Ii~LINOISPOLLUTION CONTROL BOARD
    September 29, 1975
    IN THE MATTER OF
    )
    WATER QUALITY AND EFFLUENT
    )
    R 75-2
    STANDARDS AMENDEMENTS,
    )
    COOLING LAKES
    )
    OPINION OF THE BOARD
    (by Mr. Zeitlin):
    On January 22,
    1975,
    this Board received a Proposal for
    Requlatory Amendrnert, with the signatures of more than 200
    citizens attached,
    submitted by the Commonwealth Edison
    Company
    (Edison).
    Designated as R75-2,
    “Cooling Lakes”, the
    Petition asked for revision of the Board’s thermal standards
    as they would apply to a newly defined class of
    “Artificial
    Cooling Lakes”,
    associated with steam-electric generating
    plants.
    The Edison proposal was published in Environmental
    Register No.
    98, on February
    18, 1975
    (Ex.
    2).
    Following
    publication of
    a hearing schedule,
    (Ex.
    3,
    4(a),4(b)),
    public hearings were held in Chicago,
    on May 2,
    1975,
    Springfield
    on May 23,
    1975,
    and again in Chicago on June 23,
    1975.
    After the final public hearing, the Record was held open for
    comment until July 10,
    1975.
    The Board published a Proposed
    Final Draft of th~Regulation on July
    24,
    1975,
    in Environmental
    Register No.
    106.
    Conirnents were again received by the
    Board, through August 12,
    1975.
    The Regulation was adopted
    by the Board on August
    14, 1975.
    BACKGROUND
    The Board inherited the substance of the present water
    quality and effluent standards for thermal pollutants from
    its predecessor,
    the Sanitary Water Board
    (SWB).
    Illinois
    Sanitary Water Board Rules and Regulations SWB-14, Water
    Quality Standards,
    Intrastate Waters Exclusive of Interstate
    Waters
    (1967,
    1968)
    (Although this citation applies generally,
    see also Sanitary Water Board Regulations SWB—8 through
    SWB—l3, and SWB-l5,
    applying water quality and effluent
    standards for thermal discharges as well as other pollutants.)
    18—
    681

    —2—
    Pursuant to Section
    49(c)
    of the Environmental Protection
    Act
    (Act),
    these thermal standards remained in
    effect until
    superceded or other~i.sealtered by the Board.
    Ill.
    Rev.
    Stat.,
    Ch.
    111—1/2,
    flOOl et.
    seq.
    (1973).
    Over the subsequent
    five years that the Board has been in operation,
    it has
    spent considerable time and effort on the question of thermal
    pollution.
    The Board first faced the question in efforts
    to arrive
    at the proper thermal standards for certain individual
    bodies of water:
    Lake Michigan,
    the Mississippi River,
    the
    Wabash River, and the Ohio River.
    In the matter of:
    Thermal
    Standards Lake Michigan, R70—2,
    1 PCB 697
    (1971);
    In the
    matter of Mississippi Thermal Standards,
    R70-16,
    3 PCB 177
    (1971);
    In the matter of Ohio-Wabash Thermal Standards,
    R71-l2,
    2 PCB 563 (l~7l);In the matter of Water Quality
    Standards Revisions,
    R72—4,
    10 PCB 69,
    73—78
    (1973)
    (Des
    Plaines River,
    “5—mile stretch”).
    The first consideration, of course, was the amount of
    heat that an individual discharge could contain before
    causing damage to the receiving stream and its existing
    aquatic biota.1
    (The term “heat”
    is used advisedly here.
    The Regulations and t~eBoard’s prior considerations have
    not strictly concer’ied themselves with the question of heat
    itself, but rather with the question of temperature and its
    effects.)
    In each of the cases cited above,
    the Board attempted
    to arrive at a standard for effluents which would generally
    protect the waters and marine ecology of the state.
    In doing
    so, the Board also considered the benefits to be derived
    from an effluent s~urce, and the cost and practicality of
    eliminating the thermal component from an effluent.
    The
    results are the Bcard’s present effluent aDd water quality
    standards. 2
    1.
    The Board has not heretofore made a fine distinction
    between an existing biota and that which would naturally be
    present were pollutants other than heat not present;
    the
    problem arises where thermal discharges enter an already
    polluted water.
    2.
    PCB Regs,
    Ch
    3.
    In the Matter of Effluent Criteria,
    R70-8; Water Quality Standards Revisions, R7l-14; Water
    Quality Standards Revisions for Intrastate Waters, R71-20,
    3
    PCB 755
    (opinion),
    4 PCB
    5
    (order); The Board’s opinion
    states that,
    “In large part today’s draft is simply a codification
    of existing water qu~1itystandards and associated provisions
    3 PCB at 755;
    see also
    3 PCB at 763
    (re:
    Rule 203(1)).

    —3—
    The Board has also considered the question of thermal
    effluents
    in a series of cases relating to individual dischargers;
    several of these cases directly concern the questions at
    hand:
    steam-electric generating stations and their attendant
    cooling impoundments.3
    In the most relevant of these cases,
    the Board determined that such impoundments, constructed to
    provide condenser cooling for power plants,
    fall into two
    categories:
    1)
    treatment works,
    and
    2)
    protected waters of
    the state.
    The distinction is of sufficient importance to
    have led to our considerations here.
    The distinctic1n, in summary,
    is based upon the way
    a
    cooling—water impoundment is constructed.
    Where artificial
    diking is erected,
    arid water to fill the resulting enclosure
    is largely4 obtained by withdrawal from a nearby natural
    body of water such as a lake or river, the enclosure constitutes
    a treatment works.5
    Commonly known as “perched” or “side—
    channel” lakes,
    tnese bodies of water are, as treatment
    works, exempt from the Board’s water quality standards, and
    discharges into them are not subject to the thermal effluent
    standards.
    3
    Commonwealth ~dison
    v. EPA, PCB 73-359,
    10 PCB 659
    (1974); Commonwealth Edison v.~.EPA, PCB 74-182,
    13 PCB 219
    (1974)
    (extension of variance in~PCB73—359,
    itself an
    extension of variances granted in PCB 70-21 and PCB 72-350);
    considerations
    in two cases are central to this discussion,
    in that the Board there directly dealt with the question of
    thermal effluents
    iflto “cooling lakes”:
    Central Illinois
    Public Service Co.
    v.
    EPA, PCB 73—384,
    11 PCB 677
    (1974);
    Citizens For A Bette: Environment v.
    Commonwealth Edison PCB
    73-245, and Commonwealth Edison v
    EPA, PCB 73-24~ (Consolidated),
    13 PCB 69
    (1974).
    ~PCB 73—38.4 has been appealed to the
    Illinois Appellate Court, Fifth District,
    No. 74—182
    (R.571);
    PCB 73-248
    is also before the Fifth District in case
    No.
    74—
    281.)
    4.
    Natural land contours may form part of the impoundment,
    such that some runoff from adjacent lands enters these
    lakes
    (R.11;
    see also R.97).
    5.
    This definition has previously been given only by
    implication.
    Cf., eases cited,
    note
    3,
    supra.
    18
    683

    —4—
    T~eother tyDe of impoundment, an “artificial cooling
    lake”,
    encompasses the remaining field of cooling water
    enclosures at issue here.
    Generally formed by damming an
    existing watercourse which is itself a protected water of
    the state,
    such artificial cooling lakes remain subject to
    the Board’s water çuality and effluent standards.
    This categorization by the Board was not a painless
    process.
    The utilities contended that since these cooling
    impoundments are initially formed to dispose of waste heat
    from
    a generating station’s condensers,
    it would make no
    sense to deem thei~anything but treatment works, and that
    the imposition of the water quality and effluent standards
    would be improper.7
    The Board, however, held that the
    character of
    a protected water of the state is not changed
    by the simple construction of a dam; where a stream, whether
    continuously or intermittently flowing,
    is dammed to form an
    artificial lake fox cooling purposes,
    it remains a protected
    water of the state.
    Its waters remain subject to the Board’s
    standards. 8
    6.
    For purposes of our discussion here,
    the term “cooling
    lake” should be uri~5erstoodto refer
    to cooling water impoundments
    formed by damming
    a natural stream, continuously or inter-
    mittently flowing.
    Where distinctions are required, the
    shortened terms “dammed lake”
    and “perched lake” will be
    used.
    As will be shown
    later, certain characteristics of the
    two types of impoundments are interchangeable,
    and the
    distinction between the two types will be the subject of a
    definition
    adopted in the accompanying regulation.
    The
    type of impoundment being discussed should be kept clear.
    (See discussion,
    R.55, regarding Edison’s interpretation in
    this regard prior to the Board’s decision in
    PCB 73-248,
    supra)
    7.
    See,
    eg., discussion at R.81:
    “..
    .
    the very concept of
    cooling the lake runs counter,
    really,
    to the Board’s Regulations,
    in the sense that if you are going
    to design something to be
    a cooling facility,
    it shouldn’t have to meet-—except the
    effluent from that sy3tem——
    ...
    temperature restrictions.”
    See
    also
    13 PCB at
    ‘8,
    79.
    8.
    See also, PCB
    73—384, supra,
    11 PCB at 680:
    “The Board
    in Lea~ueof Women Voters_vThorth Shore Sanitary District,
    PCB 71-7,
    12,
    13,
    14, has held that a protected water of the
    state
    (i.e.,
    Lake Michigan) cannot be used as a treatment
    works
    .
    .
    .
    .
    18
    684

    —5--
    Then, however,
    the Board stated that “The evidence
    further showed that not only
    is the lake an improvement over
    the previously existing waters, but
    it is possibly a better
    lake than natural lakes of its size and location.”
    Still
    speaking of Lake Sangchris, the Board stated that,
    “From the
    facts elicited,
    there has been no environmental damage
    proven
    ....
    13 PCB at 80,
    81.
    Based on these facts,
    the Board stated that Edison had
    two forms
    of relief open to it with regard to the thermal
    effluent from Sangcliris:
    1)
    it could seek a Variance from
    the Board’s limitations,
    if it felt that the regulations
    were arbitrary and unreasonable in their application to
    Sangchris; such
    ~.
    Variance would extend from year to year
    pending the development and implementation of a plan to
    bring Sangchris into compliance with existing regulation;
    or
    2)
    Edison could seek a Regulatory change,
    if it felt that
    the rules were then~selvesunreasonable.
    Edison chose the
    latter route.
    In this proceeding, Edison has attempted to show,
    simply,
    that the application of present water quality standards
    in Rule 203(i)
    to artificial cooling lakes
    is unnecessary
    for the protection of the environment.
    PCB Regs,
    Ch.3,
    Rule 203(i)
    (1972).
    Further, Edison has attempted to show
    that because the present limitations are unnecessary,
    it is
    not economically reasonable to apply them to artificial
    cooling lakes.
    To achieve this change, Edison offered the
    following Regulator~iamendment
    (Ex.
    1):
    1.
    (Sec.
    104):
    “Artificial cooling lake” means any
    manmade
    lake which
    is not a treatment works but
    is
    used to cool the water discharged from the condensers
    of a steam—electric generating plant for recirculation
    in substantial part to the condensers.
    2.
    (Sec.
    203(i) (10)):
    The preceding temperature
    provisic~nsshall not apply to discharges into an
    artificial cooling lake.
    3.
    (Sec.
    937(a)(7):
    Where an artificial cooling lake
    is proposed
    to be constructed by damming the flow
    of a non-intermittent stream,
    a statement from the
    Illinois De7artment of Conservation that the lake
    will not diminish the recreational value of the
    area.
    18
    685

    —6—
    During the course of the hearings Edison stipulated to
    ~.
    change in its prooosal,
    to
    the, extent that under its
    Droposed Rule 95~(a)(7)
    the statement to be required from
    bhe Illinois Depa:tment of Conservation
    (Conservation) would
    show that an artificial cooling lake to be created would
    ‘enhance” the recreational value of the area, rather than
    r~ere1y“not diminish” such recreational value
    (R.52).
    Later,
    in a letter to the Board,
    Dr.
    Briceland,
    Director
    f the Illinois Environmental Protection Agency
    (Agency),
    .~fferedthe Board
    an
    alternate wording for the proposed
    T~egu1ation:
    Rule
    104:
    “Artificial cooling lake” means any manmade lake
    which is not a treatment works but is used to cool
    the water discharged from the condensers of a
    steam-etectric generating plant for recirculation
    in substantial part to the condensers.
    Rule
    203 Ci) (10):
    Ill effluents to an artificial cooling
    iake must comply with the applicable
    provisions of th~thermal water quality
    standards as set forth in Rule 203(i),
    c~xceptwhen all of the following require-
    ments are met:
    (aa) All discharges
    from
    the artificial cooling lake to
    other waters of the state comply with the applicable
    provisions of Rule 203(1) (1—4).
    (bb) The heated effluent discharged to the artificial
    cooling lake complies with all other applicable
    provisions of this Chapter, except Rule 203 (1) (1—4).
    (cc)
    At a public hearing, the discharger demonstrates
    to the satisfaction of the Board that the artificial
    cooling lake receiving the heated effluent will be
    an environiientally’ manageable and acceptable
    fishery and recreational facility, and that control
    of the thermal component of the discharger’s
    effluent, beyond that which is proposed in the
    demonstration, would be technologically infeasible
    or economically unreasonable.
    (dd) Upon approval of such demonstration by the Board,
    the Board ~hal1 establish alternate thermal effluent
    standards to be applied to the discharge to the
    artificial cooling lake.

