ILLINOIS POLLUTION CONTROL BOARD
    June 1, 2006
     
    IN THE MATTER OF:
     
    PETITION OF LAFARGE MIDWEST, INC.
    FOR BOILER DETERMINATION
    THROUGH ADJUSTED STANDARD
    PROCEEDINGS PURSUANT TO 35 Ill.
    Adm. Code 720.132 AND 720.133
    )
    )
    )
    )
    )
    )
    )
     
     
    AS 06-3
    (Adjusted Standard - Land)
     
    OPINION AND ORDER OF THE BOARD (by A.S. Moore):
     
    Lafarge Midwest, Inc. (Lafarge) filed a petition seeking the Board’s determination that
    two raw mill dryers operated at its Joppa Portland Cement Manufacturing Plant (Plant) located at
    2500 Portland Road, Grand Chain, Massac County may both be considered a “boiler” as that
    term is defined at 35 Ill. Adm. Code 720.110 (definitions). A boiler determination would allow
    Lafarge’s dryers to be used for the combustion of off-specification used oil for energy recovery
    in compliance with 35 Ill. Adm. Code 739.161. The Illinois Environmental Protection Agency
    (Agency) recommends that the Board grant Lafarge’s petition.
     
    In today’s opinion, the Board finds on the basis of the record before it that Lafarge has
    provided sufficient justification under 35 Ill. Adm. Code 720.132 for a boiler designation for the
    two raw mill dryers at the Plant.
     
    This opinion will first describe the general procedure through which a petitioner may
    seek a boiler designation before providing the procedural and factual backgrounds of this case.
    The Board then analyzes the criteria by which the Board is to make boiler determinations on a
    case-by-case basis. Finally, the Board reaches its conclusion and issues its order.
     
    BOILER DESIGNATION PROCEDURE AND JUSTIFICATION
     
    In its Resource Conservation and Recovery Act (RCRA) waste disposal regulations, the
    Board has adopted standards for the management of used oil. 35 Ill. Adm. Code 739.100
    et seq
    .;
    see
    RCRA Update, USEPA Regulations (July 1, 1992 through December 31, 1992), R93-4
    (Sept. 23, 1993) (adopting new Part 739); RCRA Update, USEPA Regulations (April 24, 1984
    through June 30, 1985), R85-22 (Jan. 9, 1986) (adopting provisions regarding boiler
    determinations). Specifically, those used oil regulations allow burning of off-specification used
    oil for energy recovery in a limited number of devices including “[i]ndustrial boilers located on
    the site of a facility engaged in a manufacturing process where substances are transformed into
    new products, including the component parts of products, by mechanical or chemical processes.”
    35 Ill. Adm. Code 739.161(a)(2)(A).
     
    The Board has also promulgated regulations providing procedures and criteria for making
    a determination that certain devices are “boilers” that may be used for burning off-specification
    used oil, even though those devices do not otherwise meet the definition of “boiler.”
    See
    35 Ill.

     
     
      
    2
    Adm. Code 720.110 (defining “boiler” as enclosed device using controlled flame combustion
    and having specified characteristics); 35 Ill. Adm. Code 720.132 (Boiler Determinations); 35 Ill.
    Adm. Code 720.133 (Procedures for Determinations).
     
    The Board’s boiler determination regulations provide that a petitioner must seek a boiler
    determination through procedures for an adjusted standard: “[t]he Board will use the procedures
    of Subpart D of 35 Ill. Adm. Code 104 for determining . . . whether a particular enclosed flame
    combustion device is a boiler.” 35 Ill. Adm. Code 720.133;
    see
    35 Ill. Adm. Code 104.400 -
    104.428 (Adjusted Standards). Among other requirements, Subpart D requires that a petition for
    a boiler determination must contain specific information.
    See
    35 Ill. Adm. Code 104.406.
     
    “The burden of proof in an adjusted standard proceeding is on the petitioner.” 35 Ill.
    Adm. Code 104.426. “If the regulation of general applicability specifies a level of justification
    for an adjusted standard, the Board may adopt the proposed adjusted standard, if the petitioner
    proves the level of justification specified by the regulation of general applicability.” 35 Ill. Adm.
    Code 104.426(b);
    see
    415 ILCS 5/28.1(b) (2004). As noted above, the Board has specified the
    level of justification for making a boiler determination in Section 720.132. 35 Ill. Adm. Code
    720.132. The Board determines on a case-by-case basis whether a device is a boiler, even
    though it does not otherwise meet the definition of one, by considering six criteria. 35 Ill. Adm.
    Code 720.132(a-f). Those criteria are: the extent to which the unit provides for recovering and
    exporting thermal energy; the extent to which the combustion chamber and energy recovery
    equipment are of integral design; the efficiency of energy recovery; the extent to which exported
    energy is used; the extent to which the device is in common and customary use as a “boiler;” and
    other relevant factors.
    Id
    . The Board addresses each of these six factors individually below
    under “Criteria for Determination.”
     
