 
Kemperman believed that the recommended operational changes would result in compliance 
with the Board’s nighttime numeric noise emission standards. Tr. at 1507-1510. 
However, Kemperman revised his recommendations after evaluating the sound level 
measurements recorded by Zak on June 27, 1996. Tr. at 1510-1511. In this regard, he stated that 
his earlier projections were much lower than those observed by Zak. Tr. at 1511. Kemperman 
then made the following recommendations: fan speed should be reduced 50 percent during night 
time; the height of the enclosure should be increased above the fan discharge using plywood
9
with sound absorptive treatment; and the top opening of the enclosure should be closed so that 
air would be forced to go through the inlet silencer. Tr. at 1511-1512. 
Kemperman measured the sound levels from the Crown chiller unit twice after 
implementation of his recommendations. On August 9, 1996, he measured sound levels at the 
property line at elevations of 8 feet, 12 feet, and 16 feet above the ground. The measurements 
were taken at different elevations in order to account for the line of sight from the top of the 
chiller unit enclosure to the second floor bedroom window of the Shelton residence. Tr. at 1515. 
The measurements were taken at two fan speeds: one at maximum fan speed and one at slightly 
less than half of the maximum speed. Tr. at 1516. Based on his measurements, Kemperman 
concluded that reducing fan speed resulted in the decrease of sound levels by 15 to 20 dB. Exh. 
122. 
Kemperman again measured sound levels at three locations in the vicinity of the Crown 
chiller unit on August 15, 1996. The sound levels were measured four feet above the ground at 
approximately eight feet north of the property line between the Shelton and Crown residences, 
and on the patio on the east side of the Shelton residence. The third location was a second story 
bedroom window over the porch roof of the Shelton residence (14 feet above ground). The 
sound measurements on August 15, 1996, showed significant reduction in sound emission from 
the chiller unit. The sound levels measured in this final sound monitoring event were below the 
Board’s numeric noise emission standards of Section 901.102. Exh. 125. 
Effects of Noise Interference 
In June 1994, when the Crown chiller unit began operating 24 hours per day (Tr. at 375), 
the noise from the chiller unit could be heard in the Sheltons’ kitchen, living room, dining room, 
family room, master bedroom, and the bedroom of their eldest son, David B. Shelton. Tr. at 376-
377. The noise was loudest on the southern end of the Shelton home second floor, where son 
David B. Shelton’s bedroom was located. Tr. at 377. Susi Shelton testified that the noise was so 
loud that her son could not sleep in his room even with the windows closed and a fan operating 
in his room. Tr. at 377. David B. Shelton testified that the noise was very loud and annoying. 
Tr. at 523. He testified that he could feel vibrations caused by the chiller unit noise if he put his 
head on the window or wall of his bedroom. Tr. at 530-532. The loud noises were produced by 
the cycling of the system on and off, pulsating sound, and the high pitches of the fans. Tr. at 
377. Susi Shelton described the noises as worse at nighttime when they would be awakened by 
the noise. Tr. at 380. She testified that the noise prevented the family from sleeping, leading to 
exhaustion, headaches, stress, and tension in the family. Tr. at 381. 
David Shelton described the chiller unit noise in 1994 as “an extensive, deep, powerful 
drone that penetrated the house. And, it was interspersed with huge sound surges, booms, if you 
will, as different components of the system kicked in and out. At times, particularly in the 
evening, we could also hear higher pitched sound such as a waterfall and hear also beating 
sound, which I’m told were probably different phases of the system going in and out of phase 
with each other.” Tr. at 818. David Shelton said that the chiller unit noise caused family 
impacts such as loss of sleep, his son moving from his room, inability to use their backyard or 
patio, extreme tiredness, depression, anxiety, and short tempers. Tr. at 818-819. The Shelton’s
10
son stopped camping in either the front or backyard. Tr. at 528-529. Susi Shelton was unable to 
escape the noise of the chiller unit by going indoors, closing the windows, or turning on either 
music or television. Tr. 388-389. These impacts continued from June through September 1994. 
Tr. at 532, 820. David Shelton hired Mr. Shiner to take the first noise measurements of the 
Crown chiller unit on July 5, 1994. Exh. 56. 