    —7—
    Dr. Briceland’s proposed alternate wording was published by
    the Board in Environmental Register No.
    104.
    As the hearings progressed Dr. Briceland offered a
    final proposal in the matter, incorporated into the record
    as Exhibit 32:
    Rule 104:
    “Artificial cooling lake” means any manmade lake
    which is not a treatment works but
    is used to cool
    the water discharged from the condensers of a
    steam—elec~tricgenerating plant for recirculation
    in substantial part to the condensers.
    Rule 203 (1) (10):
    All effluents to an artificial cooling
    lake must comply with the applicable
    provisions of the thermal water quality
    standards as set forth in Rule 203(i),
    except when all of the following requirements
    are met:
    (aa) All discharges from the artificial cooling lake to
    other waters of the state comply with the applicable
    provisions of Rule 203(i) (1—4)
    (bb)
    The heated effluent discharged to the artificial
    cooling lake complies with all other applicable
    provisions of this Chapter, except Rule 203(i) (1-4).
    (cc) At a public hearing, the discharger demonstrates
    to the satisfaction of the Board that the artificial
    cooling lake receiving the ‘heated effluent will be
    operated i~1an environmentally acceptable manner
    so as to provide conditions capable of supporting
    an acceptable fishery,
    and that control of the
    thermal co~~nponentof the discharger’s effluent by
    means of an artificial cooling lake represents the
    most technologically feasible and economically
    reasonable means of thermal control.
    The demonstration
    documentation shall set forth the specific maximum
    thermal limits proposed by the discharger.
    (dd)
    The demonstration required in Rule 203(i) (10) Ccc)
    may take the form of those applicable portions of
    the final environmental assessments used in the
    preparation of the final environmental impact
    statemenL,
    that addresses the requirements of Rule
    203(i) (10) ,cc)
    (ee) Upon approval of such demonstration by the Board,
    the Board shall designate the proposed thermal
    effluent limits set forth in the demonstration
    as
    the ther~ialstandards to be applied to the discharge
    to that artificial cooling lake.
    18
    687

    —8—
    (ff) Any discha:~gerto an artificial cooling lake who
    has been granted a variance from one or more of
    the provisions of the thermal standards
    Rule
    203(i) (1—4)
    prior to adoption of this Rule,
    shall
    be exempted from the requirements of Rule 203(i) (10) (cc).
    The alternate thermal limitations
    for that discharge
    shall be the conditions set forth in the Illinois
    Pollution Control Board Order on the variance.
    NEED FOR CHANGE
    The hearings and the record generated in this matter,
    including the extens~veexhibits, conclusively demonstrated
    that some change is needed in the present thermal standards
    as they apply
    to artificial cooling lakes.
    This conclusion
    is mandated by our finding of the following facts:
    1.
    No substantial environmental harm has resulted at
    several existing cooling impoundments9 where the thermal
    effluents of the accompanying generating stations violate
    existing Board thermal standards.
    2.
    The cost of providing alternate methods
    tc cool the
    condenser coolant discharges from steam—electric generating
    plants associated with cooling lakes can be expensive.
    It should be noted that these findings are essentially
    similar to our findings in the earlier Edison case,
    PCB 73-
    248.
    This is not, however, mere reiteration of facts already
    found by the Board.
    The findings in the earlier Edison case
    were limited and specific; they applied solely to an individual
    artificial cooling lake,
    Edison’s Lake Sangchris.
    The
    proceeding at hand, however, has
    a much broader scope; our
    decision here will affect all presently existing artificial
    cooling lakes, and all those to be built in Illinois in the
    futureJ°
    The difference is significant.
    9.
    Both dammed and perched lakes are considered here,
    although the regulations to be adopted will affect only the
    former.
    10.
    Existing artificial cooling lakes
    in Illinois are: Lake
    Sangchris
    (Commonwealth Edison); Lake Springfield
    (City of
    Springfield); Lake of Egypt
    (SIPC); Lake Coffeen
    (CIPS).
    Presently planned artificial cooling lakes are: Lake Clinton
    (Illinois Power), Lake Newton
    (CIPS).
    18
    688

    —9—
    Nor, howeve—,are these findings to be read as a commitment
    by the Board
    to the use of artificial cooling lakes
    in all
    situations where cooling is to be accomplished in conjunction
    with a steam-electric generating station.
    While existing
    lakes have generaL’y proven environmentally acceptable, and
    the cost of alterna:e or supplemental cooling has been shown
    to be high, the present record is not conclusive as to the
    advisability of using or not using artificial cooling lakes
    in every situation.
    Whether an artificial cooling lake or
    some alternate cooling technology is to be used in
    a specific
    instance is dependent on many factors,
    and must be shown on
    a case—by-case ba3is.
    For clarity, we will consider first the costs associated
    with the various technologies for cooling at electric generating
    stations, with a brief description of the way
    in which they
    work.
    We will then discuss the results of the thermal input
    from present steam-electric generating plants on the aquatic
    biota at existing cooling impoundments.
    COOLING TECHNOLOGIES
    The present state of the art allows several engineering
    choices
    in
    the design of cooling facilities for steam-
    electric generating plants.
    Such plants generate steam to
    drive electric generaLing units, after which the steam is
    condensed back into water for re—use.
    To achieve that
    condensation,
    the used steam is passed through “condensers”,
    which are water—cooled heat exchangers.
    The water used to
    cool the condensers,
    (a considerably greater quantity than
    that used as steam to run the generators), must then in turn
    be either cooled or ‘lisposed of to make way for new, cooler
    water to absorb
    the
    heat conducted through the condensers
    (eg.,
    R.9).
    Once-Through Cooling
    One common method of accomplishing condenser cooling is
    “once—through” cooling, whereby water is taken from a
    natural water body,
    (ie,
    a lake or river), passed through the
    condensers, and then returned, untreated and unc~ooled’, to
    that or some other body of water. Since
    it requires -a large
    volume of available cooling water, this method is used
    largely on major water bodies,
    such as Lake Nichi~anie.
    Zion Station)
    or the Mississippi River
    (ie.,
    Quad Cities
    Station).
    This method of cooling is unimportant to our
    discussion here
    (R 10).
    18
    689

    —10—
    Mechanical Draft Coding Towers
    Water may alsc be cooled through the use of mechanical
    or natural draft cooling towers.
    Mechanical draft cooling
    towers, more commcn than the natural—draft variety in the
    United States,
    (R.353), dissipate waste heat to the atmosphere
    through the process of evaporation, with little or no loss
    though conduction or radiation, and a resultant loss of
    efficiency, whereas 40—50
    of cooling on lakes
    is through
    radiation
    (R.ll5.l22)
    By way of example,
    the evidence in this matter indicated
    that the use of mechanical draft cooling towers at Lake
    Sangchri~would
    in~.rolveapproximately $17.6 million.
    Costs
    incurred from the naed of such towers for auxiliary power
    and from the loss oi~generating capacity,
    as well as other
    factors, would amount to approximately $6.4 million, figured
    as the equivalent of present investment cost.
    After
    $1.2
    million in operating and maintenance costs for these towers
    is added in,
    the evidence showed that the backfitting of
    mechanical draft cooling towers at Kincaid station,
    (Lake
    Sangchris), would amount
    to approximately $25 million
    (Ex.
    6(N),
    testimony of Michael J.
    Groppi in PCB 73-248).
    Exhibit 27, submitted by Central Illinois Public Service
    Company,
    shows similar breakdowns for the costs of mechanical
    draft cooling towers at that Company’s Coffeen and Newton
    artificial cooling lakes.
    Although extensively questioned
    on cross—examination, the figures nonetheless show that the
    actual and equivalent
    (present value of lost generating
    capacity at the stations, maintenance operation,
    fuel,
    etc.,)
    costs would be approximately $20 million for Coffeen
    Station and Lake,
    and $18 million for Newton Station and
    Lake.
    Figures were also presented for Illinois Power Company’s
    proposed Clinton Nuclear Power Station.
    Figures presented
    indicated a cost for “once—through” cooling towers of $29.5
    million,
    a figure termed “capital cost” over the 30-year
    life of the Station
    CConiment C, attachment 1, p.2; Letter,
    April
    14,
    1975,
    Illinois Power to U.S. EPA).
    18
    690

    —11—
    It should also be noted that these costs do not necessarily
    replace the cost of building and maintaining an artificial
    cooling lake or its equivalent,
    even for new stations where
    the cooling impoundment has not yet been built.
    The testimony
    of several witnesses,
    as well
    as several of the exhibits,
    showed that the
    ‘.ise of mechanical draft cooling towers would
    still,
    (in the ab3ence of a large natural body of water),
    require a large
    impoundment to supply make—up water, due to
    the increased consumptive water use of such towers.
    One
    witness stated emphatically that, to account for the 50-100
    year drought conditins for which power station design must
    provide,
    a make—up water impoundment at least as large as an
    artificial cooling lake for the same facility must be built
    (R.126;
    see also R.32, 378)
    Natural Draft Cooling Towers
    Natural drafi~wet cooling tower costs were also provided
    for Lake Sangchris.
    Not presently used in Illinois,
    these
    towers,
    (the large hyperbolic structures seen in the literature),
    are much less used in the United States than in Europe,
    although some examples are available
    (R.354).
    Exhibit
    6(N)
    shows
    an estimate that Kincaid station would require a
    single hyperbolic tower 460 feet in diameter and 500 feet
    high, with a cost,
    ~figured in the same manner as for mechanical
    draft towers),
    of approximately $31 million.
    Trimming Towers
    A further type of cooling tower,
    a “trimming tower” was
    also discussed for Coffeen and Newton Stations.
    Without
    providing a breakdown,
    the conclusion was made that such
    towers, designed
    SUCh
    that after discharge to a cooling lake
    the effluent could meet a 5°F.temperature rise at the edge
    of the mixing zone,
    (ie., not a “closed cycle” system),
    would
    be less costly than a conventional closed cycle mechanical
    draft cooling tower system.
    Such towers would require the
    minimum of additional piping and additional power.
    However,
    this concept was dismissed by CIPS when it concluded that
    such towers would not work;
    “wet bulb” temperatures in the
    area would be too high to allow full and efficient performance
    for perhaps six mi’nths of the year
    (Ex.
    27,
    p.3).
    18
    —691

    —12—
    Dry Cooling Towe:s
    A final type of cooling covered in the testimony and
    exhibits was the
    “thy” cooling tower.
    Such towers do not
    achieve condenser water cooling through evaporation, and
    instead channel th?- water through finned radiators cooled by
    air passage over the radiator surface.
    It was stated
    (Ex.
    5,
    p.3) that such towers are much lower in efficiency
    than wet towers,
    since it is not possible to make use of
    evaporatve cooling.
    It was also alleged that the development
    of such towers
    is still in an “infancy” stage,
    and that they
    are not yet commercially viable
    (R. 114).
    (A hybrid tower,
    the “wet-dry” was mentioned only
    (Ex.
    5,
    p.4)
    as being
    developed to control the problem of plume drift with wet
    towers).
    Spray Canals
    Similarly,
    spray canals form an expensive alternative
    when compared to a:~tificialcooling lakes used alone.
    As
    was the case wit1~towers,
    the Board was presented with
    considerable data on the costs
    of such spray canals.
    A spray canal has been proposed by Illinois Power for
    its proposed Clinton Station and Lake, utilizing 232 total
    spray modules in a 31 mile long discharge canal. Cf.
    Illinois
    Power Co.v.
    EPA, R75-3l
    (July 31,
    1975).
    Illinois
    Power st~èsthe cost of the proposed system as a “capital
    cost of $11,522,800
    (cash flow through Unit #2 completion
    Ed:
    1983))
    and
    ...
    a total revenue requirement of $34,524,800
    to cover all capital, operating and maintenance costs over
    the assumed economic life of the generating units
    (30 years)”
    (Comment C,
    Exhibit
    1, p.2).
    A hypothetical closed cycle spray canal cooling system
    to replace Lake ~angchris for cooling at Edison’s Kincaid
    Station would have 130 spray modules in a 7,600
    ft.
    canal.
    Although the costs estimated for such a system at Kincaid
    may not be applicable generally, due to the fact that back-
    fit installation there would require extensive reconstruction,
    Edison estimated a total cost of approximately $38.4 million.
    18—
    692