    PROCEDURAL BACKGROUND
     
    On March 29, 2006, Lafarge petitioned the Board (Pet.) for a boiler determination
    through adjusted standard proceedings pursuant to 35 Ill. Adm. Code 720.132 and 720.133.
    Lafarge waived its right to a hearing on the petition. Pet. at 49,
    see
    35 Ill. Adm. Code 104.406(j)
    (requiring statement requesting or waiving hearing on petition).
     
    The Act and the Board’s regulations require publication of notice of a petition for an
    adjusted standard in a newspaper of general circulation in the area likely to be affected by the
    petitioner’s activity. 415 ILCS 5/28.1(d)(1) (2004); 35 Ill. Adm. Code 104.408(a). The
    petitioner must publish notice within 14 days of filing a petition for an adjusted standard with the
    Board. 415 ILCS 5/28.1(d)(1) (2004); 35 Ill. Adm. Code 104.408(a). As required, Lafarge on
    April 27, 2006 timely filed with the Board proof of publication indicating
    The Metropolis Planet
     
    published notice of the petition on April 12, 2006.
    See
    35 Ill. Adm. Code 104.410 (requiring
    filing of certificate within 30 days after filing petition). The Board received no request to hold a
    hearing in this matter.
     
    On May 11, 2006, the Agency filed its recommendation (Rec.). The Agency stated that,
    since 2004, it had discussed the requirements for boiler determinations with Lafarge. Rec. at 1.
    The Agency reports that Lafarge has satisfactorily addressed its questions and has incorporated

     
     
      
    3
    that information into its petition. Rec. at 2. Accordingly, the Agency recommends that the
    Board grant Lafarge’s petition and designate the two raw mill dryers at the Plant as boilers. Rec.
    at 3.
     
    FACTUAL BACKGROUND AND PETITION CONTENTS
     
    Plant Operations
     
    Lafarge owns and operates the Plant, which is located adjacent to the Ohio River at the
    common address of 2500 Portland Road, Grand Chain in Massac County. Pet. at 2; Pet., Exh. A
    (aerial photograph of vicinity of Plant). The Plant began operation in 1960 and has since
    undergone improvements and expansions. Pet. at 15. Lafarge characterizes Massac County as
    “predominantly rural” (Pet. at 2) and states that the Plant is “remote from any significant
    residential development” (Pet. at 48; Pet., Exh B (map of population density in vicinity of Plant).
    “As of January 1, 2005, Lafarge employed 124 full-time employees,” including 43 salaried
    employees, with a total annual payroll for 2004 of approximately $7,737,000. Pet. at 15.
     
    The Plant “manufactures Portland cement, which is the active ingredient of concrete.”
    Pet. at 3. While cement can be manufactured through “wet” or “dry” methods, the Plant uses the
    dry method in which Lafarge grinds, mixes, and feeds raw materials in a dry state to its two
    cement kilns. Pet. at 3. Lafarge reports that “limestone rock is the principal raw material used”
    in its manufacturing process.
    Id
    . Limestone and other raw materials primarily arrive at the Plant
    by Ohio River barges. Pet. at 3, 10. After unloading and screening these shipments, Lafarge
    conveys them “to outside storage piles, covered storage piles, concrete storage bins, and enclosed
    steel tanks.” Pet. at 10. Through a number of mechanisms, Lafarge gradually reclaims these raw
    materials from storage for use in its manufacturing process.
    Id
    .
     
    In the first stage of that process, Lafarge forms a “raw mix” consisting mostly of
    limestone and feeds it into the raw mill system. Pet. at 11. Because the raw materials are
    generally wet before processing, “[t]he raw mix is then dried by direct contact with the hot dry
    gas produced by the Raw Mill Dryers.”
    Id
    . After drying, the raw mix is ground to a fine
    consistency.
    Id
    . Once ground, “coarser material is mixed with new raw material and sent back
    through the drying and grinding processes.”
    Id
    . Fine material is conveyed to storage near the
    feed end of the cement kilns.
    Id.
     