Despite the installation of acoustical panels and discharge cones prior to the 1995 cooling 
season, the Sheltons reported that throughout April, May, and June 1995 the noise from the 
chiller unit created stress and tension in the Shelton family. Tr. at 445-446. Susi Shelton 
testified that she experienced headaches and pains down her neck and across her shoulders. Tr. 
at 445-447. The noise disrupted the Sheltons’ sleep and could be heard in the Sheltons’ kitchen, 
living room, dining room, family room, master bedroom, and throughout the entire second floor 
of their home. Tr. at 443-444. Closing windows and turning on music or television did not 
reduce the level of annoyance caused by the chiller unit. Tr. at 445-445. Son, David B. Shelton, 
testified that after the chiller unit was activated in April 1995, he slept in his bedroom only half 
the time. Tr. 533, 535. He testified that when sleeping in his bedroom, the chiller unit woke him 
when parts clicked on or off, and as a consequence in the morning he felt tired, cranky, lazy, and 
found it difficult to concentrate in school with little sleep. Tr. at 533-534. 
On June 19, 1995, Mr. Shriner again measured noise from the chiller unit in the evening. 
Exh. 60. Mr. Shriner reported that the acoustic housing and removing the discharge cones 
significantly reduced the noise. Exh. 60. After removal of the discharge cones, the Sheltons 
could still hear the low drones, high pitches, and on/off cycle emitted by the chiller unit in their 
home with the windows closed in late June, 1995. The noise was still much worse on the second 
floor. Tr. at 449. 
Throughout July, August, and September 1995, Susi Shelton was able to sleep in her first 
floor bedroom located on the northern end of her home only if the windows were closed, the 
overhead fan was operating, and she used a prescription sleeping additive. Tr. at 459-460. 
David Shelton had difficulty sleeping even when using ear plugs, with a fan operating and the 
windows closed. Tr. at 890. Susi Shelton testified that she was unable to wear her corrective 
contact lens without problems during June, July, and August 1995 because her eyes were dry 
from lack of sleep. Tr. at 460-462. However, Susi Shelton did testify that the removal of the 
discharge cones in June 1995 and an operational adjustment to reduce on-and-off cycling 
resulted in a modest reduction in the chiller unit noise. Tr. at 459. David Shelton also wrote in a 
letter to Steven Crown on June 26, 1995, that “[t]he new enclosure has helped, but it has not 
solved the air conditioner noise problem.” Exh. 41. 
Ms. Marjorie Julian testified that she was awakened at night by the noise from the Crown 
chiller unit and felt her floor vibrating from the noise. Tr. at 159-160. Ms. Julian and her 
husband, Robert, live just north of the Sheltons’ home at 727 Ardsley Road. Tr. at 126-127. The 
south face of the Julians’ home is approximately 120 to 145 feet from the Crowns’ north 
property line. Tr. at 155. 
MOTION TO DISMISS
11
The Crowns filed a motion to dismiss on the grounds that the case is now moot. Mot. 
Dis. at 1. The Crowns assert that the modifications to the chiller unit have reduced the noise 
emissions so that the unit meets both the numeric noise and nuisance noise standards. Mot. Dis. 
at 1. The Crowns maintain that even if the Board finds that the chiller unit emitted noises in 
1995 and 1996 that constituted noise pollution, there is no existing noise pollution and no future 
prospect of noise pollution . Mot. Dis. at 2. Therefore, the complaint should be dismissed with 
prejudice as moot. Mot. Dis. at 2. 
The Sheltons maintain that a Board order is necessary to ensure that the Crowns maintain 
the physical structures and operating protocols necessary to maintain compliance with the Act. 
Res. Mot. Dis. at 1. The Sheltons also cite Section 33 of the Act as a basis for ruling against the 
motion to dismiss: “It shall not be a defense to findings of violations of provisions of the Act or 
Board regulations or a bar to the assessment of civil penalties that the person has come into 
compliance subsequent to the violation...” 415 ILCS 5/33 (1996). 
The Board denies the motion to dismiss. There is ample statutory authority, as noted by 
the Sheltons at Section 33 of the Act (415 ILCS 5/33 (1996)), for the Board to find a violation of 
the Act or Board regulations in cases where compliance has been achieved subsequent to a 
violation. The Board will now discuss the allegations and findings of violation in the sections 
below. 
ARGUMENTS AND ANALYSIS 
The Sheltons have asserted that noise emitted by the Crowns’ chiller unit has violated 
both the numeric noise and nuisance noise regulations of the Board. First, the Board will discuss 
a novel argument raised by the Crowns which asserts that Section 31(b) of the Act (415 ILCS 
5/31(b) (1994)) does not authorize a citizen’s enforcement action with regard to past violations, 
based on conditions or emissions which did not exist and were not threatened when the 
complaint was filed. Resp. Br. at 3. Then, we will present the arguments and discuss the 
allegations concerning numeric noise violations. Finally, we will turn to the nuisance noise 
complaint and the civil penalty issue. 