    —13—
    IMPOUNDMENTS TO (OMPLY WITH GENERAL REGULATIONS
    The costs associated with the design and construction
    of a cooling lake
    (or any artificial impoundment) which
    would be capable of meeting the general Board therrn~jstandards
    must also be considered.
    Present Board Regulations-i-
    allow
    temperature rises of 5°F.above ambient, and set maximum
    water quality temperature standards for various waters and
    classes of waters.
    The testimony presented at the hearing
    indicated that present cooling lake technology12 would not,
    as applied to an existing or planned standard cooling lake,
    allow for compliance with Board standards.
    11.
    The principal ~oard Regulations controlling thermal
    pollution are contained in Rule 203(i) of Chapter
    2:
    Water
    Pollution.
    The Rule applies to “General Use” waters.
    Ch.
    3, Rule 205(f)
    sets
    a thermal water quality standard of
    93°F,not to be exceeded more than
    5
    of the time,
    for
    Restricted Use
    (Secondary Contact and Indigenous Acquatic
    Life Waters, Rule 302)
    Waters.
    100°F.is never
    to be exceeded.
    Rule 402,
    in Part IV:
    Effluent Standards, prohibits
    any effluent which will result
    in a violation of any water
    quality standard.
    Lake Michigan temperature standards are contained in
    Rule 206(e).
    It should be noted, however, that under Rule 201,
    Mixing Zones,
    a discharger is given an area as would be
    contained in a circLe with
    a radius of 600 feet within which
    the water quality standards may be violated.
    Were the case
    otherwise,
    all effiuents would have to meet water quality
    standards.
    (Cf,
    Ohi..o-Wabash
    Thermal Standards,
    supra,
    2
    PCB at 565,
    (citing SWB
    9 and SWB
    10, limiting mixing
    to the
    area
    “inirnediately
    adjacent to outfalls.”
    The basis
    of a
    600’-radius rnixin~i zone is questioned at
    2 PCB 566).
    An important decision of the Board, Commonwealth
    Edison v. EPA. PCB 73—359,
    10 PCB 659,
    662
    (1974), found
    that mixing zones are limited only by the area contained
    within the
    600’ circle, and riot by the shape of the circle;
    thus,
    the
    26 acre mixing zone may be
    “cigar shaped” if
    necessary.
    (Note,
    ho”iever, the limitations on mixing zones
    in Ch.
    3, Rules 201(o)
    and
    (b)).
    See also, Water Pollution Amendment Regulations,
    R73-l,
    11
    Pc~T35,
    140—41
    (1974).
    12.
    Although not conclusive,
    testimony offered by Edison
    indicated that cooling lakes tend to be roughly proportional
    in
    size,
    as betwecn generating plant size ~nd lake surface
    area, resulting
    in
    roughly equivalent heat loading on cooling
    lake surfaces
    (R.124).
    18
    693

    —14—
    The “cooling”~-3properties of an artificial cooling
    lake, testimony sho~ed,are largely dependent on two factors:
    the volume of a lake,
    and its depth
    (R.527).
    In other
    words,
    there must he a large volume of water with which
    mixing can take place before water quality standards can be
    met at the edge of a
    26 acre14 mixing zone.
    Such mixing
    allows heat to be dissipated from the effluent into adjacent
    waters through conduction;
    while this process does not
    actually remove the heat from the body of water in question,
    it does lower the temperature of the effluent fairly quickly.
    Since the adverse effects which Board regulations are designed
    to prevent are the result of temperatures in waters, rather
    than the total amount of heat contained in a water body,
    such mixing is effective.
    Testimony at the hearing showed that it is simply not
    practical to perfor~nsuch mixing on cooling lakes that
    either now exist or would be likely in Illinois.15
    In the
    opinion of one witness,
    a lake of the size of one of the
    Great
    Lakes would be required before the effluent from a
    current large electric generating station would meet the
    present Board standards at the edge of the allowed mixing
    zone
    (R.528,108).lh
    While the Board is not convinced that one of the Great
    Lakes would actually be required to meet its present standards,
    it is fairly plain that cooling lakes designed to meet
    present standards without supplemental cooling,
    (ie, towers
    or spray canals), would be far more expensive than has
    previously been
    t1’e case.
    Present lake design simply does
    not provide a sufficient body of water for the required
    mixing;
    to provide sufficient water for such mixing would
    require a much larger lake, with the additional expense of
    the additional land to be inundated.
    13.
    “cooling” here being used in the sense of temperature
    reduction,
    as opposed to actual heat loss
    (cf.
    R.l00,
    104).
    14.
    See, PCB 73—359,
    supra,
    10 PCB 659 at 661.
    By way of
    contr~E,discharge of 2,140 CFS at 13.5°F. Delta-T
    (change
    in temperature) requires a 500 acre mixing zone before the
    5°F. Delta T requirement of Rule 203(i)
    is met
    (R.l7).
    15.
    Sangchris,
    for example, has no flowing water such as
    would be used for mixing with a large river
    (R.l02).
    Sangchris
    cost in excess of $30 million for the construction of the
    enclosure alone
    (R.15).
    The lake has approximately 2700
    acres of surface area
    (R.3l)
    .
    Only 46 lake sites such as
    Sangchris, with a potential of more than 2,000 acres surface
    area, exist in Illinois, and only
    4 of those are located in
    Northern Illinois
    (R.675,
    695,
    698)
    16.
    Ex.
    5, pp I-li
    1-2 show new units varying from 200 to
    1175 megawatts, with only
    2 examples
    (of
    17) below 500
    megawatts.
    18
    694

    —15—
    LACK
    OF ENVIRONMENTAL HARM
    As was noted,
    in the quotations from PCB 73-248,
    relating to the lack of evidence of environmental harm at
    Lake Sangchris,
    the Board was impressed by the facts presented
    with relation to that Lake.
    However, more information has
    been developed since the time of the Board’s findings there,
    which must necessarily be discussed here;
    it must be remembered
    that the Regulation~proposed here would have much wider
    effect than could be justified on only the evidence presented
    in that case.
    The Regulations proposed, in both the Edison
    and Agency versions, would be effective as against all
    artificial cooling lakes.
    For that reason, we must examine
    the evidence presented regarding Lake Sangchrisl7 in the
    light of its general applicability to cooling lakes, and we
    must examine the data available regarding other similar
    lakes
    to determine whether the results noted
    at Sangchris
    are borne out in other locales.
    Environmental harm,
    as discussed here, refers
    to a
    range of potential carnage which might be envisioned as
    resulting from the construction of an artificial cooling
    lake.
    A partial listing of the factors examined in determining
    the lack of environmental harm is the effect of the thermal
    effluent into an artificial cooling lake on:
    a.
    water quality
    b.
    Phytoplankton, Zooplankton
    c.
    Benthos
    d.
    Macrophytes, Periphyton
    e.
    Fish
    f.
    Wildfowl, Aquatic Mammals
    g.
    Other uses
    It should be noted that some of the data used
    in
    our
    consideration is obt.ained from “perched” lakes which,
    as
    previously discussed would not be affected by the regulations
    proposed here.
    Such lakes are, however, sufficiently similar
    to dammed “artificial cooling lakes” to allow the use
    of
    data gathered from them.
    In effect,
    since they are
    unregulated,
    the results of their unregulated thermal discharges on the
    environment may be profitably used to show the effects of
    thermal discharges on the biota of the unregulated lakes,
    and allow extrapolation of that data
    for application to the
    “artificial cooling lakes”.
    17.
    It should be noted that Edison bore the brunt of the
    evidentiary burden
    in this proceeding, and that much of the
    data now available to the Board resultantly relates to
    Edison’s Lake Sangchris.
    The Board commends Edison for both
    the completeness ard comprehensiveness of its presentation
    in
    this matter.
    18
    695

    —16—
    A.
    Water Quality
    Edison’s 316(a) demonstration18 for Sangchris contains
    considerable data on water quality
    (Ex.
    6).
    In addition,
    Edison commissioned the Illinois State Natural History
    Survey to prepare a long—term
    (4 year)
    study on conditions
    in Lake Sangchris.
    Ex.
    6(I)
    is the first annual report on
    that study,
    and Ex.
    7 is a further semi-annual report covering
    through February,
    3975.
    Earlier data on the lake was compiled in a study by
    Limnetics,
    Inc., which prepared a limnological survey of
    Sangchris submitted to Edison in 1972
    (Ex.
    6(D)).
    In essence,
    the information available from these sources does not show
    any degradation of water quality in Sangchris which is
    attributable to the thermal components of Edison’s Kincaid
    Station effluent.
    The 1972 Limnetics,
    Inc.
    study showed that Lake Sangchris,
    with a daily discharge averaging 700 million gallons having
    a Delta T of 13.5°F. (into a lake with a total volume of
    10.7 billion gallons,
    7.7 billion of which are actually in
    the cooling loop), has generally good water quality.
    The
    only difficulty found was turbidity.
    Fine clay sediments
    entering the lake
    i”. runoff are held in suspension by plant
    operations
    (Ex.
    6 i.E),
    iv).
    Tests run to show levels for
    about
    30 parametero
    (Ex.
    6(D),
    p.84,
    Tables F—i to F-36,
    Figures E-l to E-15),
    revealed little of any interest.
    Although fairly high nitrogen levels were found, which might
    support algal blooms, low phosphorous levels in the lake
    would limit algal productivity;
    in addition, algal production
    is light limited in
    trie lake
    (R.
    308,
    293) due to the high
    levels of turbidity and suspended solids.
    Later data for Sangchris,
    (the Natural History Survey
    study results), show a continuing high water quality in
    Sangchris.
    The first annual report of that study,
    (Ex.
    6(I)),
    covering through September 4,
    1974,
    presents’ a considerable
    mass of data on water quality parameters.
    The report notes
    that nitrogen is readily leached from soil,
    and concentration
    increases during winter and spring are normal in lakes
    surrounded by agricultural lands
    (Ex. 6(I),
    p.
    1.3).
    Mercury
    concentrations were rarely at the detectable limit, and
    never beyond the limits set by Board Regulations
    (Id.).
    It
    18.
    A “316(a) demonstration” relates to application by a
    discharger to the U.S. Environmental Protection Agency for
    an “alternate thermal standard” under §316(a)
    of the Federal
    Water Pollution Control Act Amendments of 1972, P.L.
    92-500,
    70 stat.
    498,
    84 stat.
    91,
    33 U.S.C.
    1251 et.
    seq.
    (1972)
    18
    696

    —17—
    was also noted that bacteriological concentrations
    (especially
    fecal coliform) ~re affected primarily by climate rather
    than any other
    fact.or;
    the source of the coliform is the
    surrounding land, ard provides input to the lake only when
    the ground is not frozen.
    (Id.,
    p.
    1.5).
    The Sangchris
    study to date,
    (Ex.
    6(I) and 7), has shown that deeper
    portions of the lake,
    little affected by the thermal component,
    may at times violate Board dissolved oxygen
    (DO)
    standards.
    It is shown, however, that this
    is the result of natural
    phenomena rather than the thermal input.
    No violations have
    occurred thus fax in the second year of the study
    CR.
    294).
    The mass of data available for Lake Sangchris is made
    more useful by a Comparative Limnological Literature Survey
    for Sangchris Lake,
    conducted in 1973 by the Natural History
    Survey.
    Various data for five lakes, with and without
    thermal input, were collected.
    (Ex.
    6J.)
    The lakes studied
    were:
    Lake Decatur, Evergreen Lake, Lake Lou Yaeger,
    Lake
    Springfield and Lake Taylorville.
    All these lakes are
    located in centrai. Illinois, and several are very similar to
    Lake Sangchris.
    .~1thoughthere ‘were some problems with the
    comparative study due to lack of information,
    it did indicate
    that Lake Sangchris does not differ significantly from the
    other lakes in any of the water quality parameters important
    to our consideration.
    Even the turbidity of Lake Sangchris,
    which was inferred
    by testimony to be a result of plant operations at Kincaid
    Station, was not particularly high
    (R. 293).
    In fact,
    Sangchris and Springfield,
    the only two lakes
    in the study with
    a
    thermal component from power stations, had the lowest
    turbidity readings of those lakes considered
    (Ex.
    6(J),
    P.
    91,
    Tables VIII-3,
    VIIi-4).
    Sangchris did, of course,
    have
    significantly. different temperature readings
    (Id.,
    P.
    101,
    Fig. VIII-6).
    DO levels for Sangchris, Evergreen and Springfield
    were essentially similar, while Decatur had higher readings
    at most depths.
    Esse~~tia1ly,the chemical and physical
    parameters would appear
    to be more dependent on the watershed
    providing a lake’s water, and on the a~eof the lake,
    than
    on any other factor
    (Id.,
    pp.
    91,80,7.).
    Thermal discharges from the Daliman and Lakeside generating
    plants of the City of Springfield affect approximately one—
    fifth of the waters in the North Basin of Lake Springfield
    daily.
    The only water quality anomaly present in the two
    studies submitted
    Thich might be seen to be a result of the
    thermal component is
    a high nitrate level
    (Ex.
    24, pp.
    6,
    37;
    Ex.
    25, pp XII-20,21).
    This
    does not, however, appear
    to be causing problems of plankton growth,
    as the thermal
    effluents from Lakeside and Dallman Stations are stressing
    the plankton communities
    (Ex. 25,p.XII—30)
    .
    While this
    problem is not serious,
    it needs further study.
    18
    697