     
    “After introduction to the kiln, the raw material is heated to almost 3,000° F.” Pet. at 4.
    The kilns transform the raw materials into “clinker,” which is ground into finished Portland
    cement. Pet. at 12. Because the heat of the kilns drives off additional moisture and triggers
    chemical reactions yielding gaseous products, “[t]he ratio of raw feed to clinker is approximately
    1.5 to 1.”
    Id
    . After leaving the kilns, the clinker undergoes air-cooling before being conveyed to
    storage. Pet. at 12-13.
     
    Lafarge operates two finish mill systems in which it combines clinker with a small
    amount of gypsum and then grinds the mix to a fine particle size. Pet. at 4, 13. Lafarge then
    conveys the finished Portland cement product to storage silos, from which the product can be
    transferred to trucks or river barges. Pet. at 13.

     
     
      
    4
     
    Plant Emissions
     
     
    Lafarge notes that, to comply with federal and state emissions regulations, it submits to
    the Agency an Annual Emissions Report (AER) regarding activities at the Plant. Pet. at 15. In
    its most recent AER filed March 15, 2005, Lafarge reported the following emissions for the
    entire facility: carbon monoxide (CO), 448 tons/year; lead, 0.14 tons/year; NH3, 1.4 tons/year;
    nitrogen oxides (NOx), 3,310 tons/year; particulate matter (PM), 256 tons/year; particulate matter
    with an aerodynamic diameter less than or equal to a nominal 10 micrometers (PM10), 183
    tons/year; PM2.5, 30 tons/year, sulfur dioxide (SO2), 745 tons/year; and volatile organic material
    (VOM), 163 tons/ year. Pet at 15-16;
    see
    Pet, Exh. D (2004 AER).
     
    Lafarge states that, on January 14, 2004, the Agency issued it a construction permit
    authorizing the Plant’s two raw mill dryers to use both natural gas and on-specification used oil
    as fuels. Pet. at 13;
    see
    Pet., Exh. C (construction permit 03080024). The construction permit
    allows the following emissions: NOx, 16.60 tons/year; CO, 4.15 tons/year; SO2, 39.00 tons/year;
    PM, 0.10 tons/ year; and VOM, 0.50 tons/year. Pet. at 14; Pet., Exh. C at 2.
     
    Lafarge reports that it controls emissions from its raw mill system through “modern,
    high-efficiency fabric filter baghouse particulate control systems.” Pet. at 21. Lafarge further
    reports that “these baghouse systems typically achieve greater than 99.9% overall control
    efficiency.”
    Id
    . Because these filters capture dried raw materials entrained in exhaust gases and
    allow those materials to be returned to the production process, Lafarge argues that it has “a
    strong economic incentive to operate the fabric filter baghouses at maximum removal
    efficiency.”
    Id
    .
     
    Lafarge has estimated the particulate emissions that may result from the combustion of
    up to 1,500,000 gallons of off-specification used oil as supplemental fuel in the raw mill dryers
    and has concluded that PM and PM10 emissions “will be orders of magnitude lower than the
    emissions allowed by the CAAPP Title V Operating Permit.” Pet. at 22;
    see
    Pet., Exhs. D, F.
    Lafarge has also concluded that combustion of off-specification used oil will also comply with
    the construction permit issued in 2004 and allowing the use of on-specification used oil as fuel
    for the two raw mill dryers. Pet. at 22;
    see
    Pet., Exh. C. Based on these conclusions, Lafarge
    believes “that no modifications to the existing fabric filter baghouse control equipment will be
    required to further control emissions when combusting off-specification used oil fuel.” Pet. at
    22. Lafarge also believes that it will require no additional pollution control equipment to control
    those emissions. Pet. at 22-23.
     
     
    Lafarge states that, if the Board grants its petition for a boiler determination, “[t]he only
    consequence associated with the Board’s approval . . . would be a possible change in the air
    emissions from the Raw Mill Dryers.” Pet. at 26. Lafarge reports that it now complies with its
    CAAPP emissions limits through full combustion of its fuel and the use of equipment to remove
    particulate matter from exhaust gases.
    Id
    . After investigating off-specification used oil fuel
    supplied by reputable marketers, Lafarge estimates that emissions resulting from the use of used
    oil fuels “would not exceed the existing permit limits.”
    Id
    .;
    see
    Pet., Exh. G (off-specification
    used oil fuel management principles for Plant). Lafarge adds that the use of used oil fuel must be

     
     
      
    5
    reviewed and approved by the Agency through the permit issuance and modification processes.
    Pet. at 23, 26-27;
    see
    Pet. Exh. F (CAAPP permits).
     