Citizen’s Enforcement Authority with Regard to Past Violations 
The Crowns assert that because Section 31(b) of the Act (415 ILCS 5/31(b) (1994))
1 
which provides that a citizen may file “a written complaint ... against any person allegedly 
violating the Act...” is written in the present tense (i.e., violating), a citizen has no authority to 
bring enforcement action for past violations. The Crowns therefore maintain that the Board 
should use its discretionary power under Section 31(b) to dismiss the complaint. The Board does 
not agree with the Crowns, and can find no appellate or Supreme Court decision during the 
Board’s 27 years of existence that agrees with the Crowns’ argument. Therefore, the Board 
reiterates that the Sheltons have authority under Section 31(b) of the Act to bring this citizens 
enforcement action. 
1 
The Board notes that Section 31(b) in the 1994 version of the Illinois Compiled Statutes (415 
ILCS 5/31(b) (1994)) 
is now found at Section 31(d) of the Act (415 ILCS 5/31(d) (1996)).
12
Numeric Noise Allegations 
The Sheltons argue that the numeric noise limitations set forth at 35 Ill. Adm. Code 
901.102(a) and (b) apply to the Crown chiller unit and were exceeded on July 5, 1994, June 19, 
1995, June 26, 1996, and August 15, 1996. Comp. Br. at 43. The Sheltons maintain that the 
residential exemption from the numeric noise standards (35 Ill. Adm. Code 901.107(a)) does not 
apply since the Crowns’ chiller unit is not a residential unit but rather a commercial unit 
operated in a commercial manner. Comp. Br. at 43-44. In addition, the Sheltons assert that if 
the residential exemption does apply, it should only be applicable after March 1995, when the 
Crowns actually occupied their residence. Comp. Br. at 44. 
The Crowns argue that the numeric noise standards Section 901.102 have no application 
in this proceeding. The Crowns contend that Section 901.107(a) exempts the application of the 
numeric standards of Section 910.102 to sound emitted from land used as specified by SLUCM 
Code 100
2
, which includes “household units.” 35 Ill. Adm. Code 901.101(a) Appendix B at B-1 
Code 1100. The Crowns assert that characterization of the chiller unit as a commercial unit is 
irrelevant to an applicability determination with regard to the numeric noise standards at Section 
901.107(a). The Crowns maintain that the use of the premises on which the chiller is located 
determines the applicability of Section 901.107(a), since Section 907.107(a) specifically exempts 
“land used as specified in SLUCM Codes 110...,” where SLUCM Code 110 covers “household 
units.” Resp. Br. at 6. 
The Board finds that the Part 901.102 numeric standards do not apply in this case. The 
exemption at Section 901.107(a) and the SLUCM Code 110 (Part 905, Appendix B) indicates 
that the Part 901.102 numeric standards do not apply to sound emitted from land used for 
household units.
3 
Thus, it appears that the exemption at Section 901.107(a) would apply to 
noise emitted from the Crown chiller unit since the chiller unit is a part of the Crown residence, 
i.e. the “household unit.” The Board is not persuaded by the Sheltons’ argument that the Crown 
residence was a “construction site” from the time the Crowns began operating the chiller unit in 
1994, until the Crowns moved into the structure in March 1995, and therefore was not entitled to 
the residential exemption at Section 901.107. It is clear from the SLUCM definition of 
household unit that the intent to occupy a structure as separate living quarters is the key to this 
operational definition. There is no exception that during the construction phase, a household 
unit intended for occupancy as separate living quarters should be treated as a commercial unit. 
2 
The Board’s regulations adopted the use of the Standard Land Use Coding Manual (SLUCM) 
which 
3 
The term 
can be 
“household 
found at 35 
unit” 
Ill. 
is 
Admdefined 
. Code 
by 
901.101(a) 
the SLUCM 
Appendix 
Code as 
B. 
a house, an apartment, or other 
group of rooms, or a single room that is intended for occupancy as separate living quarters. 
Occupants of “household units” do not live and eat with other persons in the structure (such as 
boarding house), and there is either (1) direct access from the outside or through common hall, or 
(2) there is a kitchen or cooking equipment for exclusive use of the occupants of the unit. The 
occupants may be a family, a group of unrelated persons, or a person living alone. Mobile 
homes...