    —18—
    B.
    Phytoplankton,
    Zooplankton
    As noted above,
    the Betz Study
    (Ex.
    25, p.XII-30),
    reached the conclusion that the heated effluents from Lakeside
    and Dallman stressed the plankton communities in Lake Springfield.
    The earlier Burns/Swanson Study, however,
    (Ex.
    24,
    p.
    50),
    reached the conclusion that Lake Springfield supports a
    relatively good diversity of plankton species, both phytoplankton
    and zooplankton.
    Ii
    stated that a dominance of the diatoms
    suggests good overall ecological conditions at Lake Springfield.
    As with Lake Sangchris,
    small plankton speciman sizes were
    attributed to phytopLankton feeders, and possibly some
    temperature induced stress
    (id,
    p.
    52)
    The first annual report on Lake Sangchris,
    (Ex. (6)1,
    p.
    2.17),
    showed as a conclusion a lack of overall thermal effect
    on zooplankton or phytoplankton.
    Sangchris was described as
    a moderately eutrophic lake with a typical phytoplankton
    community.
    It was aso
    noted, that a reduction in size,
    (cell and colony sizes were consistently observed near the
    lower limits described for any given species), is
    a well—
    documented response to warm water conditions.
    The semi-
    annual report of the Natural History Survey Study,
    (Ex.
    7),
    however,
    showed that during the second year of the study,
    when plant operations were at a lower level, population
    trends at each of the sampling stations were similar to
    those observed during the previous year
    (Ex.
    7.,
    p.
    2.1).
    From all the data available~it would appear that thermal
    inputs to cooling lakes result
    in some localized effect on
    plankton communities near station outfalls.
    These effects
    do not seem serious and have not been shown to upset the
    normal productivity cycles for these lakes.
    C.
    Benthos
    There was some indication,
    (Ex.
    16, Report No.
    3),
    that
    condenser passage at Baldwin
    Lake has proved harmful to
    certain benthic organisms.
    It was also felt that fish
    predation could account for the same population decline
    (id.
    p.
    7).
    Later studies also indicated that low standing
    benthos crops may be the result of poor bottom compositions,
    primarily of clayey, heterogeneous sediments.
    It was doubted
    that high temperature caused the sparseness of bottom fauna,
    due to sampling station distributions
    (Ex.
    16, Report No.
    6,
    p.2).
    18
    698

    —19—
    Early studies at Lake Sangchris indicated some difficulties
    with the benthic population.
    This problem apparently was
    corrected in later years of operation.
    (See
    Infra,
    pp
    30)
    0.
    Macrophytes, Periphyton
    An extensive study of aquatic vegetation at Lake Baldwin,
    (Ex.
    17), was unable to determine what effect the thermal
    discharge had on the aquatic plant community.
    It was feared
    that too-extensive vegetation growth could interfere with
    the cooling properties of the lake, and possibly result
    in
    higher temperatuxe discharges.
    A study by WAPORA,
    Inc.,
    submitted March 25,
    1975,
    (Id.),
    studied the effects of
    herbicides on the lake
    as a macrophyte control measure.
    In
    essence, no thermal effect could be found.
    The Limnetics study at Sangchris
    (Ex.
    6(D),
    §
    5.3.6),
    describes normal maorophyte growth.
    Similarly,
    the periphyton,
    (shoreline growth), was found to be normal, with considerable
    growth
    (id, p.96).
    E.
    Fish
    Discussion of the fish community in cooling impoundments,
    (both dammed and diked), occupied much of the record in this
    matter.
    Of the fish populations discussed, game fish received
    the greatest amount of attention
    (eg., R.232—288).
    The record clearly indicates that several cooling
    impoundments support viable game fisheries.
    This was obviously
    true of Lake Sangchris, whose fishing virtues were praised
    by many of the witnesses.
    Fishermen representing various
    organizations,
    (ie., the Bass Anglers Sportsmen’s Society,
    the National Wildlife Association,
    the Bass Casting Association,
    and the Illinois Wildlife Federation),
    stated unequivocally
    that Lake Sangchris provides some of the best fishing in
    Illinois.
    Perhaps more importantly, they stated that the
    thermal discharge from Kincaid Station makes possible
    a
    year-round fishery,. providing winter recreation of
    a type
    not otherwise available in Illinois.
    Although this latter
    fact seemed of part~cu1arimportance to the fishermen
    witnesses,
    it was also stated that Kincaid’s thermal effluent
    makes possible year—around habitation and growth by many
    warm-water species of fish.
    Although cross—examination left
    open
    the possibility that the thermal component may eliminate
    some species which would otherwise habitate the lake,
    (R.
    452),
    this issue was not heavily dwelled upon.
    Instead,
    testimony centerc~’don the unique recreational opportunities afforded
    by Lake Sangchris.
    18
    699

    —20—
    It is apparent that Lake Sangchris
    is indeed widely
    used by Illinois residents.
    A creel census, prepared by the
    Illinois Department of Conservation,
    (Ex.
    6(L),
    indicated
    that 1973-74 usage at Lake Sangchris constituted 42,235
    total fishermen days, with each angler spending an average
    of 3.55 hours per year.
    It was projected,
    (Id.), that over
    31,000 blue gill ~ould be caught,
    and over 20,000 large
    mouth bass;
    crappy and channel catfish would account for
    12,964 and 15,006 catches, respectively. Approximately
    24,000 fish were caught during the “unique winter fishery”
    CR.
    679).
    Although Lake Springfield has been less frequently
    sampled, 1972 population analyses showed good fish growth
    rate, condition and reproduction in all game fish species
    samples.
    It appeaxs that this condition has not always been
    true of that Lake,
    however; Department of Conservation
    testimony indicated that fish condition
    at Lake Springfield
    has “changed dramatically”
    (R.
    680). Conditions now are
    thought to be good,
    and fluctuations in fish condition
    cannot be attributed to the thermal component from the City
    of Springfield’s generating stations
    CR.
    684).
    Although no
    data was available,
    the Department of Conservation felt that
    angler usage of Lake Springfield is quite extensive.
    (See also
    R.
    232—285;
    148—154;
    679;
    271;
    (Baldwin and other lakes).)
    In predicting conditions on Lake Clinton,
    Illinois
    Power cited extensi~relyfrom experience on Lake Sangchris.
    Although temperatures at Lake Clinton would be lower than
    those experienced at Lake Sangchris,
    it was predicted that
    conditions on Clinton will not vary significantly from those
    observed at Sangchris
    (eq.
    Ex.
    18,
    §
    6 p.37).
    It is predicted
    that Clinton will provide the same type of year-round fishery.
    Several specific problems, possibly attributable to the
    thermal component in Lake Sangchris, were discussed during
    the hearings in Chic.igo and Springfield.
    (For example,
    it
    was noted that in 3ome thermal plumes from electric generating
    stations, super—saturation of air in the heated water causes
    gas bubble diseases in fish
    (R.481).
    This has not been
    observed at Lake Sangchris.)
    It was pointed out,
    CR.
    466),
    that fish move away from the thermal plume during some
    seasons; while ther~is still some question as
    to whether
    this indicates
    a harmful but sub—lethal effect,
    such harm
    has not been shown.
    Although some species in Sangchris
    have,
    at times,
    s~-iownsigns of poor condition
    (i.e., weight-
    to—length ratio),
    this fact is offset by population densities
    within those species
    CEx.
    6(1);
    R.
    482).
    (See infra p.29).
    18
    700

    —21—
    Many other qi~estionswere also raised at these hearings
    with regard to the possible sublethal effects of heat on
    various fish specits.
    These include problems with reproduction,
    habitat crowding, species imbalance,
    species elimination,
    and fish diseases j~j.R.706).
    Many of these questions,
    however, remain academic, and the reader is referred to the
    record for a complete
    -
    and particularly in the Exhibits
    -
    thorough examination of these matters.
    The fact re~nainsthat the cooling impoundments examined
    in this proceedi.~gall support large fish populations. More
    importantly, the record shows that the existence of these
    fish populations may well indicate a generally healthy
    condition in the suiject lakes.
    Game fish occur at the top
    of a complex, and finely balanced, food chain and ecosystem
    (eg.
    Ex.
    6(D), p.12’~). A break in the ecology or food chain
    in a cooling lake might well prohibit the flourishing
    fisheries now found.
    This fact seems borne out by the references cited in
    the Exhibits.
    One,
    (Bush,
    et al., Potential Effects of Thermal
    Discharges on Aquatic Systems,
    8 Environmental Science and
    Technology 561
    (June,
    1974)), even suggests that the effects
    of thermal effluents on fresh water fish communities will
    suffice as a guide.Line for the protection of both fish and
    invertebrates.
    Due to the size and diversity of the biota
    to be protected,
    and the fact that thermal limitations are
    not known for all species,
    the effects on fish may well be
    our best guide.
    Certainly, the Board cannot hope in a
    proceeding of this
    iature,
    to completely resolve issues
    which apparently remain contested in the scientific community.
    But, based on the record here, we may accept the thermal
    effects on fish a~one indication of general conditions in
    the biota.
    This does not
    mean that we will blindly accept the
    existence of a fishery as our only criteria.
    Sufficient
    questions have arisen to show that many possible problems do
    exist, at many levei,s in the biota, which may be the result
    of thermal effluents.
    The record certainly indicates that,
    with fish as well ~.sother aquatic animals and plants, very
    high temperatures may produce distinct harm to the environment.
    Thus, while we dc not accept the contention that the existence
    of a fishery is the sole criteria of compatability between
    the ecosystem and additional heat loadings, the existence of
    a viable fishery must be given considerable weight.
    18
    701

    —22—
    F.
    Wildfowl,
    etc.
    There was considerable testimony,
    CR.
    305), to the
    effect that wildfowl usage of Lake Sangchris has been normal.
    It was asked at some length whether the migratory feeding,
    or other habits of wildfowl may be affected by the addition
    of heat to bodies of water used by those birds.
    The evidence
    shows that these effects,
    if they do exist, are minimal.
    Further, extensive predictive data on wildfowl usage for the
    proposed Clinton Lake has indicated that wildfowl usage of
    cooling lakes will not constitute a future problem, whether
    through the addition of nutrient or the introduction of
    parasites
    (eg.
    Ex.
    18,
    § 6.3.2.3.2,
    p.
    6—42).
    G.
    Other Considerations
    It has been argued that the function of the Board in
    protecting the environment does not allow for the consideration
    of other factors in reaching our decisions on environmental
    matters
    (eg. Submission of U.S. EPA, letter of July
    9,
    1975;
    see also,
    Ex.
    20, p.4; R.365).
    We are not convinced that
    EFiis
    is the case.
    The General ~ssemb1y made it quite clear in the Environmental
    Protection Act that there are many factors to be considered
    by the Board in reaching our decisions.
    Section 27 of the
    Act sets out a listing of factors
    to be considered,
    several
    of which are important here insofar as they require our
    consideration of the benefit of artificial cooling lakes,
    to
    both the utility company owners of such lakes and to the
    public at large.
    These factors must then be balanced against
    either the harm,
    cr the possibility of harm, which may
    result from our decision.
    It would appear that,
    within limits
    CR.
    481),
    the
    addition of heat from a steam-electric generating plant
    actually aids ir~the growth and development of gamefish in
    artificial cooling lakes
    (eg.
    R. 462).
    While the continued
    growth of fish and other aquatic organisms during winter is
    unquestionably not in the natural order of things for
    Illinois lakes;
    it would appear that this phenomena none-
    theless contributes to the recreational value of an artificial
    cooling lake.
    Further,
    it would appear that the presence of
    such
    a fishery as
    is evidently produced by the thermal
    effluent may also be a good indication of,the general environ-
    mental quality and acceptability of an artificial cooling
    lake
    (supra,
    p.
    2.~.). Apparently,
    then,
    the existence of this
    type of recreational use is compatible with the preservation
    of our environmer’t.
    18
    702

    —23—
    Two other factors, besides those which might normally
    be covered
    in
    a purely environmental consideration of the
    acceptability of higi~-temperaturethermal effluents to
    artificial cooling lakes, remain.
    The first is the need of
    the State of Illinois for the type of general recreational
    facility,
    (besides a game fishery), which has been provided
    at Lakes Sangchris and Springfield, and to a lesser extent
    at other artificia’. cooling impoundments in Illinois.
    Illinois has a serious deficit in recreational parkland for
    general use; this seems especially true of “water related”
    public land
    (eg.
    R.
    113,
    347,
    703;
    Ex.
    19).
    By providing
    multiple use areas,
    cooling lakes may thus provide a considerable
    public benefit to be weighed against any possible environmental
    harm.
    The multiple recreational uses which have accompanied
    present cooling impoundments are perhaps best shown at Lake
    Springfield.
    Testimony showed that Lake Springfield supports
    a viable fishery as well as public swimming areas,
    eight
    public parks, children’s
    zoo
    and botanical areas,
    a golf
    course,
    the Municipal Opera, a wildlife sanctuary,
    and
    boating and
    campi1’~’gareas
    (R.
    427,
    429,
    680).
    This listing
    is only partial; while this lake may not be typical of the
    uses to which an artificial cooling lake can or will be put,
    it may serve as an example of the types of
    uses
    possible.
    There was also testimony,
    (eg.,
    R.
    272,
    273),
    to the
    effect that there are multiple recreational uses, besides
    the excellent sport fishery, accompanying Lake Sangchris.
    The lake and park there provide a wildfowl refuge,
    as well
    as camping and general outdoor recreation areas
    The need for such multiple—use facilities in Illinois
    was brought out
    in the
    testimony of Dr. Wayne Rogers of the
    Illinois Departmth~.tof Conservation.
    Dr. Rogers testified
    on the beneficial qualities of these sites, and on the
    Department
    of’ Conservation’s need for such sites
    (R.
    674-
    713)
    Our finding in that artificialcooling lakes may provide
    a suitable recreaticn resource was not the result of
    a
    consensus on the record.
    Mssrs.
    Adarnczyk and Ginsler both
    stated that what is considered an acceptable recreational
    facility for some may in fact result from the destruction of
    the natural, unspoiled areas sought out by others
    (R.
    156,
    179).
    It was also pointed out that the use of an artificial
    cooling lake for recreational purposes is not always ideal,
    due to the presence of the steam-electric generating
    station
    for which the lake
    is constructed
    (R.
    696).
    18
    703