    In addition to the air emissions addressed above, Lafarge reports that it “discharges
    process wastewater, sanitary wastewater, and stormwater runoff under NPDES Permit No.
    IL0004081” issued May 26, 2000. Pet. at 16-17. While that permit was effective for a period of
    five years, Lafarge states that it submitted a timely application for renewal and that the permit
    remains in effect until the Agency acts on the application. Pet. at 16. Lafarge also report that it
    obtained a permit on April 19, 2005 for the construction of a new sanitary wastewater treatment
    facility.
    Id
    . That facility began operation in November 2005.
    Id
    .
     
    Relief Sought
     
    Lafarge notes that the Board has adopted standards for management of used oil. Pet. at 6;
    see
    35 Ill. Adm. Code 739.100
    et seq
    . Specifically, those regulations allow burning of off-
    specification used oil for energy recovery in “[i]ndustrial boilers located on the site of a facility
    engaged in a manufacturing process where substances are transformed into new products,
    including the component parts of products, by mechanical or chemical processes.” Pet. at 6-7,
    citing 35 Ill. Adm. Code 739.161(a)(2)(A).
     
    Lafarge further notes that the Board has also promulgated regulations providing
    procedures and criteria for determining that certain devices are “boilers” that may be used for
    burning off-specification used oil, even though those devices do not otherwise meet the
    definition of “boiler.” Pet. at 7,
    see
    35 Ill. Adm. Code 720.110 (definition). “Section 720.132
    establishes the criteria to be considered by the Board in making such ‘case-by-case’
    determinations, and Section 720.133 mandates use of the Adjusted Standard procedures of
    Subpart D of 35 Ill. Adm. Code 104.” Pet. at 7, citing 35 Ill. Adm. Code 720.132, 720.133.
    Lafarge states that these regulations implement, in whole or in part, the state’s program for solid
    waste under RCRA. Pet. at 8;
    see
    42 U.S.C. § 6901
    et seq.
      
     
    While Lafarge believes that its raw mill dryers meet the regulatory definition of a boiler,
    the Agency has advised Lafarge that it must seek a boiler determination in order to use off-
    specification used oil as a fuel. Pet. at 18. Because of the Agency’s advice, Lafarge states that it
    “would not risk an enforcement action by proceeding to utilize off-specification used oil as a
    fuel.”
    Id
    . Viewing the Agency’s interpretation as a prohibition from burning off-specification
    used oil, Lafarge states that “[t]here are no compliance alternatives, no capital improvements and
    no operational changes that would allow Petitioner to ‘comply with the regulation of general
    applicability.’” Pet. at 18-19.
     
    Lafarge states that it proposes to use off-specification used oil as a cost-saving measure.
    Pet. at 19. Lafarge “is proposing to use approximately 1,500,000 gallons of used oil fuel per
    year in the Raw Mill Dryers.”
    Id
    . At current market prices averaging $0.91 per gallon for
    specification used oil and $0.81 per gallon for off-specification used oil, Lafarge expects to save
    $88,000 annually by replacing specification used oil with off-specification used oil as fuel for its
    raw mill dryers.
    Id
    . Further, Lafarge expects the cost advantage of off-specification used oil to
    increase. Lafarge believes that increasing demand for natural gas will continue to outstrip new

     
     
      
    6
    production, resulting in higher natural gas prices.
    See id
    . However, Lafarge also acknowledges
    that market prices for specification and off-specification used oil will increase. Pet. at 20-21.
    While high natural gas prices might once have led some industrial facilities to convert to the use
    of refined oil fuels, Lafarge suggests that oil prices of $60-$70 per barrel have all but eliminated
    the incentive for that conversion. Pet. at 20. Generally high-energy prices, according to Lafarge,
    have increased the demand for used oil, and that increased demand will tend to increase its
    market price. Pet. at 20-21.
     