13
Even if the numeric standards were applicable, the review of the sound data indicates that 
the monitoring results cannot be compared with the numeric standards to establish a violation 
since the sound measurements were not obtained in accordance with the Board regulations at 
Section 900.103. Specifically, Section 900.103(b) requires sound measurements to be based 
upon L
eq 
averaging with a reference time of one hour. The Board has previously found that only 
sound levels measured on the basis of L
eq 
averaging over a period of one hour and corrected for 
ambient sound can be compared with the allowable octave band sound pressure levels specified 
at 35 Ill. Adm. Code 901.102 to show compliance or non-compliance. Tex v. Coggeshall, PCB 
90-182.
4 
Even though sound levels in this case appear to be measured on the basis of L
eq 
averaging, the reference times were significantly less than the required one hour. Therefore, 
even if the Board had not previously found that the residential exemption for the numeric noise 
standards applied in this case, the sound measurements in the record do not appear to be 
sufficient to find a numeric noise violation. However, as discussed further below, the sound 
evidence can still be considered when reviewing the Section 33(c) factors in a nuisance noise 
case. See Discovery South Group, Ltd., v. Pollution Control Board, 275 Ill. App. 3d 547, 559, 
656 N.E. 2d 51, 51(1st Dist. 1995). 
Nuisance Noise Allegations 
The Sheltons argue that the noise from the Crowns’ chiller unit unreasonably interfered 
with the Sheltons’ use and enjoyment of their home during those times when the chiller unit 
operated between September 1993 and August 1996. Comp. Br. at 8-25. The Sheltons maintain 
that the interference was unreasonable because a review of the five factors in Section 33(c) of the 
Act leads to a proposed Board finding against the Crowns for each factor. Comp. Br. at 41. 
Finally, the Sheltons assert that the Board should impose a $30,000 civil penalty. Comp. Br. at 
44. 
The Crowns maintain that this dispute has gone through two basic phases: the pre-
enclosure phase from fall 1993 to spring 1995, and the post-enclosure phase including summer 
and fall 1995 and early summer of 1996. Resp. Br. at 7. The Crowns argue that the noise 
controversy during the pre-enclosure phase was mediated by Winnetka and led to construction of 
the initial enclosure of the chiller unit in spring 1995. Essentially, the Crowns argue that 
because local authorities attempted to mediate the dispute during the pre-enclosure phase, the 
Board does not have jurisdiction over that time period. Resp. Br. at 7. The Crowns then argue 
that after the acoustic enclosure was in place, the Sheltons did not establish that the chiller unit 
noise unreasonably interfered with the Sheltons’ use or enjoyment of their property. Resp. Br. at 
11. The Crowns maintain that a number of witnesses testified that the acoustic enclosure 
reduced the sound levels emitted by the chiller unit in early summer 1995. Resp. Br. at 11. 
Finally, the Crowns challenged the Sheltons credibility and asserted that the Sheltons’ windows 
air conditioner was noisier than the Crown chiller unit. Resp. Br. at 13. 
4 
The Board has made exception to this precedent only in cases where a party has shown that the 
problem noise at issue is emitted in bursts shorter than one hour, such as discrete songs. See 
Village of Matteson v. World Music Theater 
(February 25, 1993), PCB 90-146, slip. op. 45-46, 
56, 275 Ill. App. 3d 547, 656 N.E. 2d 51 (1st Dist. 1995). Neither of the parties made such a 
demonstration in this case.
14
The Board finds that the testimony of the Sheltons clearly demonstrates that the noise 
from the Crowns’ chiller unit interfered with the Sheltons’ lives and use and enjoyment of their 
property. To determine if the interference was “unreasonable” the Board must examine the 
factors enumerated in Section 33(c) of the Act. Before proceeding to discuss the Section 33(c) 
factors, the Board will first address questions raised concerning the appropriate time frame to 
consider in this complaint. 
Appropriate Time Period 
The Crowns raise an apparent jurisdictional challenge to the Board’s authority to find 
nuisance noise violations pursuant to the Act for the “pre-enclosure phase” from fall 1993 to 
spring 1995 because Winnetka was attempting to “mediate” the dispute for that time period. The 
Board reiterates its order of October 5, 1995, which found that this complaint was not 
duplicitous, and therefore directed this matter to hearing. The Sheltons argue that the time 
period of the complaint should include the 1996 cooling season, up until the final enclosure 
adjustments in August 1996. However, the record shows that the Sheltons moved from their 
home in January 1996 and the house has apparently been sold. There is not enough evidence in 
the record to show that noise from the Crowns’ chiller unit interfered with the Sheltons’ lives 
and enjoyment of their property after they moved in January 1996. Therefore, the Board finds 
that the proper time period to consider in the action is from the chiller unit’s first operation in 
September 1993, until the Sheltons moved in January 1996. 