    —24—
    Besides those oublic and recreational uses,
    there
    remains a final aspect to be considered in relation to the
    construction of artificial cooling lakes.
    Principally from
    the testimony of Dr. Ackerman, Chief of the Illinois State
    Water Survey,
    it wosld appear that the impoundment of artificial
    cooling lakes may be an important measure
    in
    the husbandry
    of our natural water resources.
    While Illinois may be
    considered a “water rich”
    state, to the extent that it
    receives an abundance of rainfall and has many large rivers
    and other bodies of water,
    there are nonetheless many areas
    of the state that are effectively impoverished as regards
    available water
    (eq.,
    Ex.
    11,12,13).
    Many of the state’s
    streams are intermittent,
    and are dry much of the time.
    By
    impounding these streams, much of the water that would
    ordinarily be lost as runoff is retained and made available
    for public benefit.
    An excellent example is Lake Springfield, which provides
    a public water supply for the City of Springfield.
    The Lake
    was,
    in part, constructed to provide for this use
    (R.
    423).
    While not all artificial cooling lakes are
    or could be
    -
    used for that purpose, this
    is again evidence that condenser
    cooling,
    with effluent temperatures in excess of present
    standards,
    is not ~ncongruent with other beneficial uses.
    As was stated at th’~Springfield hearing of May 23,
    1975,
    it
    is conceivable that artificial cooling lakes might be used
    for irrigation,
    industry, or any other use of general benefit
    (R.
    340,
    349). The retention for beneficial use of waters
    which would otherwise be lost provides the Board with
    a
    factor which must be weighed
    in setting Regulations for
    environmental benefit.
    Discussion of this conservation of Illinois’ water
    resources would not be complete without again mentioning
    that cooling impoundments may be the least consumptive of
    the engineering alternatives available for steam—electric
    generating station cooling.
    Testimony indicated that,
    in
    addition to any other problems with cooling towers or canals,
    their excessive use of evaporation as the principal cooling
    mechanism is extremely water—consumptive
    (eg.,
    R.
    335,370;
    Ex.
    9;
    see also R.
    357)
    At a time wh&n Illinois
    is lacking in both public
    recreational areas and
    in a full use of its water resources,
    artificial cooling lakes have historically provided at least
    partial solutions to both problems.
    This is not to say
    that these factors are sufficient to override all environmental
    18—
    704

    —25—
    considerations.
    As was noted in the testimony of Dr. Rogers
    of the Department of Conservation,
    it would not necessarily
    be in the best interests of the state if all possible sites
    were developed for artificial cooling lakes.
    Further, the
    testimony of Mr.
    Adamczyk,
    Dr.
    Rogers, and Mr. Ginsler show
    that the types of recreational facilities provided by artificial
    cooling lakes may not always be the best use of available
    natural land.
    And
    there is the possibility that th~construction
    of an artificial cooling lake may eliminate the habitats of
    important indigenous wildlife and aquatic species
    Ceg.,
    R.
    446).
    The Board also remains concerned that the construction
    of such artificial cooling lakes may inundate excessive
    amounts of agricultural land.
    Again,
    these factors must
    be weighed on a case—by—case basis.
    But in light of the paucity of evidence demonstrating
    any actual net dai~ageto the environment from artificial
    cooling lakes, the multiple use of these lakes weighs heavily
    in favor of the adoption of these Regulations,
    and here led
    to the inclusion of the relevant portions of Rule 203(i) (10) (cc).
    This was also a consideration of the Board in adopting the
    specific thermal standard for Lake Clinton.
    GENERAL CONCLUSION
    In summary,
    the Board finds that the adoption of Regulations
    to allow for speci~icthermal standards for individual
    cooling lakes would be
    thoroughly justified.
    While the
    record has shown tnat there is not presently a full understanding
    of the environmental dynamics of lakes receiving large heat
    input,
    it nonetheless indicates that at present there
    is
    little or no indication of any significant damage.
    The record indicates that there is no question that
    excessive thermal inputs can be damaging to the aquatic
    environment of an artificial cooling lake.
    Each artificial
    cooling lake must be judged on its own merits.
    No individual
    factor can justify the complete de-regulation of these
    lakes, and no individual factor,
    (such as recreational use),
    can by itself provide the test of acceptability for an
    artificial cooling lake.
    We realize that the coverage of this regulation is
    narrow;
    it applies only to the thermal effluents from steam—
    electric generating plants.
    Since the testimony of Dr.
    Ackerman
    CR.
    353) po~ntedout that there are many other
    sources of heated water, we have considered the question of
    applying the regulation more generally.
    We are however limited
    to the facts before
    us;
    the evidence herein concerns only
    the types of impoundments discussed above.
    18
    705

    —26—
    We have therefore adopted a careful case-by-case approach
    to the situation.
    The accompanying regulation provides for
    an individual Regulatory proceeding to set specific thermal
    standards applicable to an individual artificial cooling
    lake.
    SPECIFIC STANDARDS:
    LAKE
    CLINTON AND
    LAKE
    SANGCHRIS
    In adopting these Regulations,
    the Board has decided
    that it would serve no purpose to require a further showing,
    for Illinois Power’s Lake Clinton, as would otherwise be
    required under the Regulations adopted here.
    Edison’s Lake
    Sangchris may not be treated similarly in arriving at a
    specific thermai standard.
    While the Board feels that the
    evidence present supports the adoption of a final specific
    standard for Clinton Lake,
    the same conclusion cannot be
    reached for Lake Sangchris. Our discussion of specific
    thermal
    standards for individual artificial cooling lakes
    has been limited to Lakes Clinton and Sangchris;
    although
    other lakes were mentioned in the record, the information on
    them was insufficient to warrant such discussion.
    For Lake Clinton,
    the Board has been presented with a
    specific thermal limitation proposal.
    The predictive modeling
    done for that lake
    is based on a maximum condenser cooling
    discharge of 960 F.,
    and specific, narrow operating conditions
    for
    a supplemental system to be used in conjunction with the
    lake for cooling purposes.
    For Lake Sangchris,
    however,
    the instant record nowhere
    reflects a proposed specific standard.
    Commonwealth Edison
    did not request such a standard until the public comment
    period following
    the
    final public hearing in Chicago on
    June 23,
    1975.
    In
    the record on Edison’s initial proposal,
    supra,
    its effect was shown as intended for general,
    as
    opposed to specific,
    (ie., Sangchris),
    applicability
    (R.
    124).
    As a result, the mass of evidence introduced with
    regard to Lake ~angchris, while supporting the general
    conclusions reached here,
    was insufficient to allow adoption
    of a specific standard for that Lake.

    —27—
    Further heaxing(s)
    on Lake Sarichris will, we feel,
    allow
    an opportunity for Edison to justify the higher specific
    standards which we are rejecting here.
    These higher standards
    are those requested in Edison’s comment-period submission,
    and may in fact be justifiable; but that justification does
    not exist in the present record.
    We have reached our decisions in both cases
    (Sangchris
    and Clinton) based on massive quantities of evidence submitted
    at the hearings held in Chicago and Springfield.
    It would
    serve no great purpose to require that Edison once again set
    out essentially the same data and testimony.
    We will therefore
    make provision for the incorporation of the record and
    findings here in a further hearing on Lake Sangchris.
    It is
    our hope that this will minimize duplication of effort, and
    still allow Edison a full opportunity to justify whatever
    numbers it feels would be appropriate as a specific thermal
    standard.
    The specific provisions regarding Lake Clinton will
    take effect upon proper submission to the Secretary of
    State.
    LAKE
    SANGCHRIS
    (DISCUSSION)
    Lake Sangchris has previously been before the Board,
    at
    which time the Board was impressed by the lack of environmental
    harm seen there.
    As was noted above,
    this Regulatory
    proceeding is itselZ a result of our prior consideration in
    PCB 73-248.
    When instituting this proceeding, however,
    Commonwealth Edison did not ask for a Regulation which would
    be specifically applicable to Lake Sangchris, but instead
    sought a change wh.ch would have exempted all artificial
    cooling lakes from the present standards,
    subject to certain
    conditions.
    The Board’s prior Opinion has not changed.
    Based on
    many of the same evidentiary matters presented in PCB 73-
    248,
    and on the wealth of further data seen here, we can
    impose a specific thermal standard for that lake,
    once
    one has been proposed and justified.
    That specific standard,
    n~o~d, will a~hi~7ethe result originally sought by
    Edison in this Regulatory proceeding, but will do so, we
    feel,
    in an environuentally and legally sound fashion. We
    find that the data present as regards Lake Sangchris cannot
    justify the imposition of a specific standard.

    —28—
    a.
    Background.
    Lake Sangchris was created between
    1964 and 1966 by the construction of an
    earthen dam across
    Clear Creek
    (Ex.
    6, p.3).
    By damming Clear Creek just
    below the confluence of its three branches,
    (approximately
    one mile upstream of the confluence of Clear Creek and the
    South Fork of the Sangamon River),
    a three-armed lake was
    created at a cost of about $30 million.
    The lake, with a
    surface of about 2,700 acres at a designed surface elevation
    of 580 feet, ha~a volume of approximately 10.7 billion
    gallons
    (R.15;
    Ex.
    6(D), p.iii).
    The Lake provides condenser cooling water for Edison’s
    Kincaid Station,
    a mine—mouth facility designed in the early
    1960’s to take advantage of the economies accompanying
    location near a fuel source
    (Ex.
    6, p.2;
    R.l4).
    Kincaid
    Station has two
    661
    MW units,
    and has a total condenser
    cooling discharge
    of
    2140 cfs when the station is run at
    full capacity. Normally,
    three pumps are used to provide the
    cooling water from the intake arm of Lake Sangchris,
    (the
    eastern of the three arms), and the effluent is discharged
    into the discharge
    (central)
    arm.
    (The station has four
    pumps to provide cooling water, but maintenance difficulties
    have kept one pump down for much of the station’s operating
    history, R.5l9.)
    The temperature of the effluent is dependent,
    among other things, on the temperature of the water withdrawn
    from the intake arm,
    (largely a function of the season)
    ,
    the
    level at which the plant is operating, and the
    number
    of
    pumps used
    (R.5l9:
    Ex.
    10;
    Ex.
    6(D), Table
    4—1, pp 55—60).
    The total site at Kincaid Station comprises approximately
    13,000 acres, including the lake
    (Ex.
    6,
    p.
    2).
    In February,
    1969, Edison conveyed about 2,300 of those acres
    to the
    Illinois Department of Conservation for the development of
    Lake Sangchris State Park
    (R.15).
    Since that time,
    considerable
    effort has been expended by the Department of Conservation
    to develop and operate a multi—purpose recreational site in
    conjunction with the park and lake
    (eg. R.272). Although the
    total of the actions take~9todevelop the site are too
    numerous to set our here,
    there is no question of the
    fact that Lake Sangchris is an excellent recreational asset
    and sport fishery ~eg., R.678,680), both widely and well
    used by Illinois residents
    (see also, R.232,252,268).
    19.
    See the discussion above regarding the multiple use and
    water conservation aspects of cooling lakes.
    18
    708

    —29—
    b.
    Biota.
    Much of the foregoing discussion of the
    effects of thermal discharges on the biota of artificial
    cooling lakes comes from data acquired at Lake Sangchris.
    The work done there by the Natural History Survey,
    the
    Department of Conservation and various private consultants
    for Commonwealth T~dison, (in particular the Limnological
    Survey prepared by Lirnnetics,
    Inc.), provides the Board with
    a broad base
    on
    which to reach a determination with regard
    to that Lake.
    The data and evidence show little if any harm
    from past operations at Lake Sangchris.
    Our discussion noted that game fish, at the top of the
    food chain,
    have fared well in Lake Sangchris.
    As also
    noted,
    this may be some indication of the overall “health”
    of a body of water.
    There have, however, been some anomalies
    noted in the fish population at Lake Sangchris,
    which require
    specific coverage.
    The Limnetics study, done in 1972,
    stated that gizzard shad,
    (the dominant fish in the lake at
    that time),
    showed poor condition with a low weight-to-
    length ratio
    (Ex.
    ‘5(D),
    pp. vi,
    120—125).
    It was also
    thought at that time that the channel catfish population was
    not reproducing, although this may be normal for an impoundment
    without a strong current
    (Ex.
    6(D), p.109).
    Although this problem with the gizzard shad was not
    fully discussed in the later Natural History studies,
    (Ex.
    6(1),
    p.
    4-5), the results of similar studies relating
    to the “coefficient of condition” seem to indicate that the
    weight-to-length ratio of fishes
    in Lake Sangchris may be
    more related to the local availability of food organisms
    than to water temperature
    (Ex.
    6 (I),
    p.
    4—8).
    Also, the
    problem of slow growth in certain fishes may be more than
    made up for by the numbers of individuals present in species,
    (R.686), where there is competition for limited food resources.
    This
    is not to say, however, that all questions relating
    to the fishery at Lake Sangchris have been answered.
    The
    Natural History studies have indicated that the bluegill
    population is stunted, possibly from thermal stress
    (R.483),
    and that carp may not be successfully reproducing
    (Ex.
    6(I),
    p.
    4—5;
    see also Ex.
    6,
    p.35,
    Ex.
    7, pp.
    4.3,
    4.4).
    While
    these questions and others need further study and examination,
    it has not been shown that the thermal input from Kincaid
    Station has produced any of these anomalies
    (eg.,
    R.707,
    testimony of Biologist Herndon, Department of Conservation).
    It may be that the problems which have been observed are all
    within the natural order of things
    (
    id.).