    Lafarge notes that section 720.132 of the Board’s regulations provides criteria for making
    boiler determinations. Pet. at 29, citing 35 Ill. Adm. Code 720.132. Lafarge further notes that
    these criteria closely track the regulatory definition of “boiler.” Pet. at 29, citing 35 Ill. Adm.
    Code 720.110. Lafarge suggests that the Board’s analysis of the criteria in section 720.132 is an
    analysis of whether its raw mill dryers have the physical characteristics of a boiler.
    See
    Pet. at
    29; 35 Ill. Adm. Code 720.110 (definition of “boiler”). The Board addresses each of those
    criteria below under “Criteria for Determination.”
     
    Lafarge notes that sections 7.2 and 22.4(a) of the Act (415 ILCS 5/7.2, 22.4(a) (2004))
    require the Board to adopt regulations that are “identical-in-substance” to hazardous waste
    regulations adopted by USEPA under RCRA. Pet. at 48, citing 42 U.S.C. 6921
    et seq
    . Lafarge
    further notes that federal and state regulations provide virtually identical mechanisms for
    determining whether a device is a “boiler” even if it does not otherwise meet the regulatory
    definition of that term. Pet. at 49, citing 40 C.F.R. 260.32;
    see
    35 Ill. Adm. Code 720.132.
    Consequently, “[a]pproval by the Board of Lafarge’s Petition would be consistent with federal
    law and the implementing RCRA regulations.” Pet. at 49.
     
    Finally, although it states that “[t]he regulation of general applicability does not specify
    any additional information requirements,” Lafarge requests that the Board consider the action of
    other regulatory agencies that have made boiler determinations. Pet. at 50. Lafarge reports that
    the raw mill dryers at its Alpena, Michigan plant are “virtually identical” to the dryers that are
    the subject of this petition.
    Id
    . Lafarge emphasizes that the Michigan Department of
    Environmental Quality (DEQ) determined that the Alpena dryers “meet the physical
    characteristics of a ‘boiler’” and approved Lafarge’s request to use off-specification used oil in
    them.
    Id
    .; Pet., Exh. I.
     
    CRITERIA FOR DETERMINATION
     
     
    Lafarge argues that it has demonstrated its raw mill dryers “satisfy each of the criteria
    specified at 35 Ill. Adm. Code 720.132(a) to be considered a boiler.” Pet. at 30, citing 35 Ill.
    Adm. Code 720.132(a);
    see
    35. Ill. Adm. Code 104.406(h) (justification). In its
    recommendation, the Agency “does not take issue with Petitioner’s statements on this subject.”
    Rec. at 2. The Board addresses each of the six criteria separately below.
     
    Recovering and Exporting Thermal Energy (35 Ill. Adm. Code 720.132(a))
     
     
    Lafarge states that, in order to heat the raw material mix and drive moisture from it, the
    burners in the raw mill dryers are “designed to recover the maximum amount of thermal energy

     
     
      
    7
    in the fuel being burned.” Pet. at 30. Lafarge report that “[e]ach Raw Mill Dryer functions as a
    direct-fired process heater.”
    Id
    . Thermal energy released by the combustion of fuel is
    transferred to the raw materials in order to vaporize moisture contained in the pores of that
    material. Pet. at 30-31. The dryers then export heated and dried raw materials, hot gases, and
    water vapor, all of which then pass through separators for removal of the dried raw materials
    from the exhaust gases. Pet. at 31.
     
    Lafarge describes it raw mill dryers as “fully enclosed with an outer shell of steel.” Pet.
    at 31. It characterizes the burning chamber as “lined with a high temperature resistant refractory
    material” and states that the “transport shaft is lined with ceramic tile.”
    Id
    . Consequently,
    Lafarge argues that “[t]his design is conducive to recovering as much energy as possible from
    the fuel.”
    Id
    .;
    see
    Pet., Exh. H (“Raw Mill System Schematic”).
     
    On the basis of this record, the Board finds that Lafarge’s two raw mill dryers have
    provisions in their design and operation for recovering and exporting thermal energy released by
    the combustion of off-specification used oil fuel.
    See
    35 Ill. Adm. Code 720.132(a). In this
    regard, the two raw mill dryers share physical characteristics with devices that meet the
    regulatory definition of “boiler.”
    See
    35 Ill. Adm. Code 720.110. Accordingly, the Board’s
    consideration of this factor favors designating each of the two raw mill dryers as a boiler.
     