Section 33(c)(i): Degree of Injury or Interference 
In assessing the character and degree of injury or interference caused by the noise 
emissions from the Crowns’ chiller unit, the Board looked to whether the noises “substantially 
and frequently interferes with the use and enjoyment of life and property, beyond minor trifling 
annoyance or discomfort.” Kenneth Metivier and Cynthia Metivier v. Douglas Kenyon d/b/a 
Douglas Kenyon, Inc., PCB 92-74 slip op. at 4, (December 16, 1993), citing Kvatsak. Susi and 
David Shelton, and their son David B., all testified that they were unable to sleep due to the 
chiller unit noise, which was a constant feature of their environment during the cooling season 
for the time frame in question. Son David B. Shelton was not able to sleep in his bedroom on the 
second floor facing the Crowns’ residence on numerous occasions when the chiller unit was 
operating. He testified that noise from the Crowns’ chiller unit vibrated the windows and wall of 
his bedroom. All three Sheltons testifying noted increased stress and tension in the family when 
the chiller unit noise was present. In addition, Ms. Julian, the Sheltons’ neighbor to the north, 
further from the Crowns’ residence than the Sheltons, testified that the noise from the Crowns’ 
chiller unit awakened her at night and vibrated the floor of her home. Susi Shelton attributed 
several of her medical problems to the noise, but did not introduce any evidence from medical 
personnel into the record. Nevertheless, the record in this proceeding clearly indicates that the 
noise from the Crowns’ chiller unit went beyond mere trifling annoyance to substantially and 
frequently interfere with the Sheltons’ use and enjoyment of their property. The decibel level of 
the sound measurements in this record also support this analysis. Therefore, this 33(c) factor 
supports a Board finding of unreasonable interference.
15
Section 33(c)(ii): Social and Economic Value of the Pollution Source 
The record contains little information on the social and economic value of the pollution 
source. The only evidence concerns the necessity of removing humidity from the Crown 
residence to preserve elaborate interior appointments. Therefore, this 33(c) factor neither 
supports nor mitigates a Board finding of unreasonable interference. 
Section 33(c)(iii): Suitability or Priority of Location 
The documents published by the chiller unit manufacturer warned that the 25-ton chiller 
unit may not be suitable in a residential application because of noise emitted by the unit. The 
progression of sound measurements during the pendency of this dispute demonstrate that 
operational modification and a properly designed acoustical enclosure were essential to adapt 
this particular chiller unit to a residential setting. In summary, the Crowns’ chiller unit was 
unsuitable for a residential setting before the operational controls and proper acoustical 
enclosure were in place. Therefore, this 33(c) factor supports a Board finding of unreasonable 
interference. 
Section 33(c)(iv): Technical Practicability and Economic Reasonableness of Reducing 
Emissions 
The record in this case supports a finding that the nuisance noise from the Crown chiller 
unit has been attenuated, therefore the control methods were technically practicable. The record 
does not expressly address economic reasonableness, although some monetary figures are 
available. The total cost of the HVAC system was approximately $300,000. Stip. No. 1. The 
cost of noise control was approximately $20,000. Stip. No. 1. Therefore, the Board finds that 
the seven percent (7%) additional cost of appropriate noise control was reasonable and this 
factor supports finding an unreasonable interference. 
Section 33(c)(v): Subsequent Compliance 
The record indicates that the operational controls and acoustic enclosure have mitigated 
the noise emitted from the Crown chiller unit so that it is no longer produces nuisance noise. 
Therefore, this 33(c) factor mitigates a Board finding of unreasonable interference. 
Nuisance Noise Summary 
A review of all the factors set forth in Section 33(c) of the Act supports a finding that 
noise from the Crowns’ chiller unit was an unreasonable interference in the lives of the Sheltons 
during those times when the chiller unit was operating between September 1993 and January 
1996. The record shows that the effects on the Sheltons’ lives and enjoyment of their property 
went beyond mere annoyance. The record also demonstrates that the potential for noise 
problems in a residential setting with this chiller unit could have been anticipated before 
installation because of printed warnings in the manufacturer’s literature. The nuisance noise 
emissions were mitigated with operational controls and a properly designed acoustical enclosure, 
which added a reasonable seven percent (7%) to the cost of the HVAC system. Therefore, the
16
Crowns are found to have violated Section 23 and 24 of the Act because of the nuisance noise 
emissions from their chiller unit during the time period in question. 