    —30—
    There have also been questions raised regarding the
    phytoplankton and zooplankton populations at Lake Sangchris.
    It was shown in the Limnetics 1972 study that there was a
    preponderance of the smaller species of both zoo- and phytoplankton
    (Ex.
    6(D),
    p.
    95).
    Although data for other Illinois lakes
    was not available for comparison, plankton from lakes
    in
    other parts of the country are larger
    (Id., p.86).
    This
    problem,
    however, may be more related to the selective
    feeding habits of gizzard shad than to condenser passage
    (Ex.
    6 CD),
    p.
    120)
    .
    The reduction in individual size
    is
    possibly a response, at least in part,
    to the warm water
    input from Kincaid Station
    (R.
    297).
    The earlier Limnetics study also showed a lack of
    benthos in certain areas of the Lake
    (Ex.
    6(D), p.122).
    This was attributed to oxygen deficits occurring in the
    Lake, since the major benthic organism found is very tolerant
    of low oxygen tensions
    in the water.
    The problem was attributed
    primarily to the deeper portions of the Lake.
    There
    is
    very little background data on the benthic populations
    typical of Illinois reservoirs
    CR. 501).
    Some testimony
    indicates that the population density and diversity are more
    dependent on the available substrate or habitats than on the
    water temperature
    (R.
    497—503). Later studies by the Natural
    History Survey indicate that the earlier pausity of benthos
    no longer exists, and that benthos are now “moderately
    abundant”
    in the Lake
    (R.
    298).
    Heat tolerant species are
    even found in the discharge canal
    CR.
    500).
    Other testimony indicates that the macrophyte distribution
    in Lake Sangchris is fairly normal
    (Ex.
    6(D),
    § 5.3.6), and
    that wildfowl patterns of usage are typical, both in terms
    of stay and distribution
    (R.
    305—306).
    c.
    Standards
    The evidence,
    then,
    has shown that an
    excellent fishery has been developed in Lake Sangchris,
    and
    that the fishery is extremely popular with area fishermen.
    This fact, and the record’s rather minute examination of the
    effects which the thermal effluents of Kincaid Station have
    had on the aquatic biota of the Lake,
    lead us to the conclusion
    that past operaticns of Kincaid Station, with the attendant
    thermal effluent, have probably not been environmentally
    harmful.
    However,
    two questions remain:
    1)
    Will future
    operations on Lake Sangchris be of the same nature as those
    in the past?;
    and
    2)
    What effluent temperatures at Lake
    Sangchris have produced these results?
    When these are
    answered, we may set
    a specific thermal standard for Lake
    Sangchris based on the operational history of the Station
    and the Lake.
    18
    —710

    —31—
    Cornmonwedlth Edison, in a letter to the Board dated
    July 10,
    1975..
    requested the following as the specific
    thermal standard for Lake Sangchris:
    The temperature of the condenser cooling discharge
    from Kincaid Station shall not exceed 107°F.except
    that for
    5
    of the hours in any 12 month period
    ending with any month during which time excursions
    shall be allowed up to a temperature not to exceed 122°F.
    This request was evidently based on an attachment to
    that letter, c~rnsistingof a letter to the Board from Mr.
    McCluskey of Commonwealth Edison.
    Tables attached to that
    letter indicate that the highest Delta—T experienced at
    Kincaid during the period September
    1,
    1973 through October
    31,
    1974,
    was 25°F. This Delta-T was reached with a generated
    load at the stat~.onof 1,029 Megawatts, with two of four
    cooling water cir.~ulatingpumps
    in operation.
    The letter
    goes on to extrapolate that with a full generation load of
    1286 megawatts the Delta—T could have been 31.2°F. Based
    apparently on that same data,
    the letter goes on to state
    that although the maximum discharge temperature recorded
    during that same period was 107°F.,the maximum that could
    have occurred, with two circulating pumps in operation, and
    the Station at maximum generating load, was 121,6°F.
    This request by Edison was simply not reasonable.
    First, other evidence has shown that it is unusual for there
    to be only two circulating pumps in operation
    (the station
    has four such pumps), and historically there have been three
    of them in operation to provide condenser cooling water
    (R.5l9).
    Second,
    other exhibits,
    (eg.
    Ex.
    6,
    § 316(a)
    demonstration, Tatle
    4)
    indicate that over the course of
    approximately 10 years of operation at Kincaid, the discharge
    temperature rarely even approached the numbers requested by
    Edison.
    Based on these facts, we have determined that Edison
    has requested a regulatory change based on a hypothetical,
    worst-case situation, which, based on the evidence in this
    proceeding, has never occurred.
    We therefore,
    after a
    further hearing, must arrive at a specific figure as the
    thermal standard for Lake Sangchris;
    or, alternatively,
    Edison must more fully justify the standard proposed.
    The letter cited above states that during the period of
    September 1,
    1973 through October 13,
    1974,
    there were 7,741
    observations made of the effluent temperature at Kincaid
    Station.
    During that time,
    the effluent temperatures cited
    exceeded 102°F.only 1.9
    of the time,
    and never exceeded or
    equalled 108°F.; 104°F.and 106°F.were equalled or exceeded
    only 0.2 and 0.1
    of the time, respectively.
    The temperature
    data in that letter are, however,
    incomplete.
    18—
    711

    —32—
    Table
    4 of Exhibit
    6,
    (the
    § 316(a) demonstration for
    Lake Sangchris),
    containing sparse data for the years 1966
    through 1974,
    (no figures are given for the period from
    November,
    1968 through August,
    1973),
    shows a maximum
    discharge temperature of 107°F.,with five weekly high
    temperature readings exceeding 100°F.
    Further, of approximately
    110 weekly high temperature figures given, only 28 exceeded
    90°F.,of which only
    7 readings were between 96°F.and
    100°F.
    Of the readings between 96°and 100°,three were
    96°F.,three were 97°F.,and one was 99°F. During this
    period,
    however,
    it appears that the plant was not operating
    at high levels.
    Also,
    it seems that these readings,
    (those
    taken from both the letter cited above and those shown in
    Ex.
    6), were the result of measurements made at the point of
    discharge into the plant’s discharge canal, rather than at
    the point of discharge into the Lake itself.
    (It is not
    clear where the readings contained in Mr. Mccluskey’s
    letter were taken.)
    Any standard which we may set for Lake Sangchris would
    be,
    in effect, the historic fact for that Lake.
    In the
    record before u~, the history
    is incomplete.
    While we have
    determined that serious damage to the biota has probably not
    occurred at Lake Sangchris, we cannot determine fully the
    discharge temperatures, and their historic limits, which
    have produced this result.
    SPECIFIC STANDARDS
    LAKE
    CLINTON
    (FINAL)
    The evidence presented with regard to Lake Clinton,
    which will be constructed along with the proposed Clinton
    Station,
    is larg’~1ytaken ~om
    the §316(a) demonstration
    presented to the
    us.
    EPA.~U Looking at the same evidence
    and data,
    the Board shall adopt into the instant Regulation
    the same thermal standard as has been tentatively adopted
    for Lake Clinton by the federal government pursuant to
    §316(a)
    of the
    FWPCA.
    Lake Clinton has also been rather thoroughly discussed
    by the Board in another previous matter,
    the Variance case
    of Illinois Power v.
    EPA, PCB 75-31, decided by the Board on
    July 31,
    1975.
    While some of the following discussion may
    20.
    §316(a)
    of the Federal Water Pollution Control Act
    Amendment of 1972, PL 92—500,
    33 U.S.C.
    §1326(a).
    18-.
    712

    —33—
    therefore be duplicative of that Opinion and Order, we feel
    that this
    is nonetheless necessary.
    The Board’s grant of a
    specific thermal standard for Lake Clinton is,
    in effect,
    fulfillment of the compliance plan which was accepted in
    connection with the grant of that Variance.
    To avoid some
    repetition, however, we specifically adopt that Opinion and
    Order into the record here.
    In addition
    to
    matters seen in the
    §
    316(a) demonstration
    and the earlier Variance, our decision regarding a specific
    standard for Clinton Lake is based on
    additional matters
    entered at the May 23,
    1975 hearing in Springfield and
    during the public comment period following the hearings.
    Introduced by both Illinois Power and the U.S.
    EPA, these
    matters are further evidence of acceptable conditions predicted
    for the Lake.
    The same grounds that led to our grant of the Variance
    in PCB 75-31 are those which lead us to adopt a specific
    96°F.standard for Lake Clinton, and to adopt the same
    technical conditions as those in the Variance.
    The supplemental cooling system chosen by Illinois
    Power for the Clinton Station is
    a spray canal system,
    utilizing 232 individual spray modules along the discharge
    canal running from the Station to the Lake.
    By using this
    system,
    it will be possible to meet a maximum discharge
    temperature of 96°F.
    This maximum, we find, will be sufficient
    to preserve and protect the biota of the lake.
    The proposed spray canal has been the subject of extensive
    modeling and planning.
    It has been conservatively engineered
    to meet “worse case” conditions,
    but nonetheless will not
    result
    in compliance with the general Board standards under
    those “worst case~’conditions, although the present standards
    will be met under many meteriological conditions.
    It was
    noted in the earlier Variance Opinion that there was some
    question as to whether there will in fact be violations of
    the present standards.
    We found that the estimates of
    violation in drought years were credible.
    We again find
    that to be the case.
    It should be noted that the predictive data for Lake
    Clinton is based on a rather thorough review of the literature
    with regard to thermal effects,
    and, importantly, on experience
    at Edison’s Lake Sangchris,
    as well as
    a study by the Biology
    Department of Southern Illinois University.
    Since predicted
    temperatures for Clinton will be within the range of experience
    at Lake Sangchris,
    the predicted temperature effects at Lake
    Clinton are amenable to verification from the record on Lake
    Sangchris.

    —34—
    In a letter to Illinois Power dated May
    9, 1975,
    the
    U.S. EPA Regioi1 V Administrator tentatively approved an
    alternate thermal standard for the proposed Lake Clinton.
    That tentative approval followed the submission,
    by Illinois
    Power, of voluminous data and predictions relevant to the
    proposed Lake.
    The original submission to U.S.
    EPA,
    October 10, 1974,
    was supplemented on February
    24,
    1975, and
    April 14, 1975.
    tn
    a letter dated May 16,
    1975,
    Illinois
    Power agreed to all the conditions specified by U.S.
    EPA.
    Without reiterating all of the Board’s findings in PCB
    75-31, the predictive data for the proposed Lake indicate
    that minimal,
    if any, damage will result at Lake Clinton
    from the thermal effluent. As with Lake Sangchris, Lake
    Clinton will provide considerable “refuge” area for the fish
    populations,
    so that fish will be able to effectively avoid
    the “worst—case” effects of the thermal discharge, as predicted
    above.
    Unquestionably,
    some minimal damage to the biota will
    occur.
    Entrainment will, partially as a result of the
    cooling water’s passage through the spray canal system, kill
    essentially all of the organisms entrained at certain times
    of the year.
    This will be especially true of the zooplankton
    brought in throegh the plant intake.
    However, populations
    will be reestablished downstream of the discharge due to the
    reproduction of organisms not carried through the plant.
    As was the case with Lake Sangchris,
    it is felt that
    any damage which may occur as a result of plant operation
    will be offset by the benefits to be gained.
    The thermal
    effluent may actually benefit the biota
    at times, although
    this would not occur
    in the normal course of events. This
    will take the
    foria of an additional growing period during
    the normally dormant winter months, and should affect
    almost all of the biota.
    In reaching these conclusions regarding the hiota, we
    have taken into consideration the same balancing factors
    used
    in our discussion of Lake Sangchris.
    The probable
    costs
    of alternate cooling,
    the loss of water resources and
    increased consumptive water use, the energy crisis, and many
    other factors entei here.
    These have all been covered in
    PCB 75-31,
    in the
    § 316(a) demonstration, or in our general
    discussion above, and do not require reiteration.
    There is one other important factor regarding the
    effect on the biota which we must mention here.
    Illinois
    Power has committed itself to take corrective action,
    if
    necessary,
    should biotic conditions in Lake Clinton differ
    18—
    714

    —35—
    from those predicted.
    This condition,
    also continued
    in effect from the Variance,
    is in keeping with the Board’s
    policy as stated in Rule 203 (i) (5)~that further study
    of thermal effects is needed, and that envirq~mental
    protections may be added as shown necessary.’~
    The
    corrective action envisioned here
    is not limited;
    if
    need be, we may require the backfitting of the station
    with additional cooling measures.
    In addition to the effects on the biota,
    the Variance
    Opinion in PCJ3 75-31 set out some of the available data
    on the costs of achieving compliance with the general
    thermal regulations for the proposed Clinton Station and
    Lake.
    That information appears,
    in part,
    in the
    preceeding sections of this Opinion concerned with the
    costs associated with various cooling technologies.
    Data
    on Lake Clinton is included there, along with available
    data on other existing or planned artificial cooling
    lakes.
    The following data from the Variance Opinion is
    repeated for convenience:
    Alternate Cooling System
    Cost
    (1) wet mechanical draft tower
    $48,300,000
    (2) wet natural draft tower
    71,952,000
    (3~ spray canal
    55,754,000
    (4) dry mechanical draft tower
    422,144,000
    (PCB 75—31, Opinion at 12).
    The costs shown above would be those associated with
    an “alternate” cooling system, that is,
    one which would
    not be used for cooling in conjunction with the proposed
    artificial cooling lake.
    The supplemental cooling
    system mandated in our grant of a specific thermal
    standard will,
    it is estimated, cost approximately
    $34.5 million, to include all capital, operating and
    maintenance costs over a 30—year life.
    21.
    This agreement,
    it
    is felt, will constitute a
    valid waiver of Illinois Power’s right to rely,
    if
    in fact any such right is determined to exist, on
    §316(c)
    of the FWPCA,
    supra.
    18
    715