    Integral Design (35 Ill. Adm. Code 720.132(b))
     
     
    Lafarge states that “[t]he combustion chamber and energy recovery sections of each Raw
    Mill Dryer are integral in design and assembly to function as a single unit.” Pet. at 31. Lafarge
    further states that it installed the systems as one operating unit.
    Id
    .;
    see
    Pet., Exh. H. Lafarge
    asserts that, within each system, the operation of the raw mills and raw mill dryers depend upon
    one another.
    Id
    .
     
    In addition, Lafarge argues that the Board’s definition of “boiler” includes an exemption
    from the “integral design” factor that applies to its dryers. Pet. at 31. Under that definition,
    “process heaters (units that transfer energy directly to a process stream)” “are not precluded from
    being boilers solely because they are not of integral design.” Pet. at 32, citing 35 Ill. Adm. Code
    720.110. Lafarge argues that, “[b]ecause the Raw Mill Dryers are direct-fired process heaters
    where the thermal energy of the combusted fuel is transferred directly to the raw materials being
    processed, the element of ‘integral design’ is not a sole determinative in this proceeding.” Pet. at
    32.
     
    The record in this proceeding demonstrates that Lafarge’s two raw mill dryers are direct-
    fired process heaters, which share physical characteristics with devices that meet the regulatory
    definition of “boiler.”
    See
    35 Ill. Adm. Code 720.110. As such, Lafarge’s two raw mill dryers
    qualify for the “process heater” exception under section 720.110.
    Id
    . Accordingly, the Board’s
    consideration of this factor favors designating each of the two raw mill dryers as a boiler.
     
    Efficiency of Energy Recovery (35 Ill. Adm. Code 720.132(c))
     
     

     
     
      
    8
    Lafarge notes that the regulatory definition of “boiler” sets a standard for thermal energy
    recovery efficiency: “at least 60 percent, calculated in terms of the recovered energy compared
    with the thermal value of the fuel.” Pet. at 41, citing 35 Ill. Adm. Code 720.100. Lafarge reports
    that, in order to calculate the efficiency of energy recovery, it conducted a detailed analysis of its
    raw mill dryers. Pet. at 32. Specifically, Lafarge developed a heat balance, which is “essentially
    a detailed accounting of the distribution of heat input, heat output, and system losses.” Pet. at 40.
    “[H]eat balance accounting relies on actual test data, mathematical derivations, and generally
    accepted engineering assumptions, ” and it provides input variables for the efficiency calculation.
    Pet. at 33, 40.
     
    Lafarge states that it relied upon two engineering assumptions in preparing heat balance
    calculations. First, for the “false air” assumption taking into account expansion joints, inspection
    doors and ports, normal equipment wear, and other leaking into the system, Lafarge assumed a
    value of 10%. Pet. at 40-41. Lafarge states that, within the cement industry generally and
    specifically for newer combustion equipment in cement manufacturing and mineral processing
    facilities, 10% is “an accepted assumption.”
    Id
    . Second, for the “shell radiation” assumption
    accounting for radiant heat lost to structures surrounding the dryer, Lafarge assumed a value of
    2.5 %. Pet. at 41. Lafarge also characterized this assumption as “accepted.”
    Id
    .
     
    Ultimately, Lafarge determined its energy recovery efficiency by dividing the recovered
    energy by the thermal value of the fuel for each of the two raw mill dryers. Pet. at 41-42. These
    calculations resulted in a thermal energy recovery efficiency of 86.84% for the first raw mill
    dryer and 82.05% for the second. Pet. at 42. Lafarge argues that the efficiency of the two dryers
    “clearly exceeds the Section 720.110 criterion of a minimum of 60% recovery.”
    Id
    .
     
    The record in this proceeding demonstrates that Lafarge’s two raw mill dryers achieve a
    thermal energy recovery efficiency of 86.84% for the first raw mill dryer and 82.05% for the
    second. With efficiency exceeding 60%, the two raw mill dryers share physical characteristics
    with devices that meet the regulatory definition of “boiler.”
    See
    35 Ill. Adm. Code 720.110.
    Accordingly, the Board’s consideration of this factor favors designating each of the two raw mill
    dryers as a boiler.
     