CIVIL PENALTY 
In determing the appropriate civil penalty, the Board considers the factors set forth in 
Section 33(c) and Section 42(h) of the Act. See People v. Berniece Kershaw and Darwin Dale 
Kershaw d/b/a Kershaw Mobile Home Park, PCB 92-164 (April 20, 1994). The Board must bear 
in mind that no formulae exist, and all facts and circumstances must be reviewed. Kershaw, at 
14. 
The Board has stated that the statutory maximum penalty “is a natural or logical 
benchmark from which to begin considering factors in aggravation and mitigation of the penalty 
amounts” IEPA v. Allen Barry, individually and d/b/a Allen Barry Livestock, PCB 88-71, 111 
PCB 11 at 72 (May 10, 1990). The formula for calculating the maximum penalty is contained in 
Section 42(a) and (b) of the Act (415 ILCS 5/42(a) and (b) (1994)). Section 42(a) provides for a 
civil penalty not to exceed $50,000 for violating a provision of the Act or Board regulations, and 
an additional civil penalty not to exceed $10,000 for each day during which the violation 
continues. 
Section 42(h) of the Act states that “[i]n determining the appropriate civil penalty to be 
imposed, the Board is authorized to consider any matters of record in mitigation or aggravation 
of penalty, including but not limited to the following factors: (1) the duration and gravity of the 
violation; (2) the presence or absence of due diligence on the part of the violator in attempting to 
comply with the requirements of this Act and regulations there under or to secure relief 
therefrom as provided by this Act; (3) any economic benefits accrued by the violator because of 
delay in compliance with requirements; (4) the amount of monetary penalty which will serve to 
deter further violations by the violator and to otherwise aid in enhancing voluntary compliance 
wit this Act by the violator and other persons similarly subject to the Act; and (5) the number, 
proximity in time, and gravity of previously adjudicated violations of this Act by the violator.” 
The Sheltons argue that the Board could order a maximum penalty of $3,050,000 based 
on Section 42(a) of the Act. Comp. Br. at 46. The Sheltons maintain that based on their review 
of the 42(h) factors, a civil penalty of $30,000 should be levied by the Board in this case. Comp. 
Br. at 45-46. The Crowns argue that in view of all the eventually successful measures taken to 
control sounds emitted by the chiller unit, no civil penalty is warranted. Resp. Br. at 17. 
After careful review of the Section 42(h) factors, as indicated in the remainder of this 
paragraph, and Section 33(c) factors discussed above, the Board finds that no civil penalty is 
warranted in this case. The record indicates that the duration and gravity of the violation 
supports a civil penalty. Section 42(h)(1). However, Board consideration of the other four 
factors does not support a civil penalty. The Board is concerned that mitigation of the nuisance 
noise took two full cooling seasons (see due diligence, Section 42(h)(2)), however, the record 
also shows that the Crowns continually experimented with noise control measures during that 
time. There is nothing in the record to indicate that the Crowns received economic benefits from 
noncompliance. Section 42(h)(3). The Crowns are presently in compliance, so no monetary
17
penalty is necessary to enhance compliance. Section 42(h)(4). Finally, there is nothing in the 
record to indicate that the Crowns have any previously adjudicated violations of the Act. 415 
ILCS 5/42(h)(5). 
ORDER 
The Board finds that the Crowns have violated Section 23 and 24 of the Illinois 
Environmental Protection Act in relation to the nuisance noise emitted by the chiller unit on their 
property at 685 Ardsley Road, Winnetka, Cook County, Illinois, during the times when the 
chiller unit operated between September 1993 and January 1996. The Board finds that no civil 
penalty is warranted in this case. 
This docket is closed. 
IT IS SO ORDERED. 
Section 41 of the Environmental Protection Act (415 ILCS 5/41 (1996)) provides for the 
appeal of final Board orders to the Illinois Appellate Court within 35 days of service of this 
order. Illinois Supreme Court Rule 335 establishes such filing requirements. See 145 Ill. 2d R. 
335; see also 35 Ill. Adm. Code 101.246, Motions for Reconsideration. 
I, Dorothy M. Gunn, Clerk of the Illinois Pollution Control Board, hereby certify that the 
above opinion and order was adopted on the 2nd day of October 1997, by a vote of 7-0.
Dorothy M. Gunn, Clerk 
Illinois Pollution Control Board