    —36—
    THE
    REGULATION
    The Regulation adopted on August 14,
    1975, provides two
    major additions to the existing Regulations:
    1.
    A mechanism is adopted whereby the Board may,
    in a
    regulatory proceeding, promulgate a specific thermal standard,
    on a case—by-case basis,
    for artificial cooling lakes, using
    the standards set out in new Rule 203(i) (10);
    and,
    2.
    A specific thermal standard is adopted for Lake
    Clinton.
    The final form of the Regulation differs significant-
    ly from the proposa~submitted by Commonwealth Edison.
    Rather than totally
    2 exempting all artificial cooling lakes
    from the general standards, we afl~wfor the promulgation of
    new specific standards for individual lakes.
    Even the
    definition cf an artificial cooling lake offered by Edison
    has been changed.
    Similarly, changes have been made in each of the proposed
    drafts of this Pegulation which the Board has seen.
    There
    have been five major drafts of this Regulation:
    1)
    the
    original Edison proposal;
    2)
    the first Agency draft, published
    in Environmental Register No.
    104;
    3)
    the second Agency
    draft,
    (Ex.32);
    4)
    the Board’s proposed final draft, published
    in Register No.
    106; and,
    5)
    the final Regulation.
    In
    addition, the record contains further alternate subsections
    submitted by the Agency,
    as well as other suggestions received
    during the
    two
    public comment periods.23
    The Board also
    published two alternate subsections to the Regulation with
    the proposed final draft.
    To clarify our reasoning and intent in the final Regulation,
    we will examine both the final form of the Regulation,
    and
    our rationale i~iexcising and amending portions of earlier
    drafts.
    22.
    The “total” exemption here was partially limited
    by certain
    conditions
    in Edis~ri~s
    proposed Rule 957(a) (7);
    see the discussion
    following.
    23.
    The first
    public comment period followed the close of the
    hearings on June
    23,
    1975,
    and lasted through July
    10,
    1975.
    The
    second followed publication
    of the Board’s proposed final draft in
    Environmental Register
    No.
    106 and lasted until August
    12,
    1975.
    18
    716

    —37—
    Rule 104, Definitions.
    In its final form,
    the definition
    of an “artificial cooling lake”
    is designed to make clear
    the Regulations’
    limitation to those lakes created by the
    damming of existing streams.
    Previous cases have made it
    clear that these lakes are protected waters of the state,
    whether the dammed streams are intermittent or continuously
    flowing.
    cf.,
    PCB 73—248, PCB 73—384,
    supra.
    This definition
    does not char~geour determinations in those cases.
    The definition offered by Edison in the original
    proposal was dropped primarily because it attempted “definition
    in the negative.’~ By calling artificial cooling lakes those
    which are,
    “not.
    .
    .
    .
    treatment
    works”, the Board would have
    avoided answering the important preliminary issue of the
    Regulations’ coverage.
    The final pnrase of Edison’s definition was retained,
    as a further limitation to the Regulations’ applicability.
    It was suggested,
    (comment of Mr. Marder,
    Illinois Department
    of Business and Economic Development), that the definition
    of an artificial cooling lake be expanded beyond the scope
    of the prior proposals,
    to include impoundments used for any
    cooling purpose, whether or not associated with a steam-
    electric generating plant.
    This proposal was rejected
    because the record simply fails to indicate that conditions
    under any other situation would be the same.
    While it would
    indeed seem that,
    “heat is heat”, regardless of the source,
    significant questions remain unanswered regarding the
    effects of sub-lethal thermal effluents on other pollutants,
    and the effects of such other pollutants on the biota under
    such conditions.
    The record shows that this has not been a
    problem with steam-electric generating plants, but is silent
    on the issues for any other situation.
    Rule 203(i) (10).
    The first portion of subsection
    (10)
    is intended to make it clear that any exemption which might
    be granted from the general thermal water quality rules,
    in
    a specific thermal standard, will be limited to the specific
    circumstances and requirements set out in the following
    subsections.
    It is intended in this language that any such
    exemption be narrowly limited to thermal discharges into
    artificial cooling lakes.
    18
    717

    —38—
    The original subsection 203(i) (10),
    submitted by Edison,
    would have provided a general exemption for all artificial
    cooling lakes, and was deleted in its entirety.
    The record
    simply failed to support such a generalized proposal, even
    where the conditions set up in Edison’s proposed Rule 957(a) (7)
    might have been met.
    The record did show just the opposite:
    too—great a thermal load on an artificial cooling lake can
    cause extensive environmental damage.
    The parties,
    including
    Edison,
    seemed to realize that this proposal was not viable
    by the time of the second hearing on May 23,
    1975.
    By the
    third hearing on June
    23,
    1975,
    almost no mention was made
    of the original Edison proposal.
    Particularly from the
    testimony of Dr.
    Tranquilli and his associates at the Natural
    History Survey,
    it had become clear that the Board would
    have to examine each artificial cooling lake individually.
    The language eventually used in the Regulation for the first
    portion of Rule 203(i) (10) was taken from the first Agency
    draft, which first presented the concept of a case—by-case
    approach.
    Subsection
    (aa).
    In contrast to prior Board determina-
    tions,
    (see pp.
    2—4 supra,
    and cases cited), the new Regulations
    adopted in R75—2 allow limited thermal effluent dissipation
    in protected waters of the state, once it has been shown
    that no harm to the environment will result.
    Subsection
    (aa)
    limits this exception to the boundaries of the artificial
    cooling lake in question, and prohibits any interference
    with natural temperatures in any other waters.
    The language and concept for this section are taken
    from the first Agency draft.
    The same language remained
    through the second Agency draft, but was changed in the
    Board’s proposed final draft.
    That change, which would have
    required compliance with
    “all applicable” provisions of
    Chapter Three, was deleted, and the language of the first
    and second Agency drafts was reinserted;
    this was done to
    avoid the confusion which the changed language might have
    caused, and because the language suggested by the Agency was
    more limiting.
    Subsection
    (h~). This subsection was adopted from the
    first Agency proposal, and
    is intended by the Board
    to
    narrowly limit the scope of the Regulation.
    As was the case
    18
    718

    —39—
    with subsection
    (aa),
    subsection
    (bb) was changed in the
    Board’s proposed final draft but later returned in the final
    Regulation to its initial form.
    It was decided that because
    the Regulation as a whole is limited to thermal standards
    and effects,
    it might be unnecessarily confusing to make
    reference to all the standards contained in Chapter
    3 of the
    Regulations.
    This Regulation is limited by its own terms
    to
    thermal constituents,
    and need not refer to any other section
    of the Regulations.
    Subsection
    (cc).
    This subsection makes
    it clear that
    any attempt by a discharger to obtain
    a specific thermal
    standard must take the form of a Regulatory proceeding.
    It
    also acts in part as
    a procedural rule by showing that the
    burden is upon the applicant for a specific thermal standard
    to make the showing(s) required under the Regulation.
    By
    requiring a showing that the lake will be environmentally
    acceptable,
    and by setting out in subsections
    (cc) (1) and
    (cc) (2) certain minimal elements of such a showing,
    this
    subsection is intended to give an applicant guidance to
    allow adequate preparation for the required hearing(s), and
    to give guidance as to the burden which must be met.
    The general heading of environmental acceptability as
    the thrust for the required showing under this subsection
    is
    necessarily broad.
    The many factors which the Board must
    consider, under its mandate in the Act, prohibit more concise
    or narrow a general definition.
    It is hoped that subsections
    (cc) (1)
    and
    (cc) (2) will provide sufficient guidance, but
    the showing is specifically “not limited to” the considerations
    set out in those subsections.
    Subsection
    (cc) (1)
    lists those tests which the Board
    found most helpful in evaluating artificial cooling lakes
    generally,
    and in choosing a specific thermal standard for
    Lake Clinton.
    Under subsection
    (cc) (1),
    it is not absolutely
    required that there be a fishery,
    or that an artificial
    cooling lake provide recreational or any other uses except
    that for which it was designed.
    One public comment pointed
    out that factors besides generating plant operations might
    prohibit a recreation facility.24
    But it is nonetheless
    felt that by requiring such conditions in a lake we will
    have taken a significant step in protecting water quality.
    24. An example would be the prairie chicken sanctuary
    shown in CIPS’
    letter received August 11, 1975.
    18
    719

    —40—
    Qualitatively, while the end use of a
    body of water is
    indeed important,
    and may be weighed by the Board in the
    regulatory process,
    the Board is most concerned with assuring
    water quality sufficient to allow these
    (fishery and recrea-
    tional) and any other beneficial and ecologically-sound
    uses.
    We may not require that water be properly and beneficially
    used; we must require that it can be so used.
    In subsection
    (cc) (2), the Board recognizes two points:
    first, where it would
    in the judgement of the Board be
    economically reasonable and technically feasible to meet the
    general thermal water quality standards in Rules
    203(i) (1)—
    (4), there
    is no need for a specific thermal standard under
    this regulation;
    second,
    the Board is required under the Act
    to evaluate these economic and technical factors in arriving
    at its regulatory decisions.
    (It has been argued that we
    may not consider economics or technical factors in arriving
    at suitable thermal standards to protect the environment;
    this
    is not how we interpret the Act.)
    A further point follows from our consideration of the
    environmental, economic and technical aspects of setting
    thermal regulations for individual artificial cooling lakes:
    in balancing all of these factors to determine a specific
    thermal standard, the Board may well find that such a standard
    cannot be justified.
    A necessary corollary is that the
    Board might find that an artificial cooling lake incapable
    of meeting the ~‘eneralthermal standards of Rules
    203(i) (1)-
    (4)
    would not be environmentally acceptable, and that if the
    generating~Tantin question is to be built,
    some supplemental
    or other cooling mechanism must be provided,
    (e.g., Lake Clinton).
    We decline to give blanket approval to artificial cooling
    lakes at any thermal standard other than those designed for
    the general protection of the waters of the state,
    and
    contained in the general thermal water quality standards.
    As with other parts of the Regulation,
    the concept here
    came from the first and second Agency drafts.
    The first
    Agency draft of subsection
    (cc), set out on page
    6,
    supra,
    overemphasized the necessity of having an acceptable fishery
    and recreational
    facility.
    While the underlying thoughts of
    this section were retained,
    it was re—phrased to emphasize
    environmental effects generally,
    and require only “conditions
    capable of supporting” fishery and recreational uses.
    18
    720

    —41—
    The “conditions capable” concept was introduced in the
    second Agency draft, along with some of the language used
    in the final Regulation to include the economic and technical
    reasonableness tests.
    The “public hearing” phrase in the
    second Agency draft was changed to read,
    “regulatory hearing”,
    for clarity.
    The words,
    “so as to provide” in the second
    Agency draft were also dropped, as being unnecessarily
    self—limiting.
    One significant change from the Board’s proposed final
    draft
    to the final Regulation should also be discussed.
    Subsection
    (cc)
    in the Board’s proposed final draft would
    have required that “management” of an artificial cooling
    lake be performed in an environmentally acceptable manner.
    In the final Regulation,
    this was changed to reflect
    a
    requirement that the artificial cooling lake
    itself be
    environmentally acceptable.
    Many of the defects in the language of subsection
    (cc)
    in the two Agency drafts were also seen in the Board’s
    proposed final draft.
    Insofar as the Act sets a broad range
    of factors to be considered in regulatory proceedings, most
    of the language deleted or amended in subsection
    (cc)
    between the proposed final draft and the final Regulation
    itself was found to be improperly limiting future Board
    considerations of artificial cooling lakes; it was removed or
    changed to correct that deficiency.
    Subsection
    (dd).
    This section is provided in the
    Regulation to minimize the duplication of paperwork which
    might otherwise result.
    It is hoped that if presentation
    of similar facts and data before other agencies or regulatory
    bodies is required, the same materials used there may be
    used to satisfy the showing requirements of subsection
    (cc).
    The specific instances listed in that section are
    for general guidance, and it
    i.s expected that any appropriate
    reports or materials which address the requirements of
    subsection
    (cc) may be used.
    The language and idea in subsection
    (dd)
    of the final
    Regulation first appeared in the second Agency draft and
    were necessary additions.
    The changes subsequently made
    were for purposes of clarity.
    18
    721