    Use of Exported Energy (35 Ill. Adm. Code 720.132(d))
     
     
    Lafarge suggests that the raw mill dryers use exported energy in a manner consistent with
    the regulatory definition of a boiler. Lafarge notes that the definition specifies “[t]he unit must
    export and realize at least 75% of the recovered energy, calculated on an annual basis. In this
    calculation, no credit may be given for recovered heat used internally in the same unit.” Pet. at
    42, citing 35 Ill. Adm. Code 720.110. Lafarge states that “[i]nternal use of the recovered heat
    only occurs during preheating every time the system is started” and that “preheating hours
    account for 1.5% of the total operating hours in a year.” Pet. at 42. Lafarge concludes that,
    “[w]ith the loss of 1.5% of the fuel heat input due to preheating the dryer, the annual energy
    recovery is estimated to be 82.40% for Raw Mill Dryer #1 and 79.85% for Raw Mill Dryer #2.”
    Id
    .
     

     
     
      
    9
    The record in this proceeding demonstrates that Lafarge’s two raw mill dryers export and
    realize 82.40% and 79.85%, respectively, of the recovered energy, calculated on an annual basis.
    In this regard, they share physical characteristics with devices that meet the regulatory definition
    of “boiler.”
    See
    35 Ill. Adm. Code 720.110. Accordingly, the Board’s consideration of this
    factor favors designating each of the two raw mill dryers as a boiler.
     
    Use as “Boiler” (35 Ill. Adm. Code 720.132(e))
     
     
    Lafarge argues that its raw mill dryers are functionally equivalent to boilers. Lafarge
    states that “[d]irect-fired dryers and process heaters are widely used in the production of cement
    and other non-metallic mineral products.” Pet. at 42. These devices consume large amounts of
    fuel in order to generate the high temperatures needed to dry raw materials and ultimately
    produce Portland cement. Pet. at 42-43.
     
    Lafarge states that it operates a large Portland cement manufacturing plant near Alpena,
    Michigan. Pet. at 43. The Michigan DEQ has granted that plant permission to use off-
    specification used oil as fuel in its raw mill dryers.
    Id
    . Lafarge states that DEQ based its
    approval on a demonstration that the dryers satisfied the physical boiler criteria established by
    USEPA and adopted by both Michigan and Illinois.
    Id
    .;
    see
    Pet., Exh I. (DEQ concurrence that
    dryer is boiler).
     
    Lafarge contends that the raw mill dryers at the Plant and in Alpena are “virtually
    identical” with respect to the to the physical criteria contained in the regulatory definition of
    “boiler,” including integral design, combustion efficiency, and energy recovery.” Pet. at 44.
    Lafarge claims that DEQ’s determination that the Alpena dryers have boiler characteristics is
    persuasive evidence that that the dryers in this proceeding are “in common and customary use as
    a ‘boiler’ functioning primarily to produce steam, heated fluids, or heated gases.” Pet. at 44-45,
    citing 35 Ill. Adm. Code 720.132(e). Lafarge further claims that, if the Board grants a boiler
    determination in this case, that result “would be consistent with the findings of other
    environmental regulatory authorities.” Pet. at 45.
     
    The record in this proceeding shows that Lafarge’s two raw mill dryers are commonly
    and customarily used as boilers functioning primarily to produce steam, heated fluids, or heated
    gases. Accordingly, the Board’s consideration of this factor favors designating each of the two
    raw mill dryers as a boiler.
     
    Other Relevant Factors (35 Ill. Adm. Code 720.132(f)
     
     
    Lafarge states that federal used oil regulations specify both procedures and criteria for
    making a case-by-case determination that a particular combustion device such as its raw mill
    dryers should be considered a “boiler” for the purpose of using off-specification used oil fuel.
    Pet. at 45, citing 40 C.F.R. 260.32 (criteria), 40 C.F.R. 260.33 (procedures). Lafarge notes that
    the Board “has completed ‘identical-in-substance’ rulemakings to adopt these federal RCRA
    regulations as the Illinois regulations applicable to the combustion of off-specification used oil in
    boilers and similar combustion devices.” Pet. at 45;
    see
    RCRA Update, USEPA Regulations
    (April 24, 1984 through June 30, 1985), R85-22 (Dec. 20, 1985).

     
     
      
    10
     
    Lafarge notes that, in the preamble accompanying publication of the rules in the
    Federal
    Register
    , USEPA explained regulations and applied them to specific fact patterns. Pet. at 45.
    Lafarge urges that “the justifications set forth by USEPA to explain and interpret the criteria for
    making ‘case-by-case’ boiler determinations can and should be relied upon by the Board.” Pet.
    at 46. In its preamble, USEPA elaborated on four factors that distinguish industrial boilers from
    non-industrial boilers with regard to allowing the burning of off-specification used oil for fuel.
    Pet. at 46-47, citing 50 Fed. Reg. 49164. First, because industrial boilers are less numerous and
    are less likely to be located in populated areas, those sources pose less risk of exposing
    individuals to emissions from burning off-specification used oil. Pet. at 46. Second, industrial
    boilers are more likely to be operated by trained personnel.
    Id
    . Third, industrial boilers are more
    likely to be “equipped with combustion controls sophisticated enough to maintain peak
    combustion efficiency when burning fuels the unit is not designed to burn.”
    Id
    ., citing 50
    Fed.Reg. 49182. Finally, “many industrial furnaces and some boilers are equipped with
    particulate control equipment that may adequately control emissions from metal-bearing waste
    fuels. Pet. at 46-47, citing 50 Fed. Reg. 49182.
     
    Addressing those factors, Lafarge first notes that its plant “is located in the sparsely
    populated, rural Massac County and its location is remote from any significant residential
    development.” Pet. at 47-8;
    see
    Pet., Exh. B (USEPA population density map of vicinity of
    plant). Second, Lafarge states that its plant and the raw mill dryers in particular are operated by
    trained personnel. Pet. at 48. Third, Lafarge notes that “[t]he Raw Mill Dryers are equipped
    with [] state-of-the-art, efficient combustors and operating controls to maximize complete
    combustion of the fuels.”
    Id
    . Finally, Lafarge states that the dryers incorporate fabric filter
    baghouses, cyclones, and air separators to capture dried raw materials and to control the emission
    of particulates and other contaminants.
    Id
    . Lafarge concludes that, in addition to satisfying
    physical criteria established by the Board, its dryer also satisfies non-physical criteria that justify
    combustion of off-specification used oil. Pet. at 47.
     
    The record in this proceeding demonstrates that Lafarge’s two raw mill dryers generally
    satisfy these non-physical criteria established for boilers. Accordingly, the Board’s
    consideration of this factor favors designating each of the two raw mill dryers as a boiler.
     
    CONCLUSION
     
    For the reasons described above, the Board finds that Lafarge has provided sufficient
    justification under 35 Ill. Adm. Code 720.132 and determines that each of the two raw mill
    dryers at its Joppa Portland Cement Manufacturing Plant is a “boiler by designation” under 35
    Ill. Adm. Code 720.110. This determination allows Lafarge to use the two raw mill dryers for
    combustion of off-specification used oil for energy recovery in compliance with 35 Ill. Adm.
    Code 739.161 and subject to compliance with all other applicable federal and state permits,
    standards, and requirements and any modifications thereto.
     
    This opinion constitutes the Board’s findings of fact and conclusions of law.
     
    ORDER

     
     
      
    11
     
    1. The Board finds that Lafarge has provided sufficient justification under 35 Ill. Adm.
    Code 720.132 and determines that each of the two raw mill dryers operated by
    Lafarge at its Joppa Portland Cement Manufacturing Plant is a “boiler by
    designation” under 35 Ill. Adm. Code 720.110.
     
    2. As a “boiler by designation,” the two raw mill dryers at Lafarge’s Joppa Portland
    Cement Manufacturing Plant can use off-specification used oil for energy recovery in
    compliance with 35 Ill. Adm. Code 739.161 and subject to compliance with all other
    applicable federal and state permits, standards, and requirements and any subsequent
    modifications thereto.
     
    IT IS SO ORDERED.
     
    Section 41(a) of the Environmental Protection Act provides that final Board orders may
    be appealed directly to the Illinois Appellate Court within 35 days after the Board serves the
    order. 415 ILCS 5/41(a) (2004);
    see also
    35 Ill. Adm. Code 101.300(d)(2), 101.906, 102.706.
    Illinois Supreme Court Rule 335 establishes filing requirements that apply when the Illinois
    Appellate Court, by statute, directly reviews administrative orders. 172 Ill. 2d R. 335. The
    Board’s procedural rules provide that motions for the Board to reconsider or modify its final
    orders may be filed with the Board within 35 days after the order is received. 35 Ill. Adm. Code
    101.520;
    see also
    35 Ill. Adm. Code 101.902, 102.700, 102.702.
     
    I, Dorothy M. Gunn, Clerk of the Illinois Pollution Control Board, certify that the Board
    adopted the above opinion and order on June 1, 2006, by a vote of 4-0.
     
    Dorothy M. Gunn, Clerk
    Illinois Pollution Control Board
     

    Back to top