    —42—
    Subsection
    (ee).
    This subsection is essentially
    procedural, and points out that an adequate showing under
    subsection
    (cc) must be made before any specific thermal
    standard will be promulgated by the Board.
    Similar language
    to that of subsection
    (ee)
    of the final Regulation first
    appeared in subsection
    (dd) of the first Agency proposal.
    In subsequent drafts,
    the word “alternate” was changed to
    reflect the difference between the specific thermal standards
    to be set under this Regulation,
    and an alternate thermal
    standard to be set pursuant to §316(a)
    of the FWPCA.
    As proposed in the second Agency draft,
    this subsection
    was simply too limiting.
    The language used there for
    (ee)
    would have required an “all or nothing” determination by
    the Board,
    in that it did now allow for the adoption of
    any specific thermal standard other than that requested by
    a discharger.
    The Board requires a greater flexibility
    in determining the proper thermal standard for an individual
    artificial cooling lake, and the language of subsection
    (ee) was changed accordingly.
    Other Subsections.
    Both the second Agency draft
    and the Board’s proposed final draft contained additional
    subsections to Rule 203 (i) (10),
    which were subsequently
    dropped in the final Regulation.
    A subsection
    (ff) was
    contained in both the second Agency draft and the Board’s
    proposed final draft, and the latter contained an additional
    subsection
    (gg).
    Subsection
    (ff)
    as contained in the second Agency draft
    would have led the Board to consideration of a
    “grandfather”
    clause,
    based on the existence of a Variance, before there
    was in fact any artificial cooling lake with an applicable
    Variance.
    The Agency apparently felt that this would be
    appropriate to deal with the case of Illinois Power’s Lake
    Clinton, which was then the subject of a pending Variance
    proceeding in PCB 75-31.
    (On July 31,
    1975, the Board did
    grant
    a two year Variance of
    “specific standards”
    for
    Lake Clinton.) While this was intended by the Agency to
    eliminate unnecessary duplication of effort by Illinois
    Power, the Board felt that the statutory requirements for
    Variances and those for regulatory amendments were not
    sufficiently similar to allow this as a “grandfather”
    vehicle.
    It was questionable whether,
    1)
    the public
    18
    722

    —43—
    hearing requirements for a Regulation could properly be
    fulfilled by the Variance hearings, and
    2) because a Variance
    is designed to grant temporary relief from the general rules,
    and is conditioned on efforts to achieve compliance with
    those general rules,
    it was not clear that temporary
    approval of a thermal effluent under those conditions would
    be legally sufficient to justify the permanent imposition
    of the same standard.
    In the Board’s proposed final draft, published on
    July 24,
    1975, we significantly changed the thrust of
    subsection
    (ff).
    Instead of granting an actual
    “grandfather”,
    the Board’s language provided that certain factors could
    amount to prima facie proof of compliance with the showing
    requirements of subsection
    (cc).
    The Board proposed this
    subsection to resolve the problems which the Board had
    seen with duplication of effort, and in part to recognize
    that the points considered by the U.S. EPA in a 316(a)
    determination approximate those which the Board might
    consider in reaching a specific thermal standard for an
    artificial cooling lake.
    Among
    other problems raised
    regarding this language,
    it was pointed out that this
    version of subsection
    (ff) might shift the burden in the
    regulatory proceedings envisioned in subsection
    (cc) away
    from the discharger and to any citizen objectors.
    The
    problem of re-delegation vis-a-vis the Board’s fact finding
    function under the Act was also a problem with this language.
    With its proposed final draft the Board also offered
    an alternate section
    (ff)
    in an attempt to deal with the
    problem of pre-emption as between federal law,
    (in §316 (a)),
    and applicable state
    law.
    By dropping subsections
    (ff)
    and
    (gg)
    in the final Regulation, we effectively eliminate
    any present case or controversy on the issue,
    so we need
    not discuss it here.
    In
    a public comment dated July 28,
    1975,
    the Agency
    submitted two further proposals for alternate language in
    subsection
    (ff).
    Again,
    the central issue in these proposals
    by the Agency was
    a
    “grandfather” for Lake Clinton, or
    any other artificial cooling lake which might achieve the
    same regulatory status.
    The Agency alternatives focused
    on the following facts:
    1.
    Lake Clinton had already been the subject of
    numerous public hearings and regulatory proceedings before
    public bodies,
    i.e.,
    the AEC and NRC.
    18
    723

    —44—
    2.
    Lake Clinton had already received tentative
    approval of an alternate th~rma1standard under
    §316 (a)
    of the
    FWPCA,
    from the U.S. Environmental Protection Agency.
    3.
    Lake Clinton was then before the Board in a
    Variance proceeding, PCB 75-31, wherein
    the
    Agency had already
    submitted a Recommendation that the Variance be granted,
    adopting essentially the same standards as those contained
    in the tentative §316(a)
    approval of U.S. EPA.
    It was the Agency’s contention that any discharger
    having met the burden already carried by Illinois Power for
    Lake Clinton should be entitled to a specific regulatory
    thermal standard without again being required to propose
    and defend the same standard.
    While the Board agrees that
    duplication of effort
    is to be avoided whenever possible,
    we cannot delegate our fact finding or regulatory functions
    to another agency, even where that agency’s requirements
    and goals are the same as those of the Board.
    While we may
    rely on the expertise of other agencies, we cannot redelegate
    our statutory powers to them.
    We may take steps to avoid
    unnecessary duplication only to the extent allowed by law.
    Although the Board did not adopt any of the language
    in subsection
    (ff),
    from any of the drafts, the same result
    for Lake Clinton was reached in new Rule 203 (1) (11) (aa).
    However,
    the determination to apply a specific thermal
    standard to Lake Clinton was based in part on the foregoing
    factors, but more importantly, also on the following
    additional fact:
    4.
    Illinois Power was a participant in the
    instant proceeding,
    and its Lake Clinton was therefore
    the subject of consideration in it.
    The Board was able
    to examine essentially all the materials in this proceeding
    which had previously been submitted to the AEC, NRC,
    U.S.
    EPA,
    and to this Board in the Variance case.
    The record in this
    proceeding was then replete with the substantive environmental
    showing which is the justification for a specific thermal
    standard for Lake Clinton.
    Subsection
    (gg) was subsequently dropped as unnecessary.
    Those factors which the Board must consider in any regulatory
    proceeding are presently set out in the Act.
    Unlike
    subsection
    (cc),
    it was not felt that additional guidance
    will be required in this regard.
    Specifically addressing
    18
    724

    —45—
    alternate subsection
    (gg) as published with the Board’s
    proposed final draft, we note that whether the requirements
    for a showing under subsection
    (cc) will affect our future
    determinations under Rule 410 (c), after assumption of
    NPDES authority, must be decided on a case—by—case basis.
    Nor did the final Regulation contain the proposed Rule
    957(a) (7)
    seen in Edison’s original draft.
    By requiring only
    a statement from the Illinois Department of Conservation
    concerning a lake’s recreational value, the Edison proposal
    completely ignored the need for any consideration of the
    overall environmental effect of an existing or proposed
    artificial cooling lake.
    As it has been noted, there may
    indeed be some relationship between the recreational value
    of a lake and its environmental soundness.
    The record notes
    that it is the existence of, or the conditions capable of
    supporting,
    fish at the top of the aquatic biota that is a
    significant binding fact in the relationship between recreation
    and environmental soundness.
    The section as proposed by
    Edison was therefore notably deficient.
    The recreational
    value of a lake
    is,
    however, one of many aspects to be
    considered by the Board in a Regulatory proceeding pertaining
    to an artificial cooling lake.
    Rule 203(i)(ll).
    This section was added
    to the final
    Regulation because,
    1) The Board had before it sufficient
    legal and factual grounds to set a specific thermal standard
    for Lake Clinton, and,
    2)
    it would serve no purpose,
    at yet
    another hearing,
    to once again examine the evidence on Lake
    Clinton, at further expense to both the discharger and the
    Board.
    Subsection 203(i) (11) (aa) (1).
    This subsection sets an
    absolute maximum thermal standard for Lake Clinton.
    This is
    the same maximum set by the Board in the Variance case,
    PCB
    75-31,
    and by U.S. EPA in its tentative §316(a) determination,
    and by NRC in its recommendation to U.S. EPA.
    The basis
    for this standard
    is
    fully set out in the Variance Opinion,
    and the evidence is again examined,
    in part,
    in the foregoing
    sections of this Opinion,
    (cf., Ex.l to comment
    c,
    Copy of
    letter from Illinois Power~. to U.S. EPA,
    dtd. April
    14,
    1975).
    18
    725

    —46—
    In summary, we have examined the possibility of
    ecological damage, and weighed this against the costs which
    would be required to comply with general Board thermal
    standards vis-a-vis alternate cooling methods at Clinton
    Station,
    and,
    the public benefits which will accrue from
    Clinton Station and Lake.
    Our findings are:
    1.
    ‘rhere remains a possibility of ecological harm
    in Lake Clinton; but the possibility is no more than that:
    a
    possibility.
    In the Board’s grant of a specific thermal
    standard
    it was
    a most important consideration that Illinois
    Power had committed itself to whatever corrective action
    may be necessary should such a possibility be realized.
    Further,
    the present record indicates an improbability of
    even minimal environmental damage, other than as noted in
    the Variance Opinion and the foregoing parts of this
    Opinion, under the conditions accompanying the imposition
    of the specific thermal standard for Lake Clinton.
    (These
    conditions are those taken from the Variance.)
    2.
    Clinton Station and Lake will provide
    considerable public and economic benefit to the immediate
    area and to the state as a whole.
    3.
    The costs
    to provide such cooling as would
    be required to meet the general thermal standards would be
    excessive,
    and in light of the foregoing a requirement
    that those standards be met cannot be justified by the
    record before us.
    Indeed,
    as we noted in the Variance Opinion, effluent
    temperatures at Lake Clinton will possibly not exceed the
    general thermal standards during most years under average
    meteriological conditions.
    But predictable and probable
    conditions
    in
    dry years will result in
    summer
    effluent
    temperatures approaching or equalling 96°F.
    Subsection 203(i)(l1)(aa)(2).
    This subsection
    specifically adopts into the Regulation conditions
    Ci)
    through
    (viii), which accompanied the Variance granted
    in PCB 75-31.
    While the principal grounds for our imposition
    of the specific thermal standard for Lake Clinton were our
    findings on the likelihood of environmental damage and the
    costs of requiring compliance with the general standards,
    the matters which are the subject of those conditions to the
    Variance provided additional factors which,
    under the Act,
    had
    to be weighed.
    These factors provided further weight
    in favor of imposing a specific thermal standard.
    18—
    726

    —47—
    The most important of these conditions, was Illinois
    Power’s
    commitment
    to
    take
    whatever
    measures
    are
    necessary
    to
    prevent
    further
    environmental
    damage
    should
    conditions
    as predicted in the S3l6(a) demonstration for Lake Clinton
    riot be achieved in the Lake.
    The condition is of sufficient
    importance to warrant its inclusion here:
    That if it is determined after operation of
    the first unit or by ongoing research,
    that
    conditions
    in
    Clinton
    Lake
    will
    be
    significantly
    different
    than
    has
    been
    described
    in
    the
    316(a)
    demonstration,
    or
    if it is determined
    that the cooling water use, recreational
    aspects
    of
    the
    lake,
    or
    that
    protection
    and
    propagation of indigenous aquatic life cannot
    be
    assured,
    Illinois
    Power
    Company
    shall
    take
    whatever
    measures
    are
    needed
    to
    correct
    the
    problem,
    including
    backfitting
    of
    the
    proposed
    or
    existing
    plant
    with
    additional
    cooling
    facilities.
    That condition is a total commitment in plain language
    to
    provide
    adequate
    protection
    of
    the
    aquatic
    environment
    and biota in the proposed
    Lake.
    It is in keeping with the
    Board’s previously stated intent in Rule 203(i) (5).
    Further,
    it is our opinion that this commitment by Illinois Power
    will act as an effective waiver of any right which the company
    might have under
    §1316(d)
    or §1326(d) of Title
    33, United
    States Code,
    or any other statutory language designed to
    prevent the imposition of more stringent standards at a
    future date.
    (FWPCA,
    §S306(d), 316(c).)
    That being the
    case, we are assured that protection of the environment will
    not be jeopardized by our action here.
    To a lesser degree,
    the remaining conditions also entered
    into our consideration of the specific thermal standard for
    Lake Clinton.
    These included a commitment by Illinois Power
    to provide start-up and shut-down procedures for the
    Station which will prevent
    “thermal shock”, which the instant
    record showed may prove damaging to aquatic life even when
    the upper and lower temperatures would not, by themselves,
    prove harmful.
    In addition, Illinois Power has agreed to
    submit operating plans for the
    Lake
    which will assure
    protection of its fishery and recreational value.
    This,
    in conjunction with a commitment to allow public access
    to the Lake,
    will provide a further and considerable public
    beneficial use of the Lake.
    18—
    727

    —48—
    Finally,
    ft should be noted that condition
    (i)
    of the
    Variance is
    in effect a part of the specific thermal standard
    which we have imposed.
    That condition is
    a requirement that
    Illinois Power operate a supplemental cooling system in
    conjunction with the lake itself, employing a minimum of
    232 spray modules along the 3.1 mile discharge canal from
    the Station’s two units to the Lake.
    The condition can be
    summarized as a requirement that the “spray canal”, more
    fully described in a earlier section of this Opinion, will
    be phased into operation each summer as ambient and discharge
    temperatures rise,
    to assure safe temperature levels in the
    Lake.
    If, even with this supplemental cooling system in
    operation, temperatures were to exceed the 96°absolute
    maximum specific thermal standard, Illinois Power must take
    whatever actions are necessary——including a cutback in
    generating operations--to remain within that maximum.
    I, Christan L. Moffett, Clerk of the Illinois Pollution
    Control Board, hereby certify that
    he above Opinion was
    adopted on the
    ~g1~
    day of
    _____________,
    1975, by a
    vote of
    _______
    to
    ________
    ChristanL. Mof
    t
    erk
    Illinois Pollutio
    ntrol Board
    18 —728

    Back to top